Plan Review Details - Permit 06070941
Plan Review Stops For Permit 06070941
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-07-03 Cont ID  
Sent By jwitmer Date 2007-07-03 Time 10:42 Rev Time 3.33
Received By jwitmer Date 2007-07-03 Time 08:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-01-23 Cont ID  
Sent By jwitmer Date 2007-01-23 Time 11:27 Rev Time 2.22
Received By jwitmer Date 2007-01-23 Time 11:27 Sent To  
Notes
2007-01-23 11:31:24BUILDING PLAN REVIEW
 PERMIT: 06070941
 ADD: 1711 LONGWOOD DR
 CONT: SOUTH EAST GENERAL CONT.
 TEL: (561460-9697
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4A) SEMI -COMPLIED, THE NUCAR BUILDING PLANS NOW HAVE
 THE RIGHT
 MUNICIPALITY BUT BOTH SETS OF SEALED PLANS, THE
 SIGNATURE IS A COPY
 OR RUBBER STAMP SIGNATURE OF COREY D. NORRIS P. E.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGNPROFESSIONAL
 AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4B) THE STRUCTURAL DESIGN CALCULATIONS FOR THE NUCOR
 BUILDING
 SYSTEM BY JEFFERY P. BARKMAN, P. E. ONE SET HAS THE
 ORIGINAL SIGNATURE AND SEAL,
 THE OTHER SET THE SIGNATURE IS COPIED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) PRODUCT APPROVALS:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING DOORS - NOT REVIEWED BY THE DESIGNER OF
 RECORD
 B) OVERHEAD GARAGE DOORS- NOT A FLORIDA APPROVAL OR
 MIAMI-DADE REPORT.
 WILL REQUIRE ORIGINAL REPORT WITH ENGINEERS
 SIGNATURE AND SEAL, A THIRD PARTY
 QUALITY ASSURANCE PARTY APPROVED BY THE STATE.
 C) ROOFING ASSEMBLIES, NOT REVIEWED BY THE DESIGNER OF
 RECORD, ALSO THE STRESS ON THE PANELS WAS
 NOT
 HIGHLIGHTED AS REQUESTED IN THE MEETING WITH THE
 DESIGNER AND CONTRACTOR.
  
 10)THIRD REQUEST, W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11)3RD REQUEST, OVERHEAD DOOR,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12)COMPLIED.
  
 13) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-23 Cont ID  
Sent By jwitmer Date 2007-01-23 Time 11:25 Rev Time 2.22
Received By jwitmer Date 2007-01-23 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-02 Cont ID  
Sent By jwitmer Date 2006-11-02 Time 16:31 Rev Time 3.33
Received By jwitmer Date 2006-11-02 Time 16:31 Sent To  
Notes
2006-11-02 16:38:41FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
 NOTE THERE ARE (2) NOTICE OF COMMENCEMENTS
 SUBMITTED, ONEIS FOR A STRUCTURE IN DELRAY, PLEASE
 REMOVE.
 THE SECOND IS FOR THE SITE AND IT IS NULL AND VOID.
 WORK HAS TO HAVECOMMENCED WITHIN
 90 DAYS OF RECORDING, WILL NEED TO BE RE-RECORDED.
  
 3)PLEASE SEE ELECTRICAL NOTE # 7 ABOUT DRAFTING
 SERVICES WORKING IN CONJUCTION WITH DESIGN
 PROFESSIONALS.
 STATE OF FLORIDA DIVISION OF ADMINISTRATIVE HEARINGS
 CASE# 03-0489.
  
 4)NUCAR BUILDING PLANS ARE CPOIES PLANS WERE USED IN
 PALM BEACH GARDEN. SEE JOBSITE LOCATION.
  
 5) COMMENT 6A FROM THE PREVIOUS REVIEW.THE SURVEY
 PROVIDED IS A COPY AND NOT SIGNED NOR SEALED.
  
 6) COMMENT 6B FROM THE PREVIOUS REVIEW:
 6B) SHEET A/1 INDICATES THAT TWO
 BUILDINGS APPEAR TO BE TIED TOGETHER
 FORMING ONE LARGE STRUCTURE IS THIS
 CORRECT?
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 7) COMMENT FROM THE PREVIOUS REVIEW:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) SQ. FT. FOOTPRINT (TOTAL BUILDING)
 H) OCCUPANT LOAD
 I) FLOOD ZONE
 J) FLOOD ELEVATION
 K)L.O.M.R.
  
 8) SHEET A/1 OF DIAZ DRAWINGS,
 CORRECTIONS:
  
 8A) NOTE (2C) INDICATES PLANS ARE
 DESIGNED TO ASCE 7-98 SEE 1609 & CHAPTER
 35 REFRENCED STANDARDS ASCE7-02.
  
 8B) SOIL BEARING OF 2000PSF PLEASE
 PROVIDE SOILS REPORT.
  
 8C) NOTE 14 INDICATES AN EXTERIOR PORCH
 STUCCO CEILING? PLEASE INDICATE WHERE
 THIS CAN BE LOCATED.
  
 8D) NOTE 15 REFRENCES THE 2001 FBC AND
 PBC AMENDMENTS DELETE BOTH ONLY
 AMENDMENTS TO 2004 FBC ARE CHAPTER 1
 WHICH ARE ADMINISTRATIVE AND TO THAT
 JURISDICTION ONLY.
  
 8E) NOTE 16 AGAIN INDICATES PBC
 AMENDMENTS PLEASE DELETE TO COUNTY
 AMENDMENTS.
  
 8F) COMPLIED.
  
 9) PRODUCT APPROVALS:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING DOORS
 B) OVERHEAD GARAGE DOORS
 C) ROOFING ASSEMBLIES
  
 10) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12) E-1 INDICATES STOCK ROOM WHAT TYPE
 OF INVENTORY SHALL BE STORED? 106.1.2*
 WPB ADMINISTRATIVE CODE.301.1.
  
 13)THE PERMIT FEES ARE TO BE PAID IN FULL
 AT TIME OF APPLICATION, THE THIRD REVIEW WILL
 NOT TAKE PLACE UNTIL ALL FEES ARE PAID IN FULL. MORE
 COMMENTS MAY BE FORTH COMING WITH
 NEW AND OR ADDITIONAL INFORMATION ON
 FUTURE REVIEWS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By jwitmer Date 2006-08-09 Time 07:20 Rev Time 2.22
Received By jwitmer Date 2006-08-09 Time 07:18 Sent To  
Notes
2006-08-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070941
 ADD: 1711 LONGWOOD DR
 CONT: SOUTH EAST GENERAL CONT.
 TEL: (561460-9697
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
 NOTE THE NOTICE OF COMMENCEMENT
 SUBMITTED IS FOR A STRUCTURE IN DELRAY.
  
 3) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
 PLANS ARE COPIES OF A PROJECT THAT WAS
 LOCATED IN PALM BEACH GARDENS , PROJECT
 NAME DUNCAN, AQUA VAC.
  
 4)NUCAR BUILDING PLANS ARE COPIES SO ARE
 THE SIGNATURES:
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 6A) PROVIDE SURVEY THAT IS LEGIBLE.
  
 6B) SHEET A/1 INDICATES THAT TWO
 BUILDINGS APPEAR TO BE TIED TOGETHER
 FORMING ONE LARGE STRUCTURE IS THIS
 CORRECT?
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 7) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) SQ. FT. FOOTPRINT (TOTAL BUILDING)
 H) OCCUPANT LOAD
 I) FLOOD ZONE
 J) FLOOD ELEVATION
 K)L.O.M.R.
  
 8) SHEET A/1 OF DIAZ DRAWINGS,
 CORRECTIONS:
  
 8A) NOTE (2C) INDICATES PLANS ARE
 DESIGNED TO ASCE 7-98 SEE 1609 & CHAPTER
 35 REFRENCED STANDARDS ASCE7-02.
  
 8B) SOIL BEARING OF 2000PSF PLEASE
 PROVIDE SOILS REPORT.
  
 8C) NOTE 14 INDICATES AN EXTERIOR PORCH
 STUCCO CEILING? PLEASE INDICATE WHERE
 THIS CAN BE LOCATED.
  
 8D) NOTE 15 REFRENCES THE 2001 FBC AND
 PBC AMENDMENTS DELETE BOTH ONLY
 AMENDMENTS TO 2004 FBC ARE CHAPTER 1
 WHICH ARE ADMINISTRATIVE AND TO THAT
 JURISDICTION ONLY.
  
 8E) NOTE 16 AGAIN INDICATES PBC
 AMENDMENTS PLEASE DELETE TO COUNTY
 AMENDMENTS.
  
 8F) A/1 SCOPE OF WORK INDICATES THAT
 THERE IS AN APPARENT STRUCTURE AND JUST
 REPAIR OF BUILDING. THE PERMIT
 APPLICATION INDICATES "REPLACE" BUILDING
 AND THERE IS A DEMO PERMIT FOR A METAL
 BUILDING? PLEASE CLARIFY,CORRECT.
  
 9) PRODUCT APPROVALS:
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING DOORS
 B) OVERHEAD GARAGE DOORS
 C) ROOFING ASSEMBLIES
  
 10) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12) E-1 INDICATES STOCK ROOM WHAT TYPE
 OF INVENTORY SHALL BE STORED? 106.1.2*
 WPB ADMINISTRATIVE CODE.301.1.
  
 MORE COMMENTS MAY BE FORTH COMING WITH
 NEW AND OR ADDITIONAL INFORMATION ON
 FUTURE REVIEWS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By dpalmer Date 2007-01-22 Time 12:20 Rev Time 0.00
Received By dpalmer Date 2007-01-22 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 16:30 Sent To  
Notes
2006-10-15 16:47:46*** UNSAT2ND REVIEW ***
  
 PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW
 NOTES.
  
 1) NOTE:NO, ONLY ONE SET OF ELECTRICLA PLANS
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT TWO COMPLETE SETS
 MINIMUM (UP TO THREE MAY BE SUBMITTED).
 PLEASE SEE ONLY ONE SET OF ELECTRICAL ,
 ONLY ONE SHEET A/2, AND FOUR A/1'S. ONLY
 ONE LARGE ZONING SITE/SURVEY PLANS.
 PLEASE BE SURE TO ATTACH ALL SHEETS INTO
 EACH SET IN A NEAT AND ORDERLY FASHION.
 MANY OF THE SHEETS ARE SEPARATED ETC.
 FBC 106.1
  
 2) NOTE: OK, HOWEVER SEE NOTE ABOVE AND SEE NEW NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE ALL SETS CONTAIN
 AN ORIGINAL SIGNATURE, DATE AND SEAL BY
 ALL ENGINEERS AND DESIGNERS OF RECORD.
 PLEASE SEE BUILDING REVIEW COMMENTS TO
 FOLLOW AS THE "NUCOR" SETS CONTAIN A
 RAISED SEAL OVER A "PHOTO-COPIED"
 SIGNATURE FROM THE DESIGN PROFESSIONSL.
 PLEASE SEE STRUCTURAL DESIGN CALCS WHERE
 ONLY ONE SET CONTAINS AN ORIGINAL
 SIGNATURE..
 FS 471.025, FAC 61G15-23.002.
  
 3) NOTE: NO, STILL UNCLEAR AS NEW FOOTING ECT ARE BEING
 SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE THE ELECTRICAL
 WITH BUILDING AS THE BUILDING IS NEW YET
 THE ELECTRICAL PLANS HAS NOTES THAT THIS
 IS ALL EXISTING.?
  
 4) NOTE: NO, PLEASE SEE VALUE HAS NOT YET BEEN ADJUST.
 PLEASE KNOW, ONE WILL BE ASSESSED USING MARSHALL'S &
 SWIFT GUIDE AS ADOPTED UNDER THE FBC IF NOT ADJUSTED
 FOR COMPLETE SCOPE FOR ALL .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE APPLIED VALUE SHALL
 BE BASED ON ALL LABOR AND MATERIALS,
 EVEN IF ANY MATERIALS ARE OWNER
 SUPPLIED. PLEASE KNOW, A VALUE MAY BE
 ASSESSED BY THIS OFFICE. FBC 108.3
  
 5) NOTE:NO, SAME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE FOLLOWING
 CURRENT CODES ARE REFLECTED ON PLANS.
 PLEASE REF: 2002 NFPA-70, 2003 NFPA-101,
  
 PLEASE ALSO LIST THE 2004 FBC.
  
 6) NOTE:OK, AS THIS WAS NOT APPLICABLE.
  
 ** NEW NOTE **
  
 7) NOTE: PLEASE SEE FS 471.003 AND FS 481.229 AS A
 DRAFTING FIRM MAY NOT PROVIDE SIGNED AND SEALED
 DOCUMENTSFORARCHITECTURAL SERVICES OR ENGINEERING
 SERVICE WHEN WORK IS REQUIRED TO BE DONE BY THIS
 TRADES. PLEASE KNOW, UNLESS "EMPLOYED" BY THE ENGINEERS
 OF RECORD AS SHOWN. PLEASE BE SURE ALL REQUIRED SCOPE
 OF WORK AS MENTIONED ABOVE IS DONE BY THE ENGINEERS.
 WITH THEIR TITLE BLOCKS. ETC
 PLEASE CONTACT EITHER THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'SOR THE FLORIDA BOARD OF ARCHITECT'S LEGAL
 COUNSEL IF THERE ARE ANY QUESTIONS.
 THIS WAS NOT NOTED ON PREVIOUS REVIEW AS THIS HAS TO
 THE ATTENTION OF THIS OFFICE FROM THE STATE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 08:05 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 19:10 Sent To  
Notes
2006-08-07 00:00:00REVIEW IN PROGRESS
 *** UNSAT ***
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 MINIMUM (UP TO THREE MAY BE SUBMITTED).
 PLEASE SEE ONLY ONE SET OF ELECTRICAL ,
 ONLY ONE SHEET A/2, AND FOUR A/1'S. ONLY
 ONE LARGE ZONING SITE/SURVEY PLANS.
 PLEASE BE SURE TO ATTACH ALL SHEETS INTO
 EACH SET IN A NEAT AND ORDERLY FASHION.
 MANY OF THE SHEETS ARE SEPARATED ETC.
 FBC 106.1
  
 2) NOTE: PLEASE BE SURE ALL SETS CONTAIN
 AN ORIGINAL SIGNATURE, DATE AND SEAL BY
 ALL ENGINEERS AND DESIGNERS OF RECORD.
 PLEASE SEE BUILDING REVIEW COMMENTS TO
 FOLLOW AS THE "NUCOR" SETS CONTAIN A
 RAISED SEAL OVER A "PHOTO-COPIED"
 SIGNATURE FROM THE DESIGN PROFESSIONSL.
 PLEASE SEE STRUCTURAL DESIGN CALCS WHERE
 ONLY ONE SET CONTAINS AN ORIGINAL
 SIGNATURE..
 FS 471.025, FAC 61G15-23.002.
  
 3) NOTE: PLEASE CORRELATE THE ELECTRICAL
 WITH BUILDING AS THE BUILDING IS NEW YET
 THE ELECTRICAL PLANS HAS NOTES THAT THIS
 IS ALL EXISTING.?
  
 4) NOTE: PLEASE SEE APPLIED VALUE SHALL
 BE BASED ON ALL LABOR AND MATERIALS,
 EVEN IF ANY MATERIALS ARE OWNER
 SUPPLIED. PLEASE KNOW, A VALUE MAY BE
 ASSESSED BY THIS OFFICE. FBC 108.3
  
 5) NOTE: PLEASE BE SURE THE FOLLOWING
 CURRENT CODES ARE REFLECTED ON PLANS.
 PLEASE REF: 2002 NFPA-70, 2003 NFPA-101,
  
 PLEASE ALSO LIST THE 2004 FBC.
  
 6) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1,
 .1.2 AND .1.3 AS
 AUTOMATED SHUT OFF OF LIGHTING WILL BE
 REQUIRED AS THIS NEW STRUCTURE IS PART
 OF A BUILDING ALRGER THAN 5,000 SQ FT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-07 Cont ID  
Sent By mawillia Date 2007-02-07 Time 09:47 Rev Time 0.00
Received By mawillia Date 2007-02-07 Time 09:46 Sent To  
Notes
2007-02-07 09:49:27*****APPROVED*****
  
  
  
 SHEET E-1 WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-25 Cont ID  
Sent By mcarsill Date 2006-10-25 Time 08:12 Rev Time 0.00
Received By mcarsill Date 2006-10-25 Time 08:12 Sent To  
Notes
2006-10-25 08:18:051. PLANS DO NOT DECLARE TYPE OF STORAGE ANTICPATED. 2.
 PLANS OR INFORMATION PROVIDED DOES NOT INDICATE IF THE
 EXISTING BUILDING IS FIRE SPRINKLER PROTECTED. 3.
 PLEASE ILLUSTRATE EXIT DOOR LOCATIONS FOR THE EXISTING
 BUILDING.
 4. NO PORTABLE FIRE EXTINGUISHERS SHOWN WITH DRAWINGS.
 5. NO DOOR SCHEDULE OR HARDWARE SCHEDULE.
 6. PLEASE DECLARE EXISTING BUILDING CONSTRUCTION TYPE
 AND OCCUPANCY CLASSIFICATION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By mawillia Date 2006-09-14 Time 11:19 Rev Time 0.00
Received By mawillia Date 2006-09-14 Time 11:19 Sent To  
Notes
2006-09-14 00:00:00*****DENIED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONDERS ACCESS TO SAID
 PROPERTY OR PROPERTIES IN THE VICINITY.
  
 3.) EXITS TO REMAIN CLEAR AND
 UNOBSTUCTED.
  
 4.) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.) COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE 2004, 2004 EDITION.
  
 6.) PLEASE INDICATE/DISPLAY/SHOW
 LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE PROTECTION SYSTEM. HOW
 WILL THEY BE AFFECTED BY THE SCOPE OF
 WORK?
  
 7.) IF THE FIRE ALARM AND/OR SPRINKLER
 SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE
 OF WORK, SEPARATE SHOP DRAWINGS/PLANS
 AND PERMIT IS REQUIRED.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
 8.)

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By tadams Date 2006-07-18 Time 09:21 Rev Time 0.00
Received By tadams Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-29 Cont ID  
Sent By rbrown Date 2007-06-29 Time 16:02 Rev Time 0.00
Received By rbrown Date 2007-06-29 Time 16:02 Sent To  
Notes
2007-06-29 16:03:09TO JIM WITMER FOR BUILDING/STRUCTURAL REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-29 Cont ID  
Sent By rbrown Date 2007-06-29 Time 13:57 Rev Time 0.00
Received By rbrown Date 2007-06-29 Time 13:57 Sent To  
Notes
2007-06-29 14:05:08ZONING REVIEWER RETURNED PLANS TO CONSTRUCTION
 SERVICES.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-08 Time 08:45 Rev Time 0.00
Received By adarroug Date 2007-01-08 Time 08:45 Sent To  
Notes
2007-01-22 08:46:08TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-25 Cont ID  
Sent By adarroug Date 2006-09-25 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-09-25 Time 12:48 Sent To  
Notes
2007-01-09 18:52:09WAITING FOR "COMM" BD
2006-10-12 13:51:36TO "COMM" BD#28
2006-09-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-25 Cont ID  
Sent By adarroug Date 2006-09-14 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 09:17 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #2
2006-07-20 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By dpalmer Date 2007-01-22 Time 12:04 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2007-01-22 12:04:42NO MECH PLANS, NO MECH SCOPE, NO MECH CONTRACTOR.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By dpalmer Date 2007-01-22 Time 12:04 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2007-01-22 12:05:32NO PLUMBING PLANS, NO PLUMBING SCOPE, NO PLUMBING
 CONTRACTOR

Review Stop Z ZONING
Rev No 4 Status P Date 2007-06-29 Cont ID  
Sent By kdfreema Date 2007-06-29 Time 15:48 Rev Time 0.00
Received By kdfreema Date 2007-06-29 Time 15:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-01-26 Cont ID  
Sent By kdfreema Date 2007-01-26 Time 14:02 Rev Time 0.00
Received By kdfreema Date 2007-01-26 Time 14:02 Sent To  
Notes
2007-01-26 14:02:41**FAILED**
  
 AN INFORMAL SITE PLAN REVIEW IS REQUIRED FOR ADDITIONS
 IN EXCESS OF 1,000 SQUARE FEET.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 TO SCHEDULE A PRE-APPLICATION APPOINTMENT.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-27 Cont ID  
Sent By kdfreema Date 2006-10-27 Time 08:32 Rev Time 0.00
Received By kdfreema Date 2006-10-27 Time 08:32 Sent To  
Notes
2006-10-27 08:50:37A FULL-SIZE SURVEY COMPLETED WITHIN THE LAST YEAR IS
 REQUIRED, THE SUBMITTED SURVEY DATES FROM 1993.
  
 PLEASE SHOW THE SCOPE OF WORK ON THE FULL-SIZE SURVEY
 INCLUDING THE DISTANCE FROM THE NEW STRUCTURE TO ALL
 PROPERTY LINES.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT (561)
 822-1435 WITH ANY QUESTIONS YOU HAVE.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-14 Cont ID  
Sent By kdfreema Date 2006-08-14 Time 16:12 Rev Time 0.00
Received By kdfreema Date 2006-08-14 Time 16:12 Sent To  
Notes
2006-08-14 00:00:00SUBMISSION OF A SITE PLAN IS REQUIRED.