Plan Review Details - Permit 06070943
Plan Review Stops For Permit 06070943
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 10:03 Rev Time 0.00
Received By alange Date 2006-09-26 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By alange Date 2006-08-08 Time 08:41 Rev Time 0.00
Received By alange Date 2006-08-08 Time 08:41 Sent To  
Notes
2006-08-08 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 18:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 08:57 Sent To B
Notes
2006-09-17 00:00:00**** UNSAT 2ND REVIEW.***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND NEW NOTE.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTE ADDED AT THE BOTTOM.
  
 ********** UNSAT *************
  
 1) NOTE: NO/OK, RISER MENTIONS THE METER
 MAIN FEEDS TWO MLO'S, YET THE 2ND RISER
 FOR INSIDE EQUIPMENT SHOWS TWO MCB'S?
 PLEASE CORRELATE. CALCULATIONS OK,
 HOEVER SEE NEW NOTE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE LABEL ALL PANELS AND
 DISCONNECT ON PLANS. PLEASE CLARIFY
 WHICH PANEL IS BEING FED WITH THE
 GENERATOR AND PLEASE SUBMIT LOAD
 CALCUALTIONS FOR THAT PANEL AND ALL
 LOADS. PLEASE KNOW, ANY HEAT STRIPS IN
 AHU'S SHALL BE FIGURED AT 100% UNLESS
 LOADING SHEDDING IS PROVIDED. PLEASE
 PROVIDE DETAIL IF THIS IS THE CASE.
 PLEASE SEE LOADS AS SHOWN EXCEED RATING
 OF THE GENERATOR.
 PLEASE SEE NO PANEL SCHEDULES ARE
 PROVIDED SHOWING THE NEW OCP ETC FOR NEW
 EM SUB PANEL.??
 220,702.5, 240.4,310.16,215.5 ETC
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK, SHOWN WITH 5' MIN ON ALL
 SIDES.
  
 6) NOTE: OK.
  
 7) NOTE: NO, THIS IS THE SAME. ALL
 SHEETS DONE BY THE CONTRACTOR. (NOT
 MANUFACTURES)
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW ALL PLANS/DESIGNS
 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SAID PLANS/DESIGN AND LOAD CALCULATIONS.
  
  
 *** NEW NOTE ***
  
 8) NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 MADE INTO SETS. PLEASE SEE LOOSE SHEETS
 SUBMITTED AND PLEASE SEE ONLY ONE COPY
 OF THE PANEL SCHEDULES/LOAD
 CALCULATIONS, ONE COPY OF OTHER SHEETS
 AS WELL.
 MUST HAVE TWO SETS MIN.
 FBC 106.1, 106.1.2 ADMIN SECT.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 20:01 Sent To M
Notes
2006-07-27 00:00:00********** UNSAT *************
  
 1) NOTE: PLEASE LABEL ALL PANELS AND
 DISCONNECT ON PLANS. PLEASE CLARIFY
 WHICH PANEL IS BEING FED WITH THE
 GENERATOR AND PLEASE SUBMIT LOAD
 CALCUALTIONS FOR THAT PANEL AND ALL
 LOADS. PLEASE KNOW, ANY HEAT STRIPS IN
 AHU'S SHALL BE FIGURED AT 100% UNLESS
 LOADING SHEDDING IS PROVIDED. PLEASE
 PROVIDE DETAIL IF THIS IS THE CASE.
 PLEASE SEE LOADS AS SHOWN EXCEED RATING
 OF THE GENERATOR.
 PLEASE SEE NO PANEL SCHEDULES ARE
 PROVIDED SHOWING THE NEW OCP ETC FOR NEW
 EM SUB PANEL.??
 220,702.5, 240.4,310.16,215.5 ETC
  
 2) NOTE: PLEASE SEE FEEDERS FROM MAIN IS
 NOT LARGE ENOUGH. PLEASE SEE
 310.16,240.4 FOR MIN SIZES. SHOWS #1 ON
 200A'S??
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.24B,250.110,250.122 ETC
  
 4) NOTE: PLEASE SEE RISER SHOWS A SE
 RATED ATS AND SPECS SUBMITTED DO NOT
 CORRELATE.
 110.3,90.7
  
 5) NOTE: PLEASE PROVIDE ALL MINIMUM
 CLEARENCES FOR GEN. PLEASE PROVIDE MIN
 CLEARENCES RECOMMENDED BY MANUFACTURE.
 PLEASE KNOW, THIS OFFICE HAS OBTAINED
 LTRS WHICH REQUIRES A MIN OF 5' FROM ALL
 SURROUNDING FOR THIS TYPE OF UNIT.
 110.3, 90.7.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE MISSING
 DISCONNECTING MEANS FOR FEEDERS FROM GEN
 AT HOUSE. 225.31-225.39.
 THE DISCONNECTSHALL NOT REQUIRE OCP,
 HOWEVER MUST BE GROUPED WITHEXISTING
 MAINS AND RATED FOR THE LOAD SERVED.
 ** BRKR ON GEN IS NOT ACCEPTABLE.
  
 7) NOTE: PLEASE KNOW ALL PLANS/DESIGNS
 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 SAID PLANS/DESIGN AND LOAD CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-01 Cont ID  
Sent By mperson Date 2006-08-01 Time 11:17 Rev Time 0.15
Received By mperson Date 2006-08-01 Time 11:17 Sent To B
Notes
2006-08-01 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-28 Cont ID  
Sent By adarroug Date 2006-09-28 Time 13:55 Rev Time 0.00
Received By adarroug Date 2006-09-28 Time 13:55 Sent To E
Notes
2006-09-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 10:22 Sent To E
Notes
2006-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 18:02 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 18:02 Sent To E
Notes
2006-07-27 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By alange Date 2006-08-08 Time 08:59 Rev Time 0.00
Received By alange Date 2006-07-20 Time 16:00 Sent To  
Notes
2006-07-20 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 15:28 Rev Time 0.15
Received By tgordon Date 2006-07-28 Time 15:28 Sent To P
Notes
2006-07-28 00:00:00*** PROVISO ***
 1)PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-23 Cont ID  
Sent By mmclean Date 2006-07-23 Time 14:29 Rev Time 0.00
Received By mmclean Date 2006-07-23 Time 14:29 Sent To I
Notes
2006-07-23 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 4.7FT FROMREAR PROPERTY
 LINE.


Account Summary | Usage Policy | Privacy Policy