| Plan Review Stops For Permit 06070943 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-09-26 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-09-26 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-08 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-08-08 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | DENIED | | | | | | SHOW GENERATOR SLAB DETAIL AND METHOD OF | | | ATTACHMENT TO SLAB. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-28 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-28 |
Time |
18:26 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-17 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-17 |
Time |
08:57 |
Sent To |
B |
|
| Notes |
| 2006-09-17 00:00:00 | **** UNSAT 2ND REVIEW.*** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW AND NEW NOTE. | | | PLEASE SEE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM PREVIOUS REVIEW WITH NEW | | | NOTE ADDED AT THE BOTTOM. | | | | | | ********** UNSAT ************* | | | | | | 1) NOTE: NO/OK, RISER MENTIONS THE METER | | | MAIN FEEDS TWO MLO'S, YET THE 2ND RISER | | | FOR INSIDE EQUIPMENT SHOWS TWO MCB'S? | | | PLEASE CORRELATE. CALCULATIONS OK, | | | HOEVER SEE NEW NOTE. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE LABEL ALL PANELS AND | | | DISCONNECT ON PLANS. PLEASE CLARIFY | | | WHICH PANEL IS BEING FED WITH THE | | | GENERATOR AND PLEASE SUBMIT LOAD | | | CALCUALTIONS FOR THAT PANEL AND ALL | | | LOADS. PLEASE KNOW, ANY HEAT STRIPS IN | | | AHU'S SHALL BE FIGURED AT 100% UNLESS | | | LOADING SHEDDING IS PROVIDED. PLEASE | | | PROVIDE DETAIL IF THIS IS THE CASE. | | | PLEASE SEE LOADS AS SHOWN EXCEED RATING | | | OF THE GENERATOR. | | | PLEASE SEE NO PANEL SCHEDULES ARE | | | PROVIDED SHOWING THE NEW OCP ETC FOR NEW | | | EM SUB PANEL.?? | | | 220,702.5, 240.4,310.16,215.5 ETC | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: OK. | | | | | | 4) NOTE: OK. | | | | | | 5) NOTE: OK, SHOWN WITH 5' MIN ON ALL | | | SIDES. | | | | | | 6) NOTE: OK. | | | | | | 7) NOTE: NO, THIS IS THE SAME. ALL | | | SHEETS DONE BY THE CONTRACTOR. (NOT | | | MANUFACTURES) | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE KNOW ALL PLANS/DESIGNS | | | SHALL CONTAIN THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | SAID PLANS/DESIGN AND LOAD CALCULATIONS. | | | | | | | | | *** NEW NOTE *** | | | | | | 8) NOTE: PLEASE SUBMIT TWO COMPLETE SETS | | | MADE INTO SETS. PLEASE SEE LOOSE SHEETS | | | SUBMITTED AND PLEASE SEE ONLY ONE COPY | | | OF THE PANEL SCHEDULES/LOAD | | | CALCULATIONS, ONE COPY OF OTHER SHEETS | | | AS WELL. | | | MUST HAVE TWO SETS MIN. | | | FBC 106.1, 106.1.2 ADMIN SECT. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-27 |
Time |
20:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-27 |
Time |
20:01 |
Sent To |
M |
|
| Notes |
| 2006-07-27 00:00:00 | ********** UNSAT ************* | | | | | | 1) NOTE: PLEASE LABEL ALL PANELS AND | | | DISCONNECT ON PLANS. PLEASE CLARIFY | | | WHICH PANEL IS BEING FED WITH THE | | | GENERATOR AND PLEASE SUBMIT LOAD | | | CALCUALTIONS FOR THAT PANEL AND ALL | | | LOADS. PLEASE KNOW, ANY HEAT STRIPS IN | | | AHU'S SHALL BE FIGURED AT 100% UNLESS | | | LOADING SHEDDING IS PROVIDED. PLEASE | | | PROVIDE DETAIL IF THIS IS THE CASE. | | | PLEASE SEE LOADS AS SHOWN EXCEED RATING | | | OF THE GENERATOR. | | | PLEASE SEE NO PANEL SCHEDULES ARE | | | PROVIDED SHOWING THE NEW OCP ETC FOR NEW | | | EM SUB PANEL.?? | | | 220,702.5, 240.4,310.16,215.5 ETC | | | | | | 2) NOTE: PLEASE SEE FEEDERS FROM MAIN IS | | | NOT LARGE ENOUGH. PLEASE SEE | | | 310.16,240.4 FOR MIN SIZES. SHOWS #1 ON | | | 200A'S?? | | | | | | 3) NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS. | | | 250.24B,250.110,250.122 ETC | | | | | | 4) NOTE: PLEASE SEE RISER SHOWS A SE | | | RATED ATS AND SPECS SUBMITTED DO NOT | | | CORRELATE. | | | 110.3,90.7 | | | | | | 5) NOTE: PLEASE PROVIDE ALL MINIMUM | | | CLEARENCES FOR GEN. PLEASE PROVIDE MIN | | | CLEARENCES RECOMMENDED BY MANUFACTURE. | | | PLEASE KNOW, THIS OFFICE HAS OBTAINED | | | LTRS WHICH REQUIRES A MIN OF 5' FROM ALL | | | SURROUNDING FOR THIS TYPE OF UNIT. | | | 110.3, 90.7. | | | FBC 106.1.2 | | | | | | 6) NOTE: PLEASE SEE MISSING | | | DISCONNECTING MEANS FOR FEEDERS FROM GEN | | | AT HOUSE. 225.31-225.39. | | | THE DISCONNECTSHALL NOT REQUIRE OCP, | | | HOWEVER MUST BE GROUPED WITHEXISTING | | | MAINS AND RATED FOR THE LOAD SERVED. | | | ** BRKR ON GEN IS NOT ACCEPTABLE. | | | | | | 7) NOTE: PLEASE KNOW ALL PLANS/DESIGNS | | | SHALL CONTAIN THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | SAID PLANS/DESIGN AND LOAD CALCULATIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-08-01 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-01 |
Time |
11:17 |
Rev Time |
0.15 |
| Received By |
mperson |
Date |
2006-08-01 |
Time |
11:17 |
Sent To |
B |
|
| Notes |
| 2006-08-01 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL GEN/RES INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-28 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-28 |
Time |
13:55 |
Sent To |
E |
|
| Notes |
| 2006-09-28 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-08 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-08 |
Time |
10:22 |
Sent To |
E |
|
| Notes |
| 2006-09-08 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-27 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-27 |
Time |
18:02 |
Sent To |
E |
|
| Notes |
| 2006-07-27 00:00:00 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-08 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-20 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-28 |
Time |
15:28 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-07-28 |
Time |
15:28 |
Sent To |
P |
|
| Notes |
| 2006-07-28 00:00:00 | *** PROVISO *** | | | 1)PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | PROVIDE MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AT THE JOBSITE FOR THE | | | FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-07-23 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-23 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-23 |
Time |
14:29 |
Sent To |
I |
|
| Notes |
| 2006-07-23 00:00:00 | NOTE: | | | THE PROPOSED GENERATOR SHALL NOT BE | | | CLOSER THAN 4.7FT FROMREAR PROPERTY | | | LINE. |
|
|