Plan Review Details - Permit 06070950
Plan Review Stops For Permit 06070950
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-15 Cont ID  
Sent By dpalmer Date 2006-08-15 Time 09:48 Rev Time 0.00
Received By dpalmer Date 2006-08-15 Time 09:48 Sent To PC
Notes
2006-08-15 00:00:00REDLINE DEQUIPMENT GRND.
 250.110,250.122

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 19:56 Sent To PC
Notes
2006-07-20 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE CLARIFY FEEDERS INTO
 EXISTING PANEL.
 PLEASE SEE RISER SHOWS 150A FEED TO THE
 NEW 100 MLO?
 240.4,240.21,310.16,215.5,
  
 2) NOTE: PLEASE SEE MISSING AIC RATING
 FOR NEW MAINS/ SERVICE EQUIPMENT.
 110.9/
  
 3) NOTE: PLEASE VERIFY AND SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANEL.
 250.110, 250.122,250.24B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 17:46 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 17:46 Sent To E
Notes
2006-08-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-20 Time   Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 16:10 Sent To  
Notes
2006-07-20 00:00:00TO "E" BOX