Plan Review Details - Permit 06070921
Plan Review Stops For Permit 06070921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-11 Cont ID  
Sent By alange Date 2006-10-11 Time 08:19 Rev Time 0.00
Received By alange Date 2006-10-11 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By alange Date 2006-09-07 Time 13:15 Rev Time 0.25
Received By alange Date 2006-09-07 Time 13:15 Sent To  
Notes
2006-09-07 00:00:00DENIED
  
 1.SHOW GENERATOR SLAB DETAIL AND
 METHOD OF ATTACHMENT TO SLAB.
  
 2.SEPERATE GENERATOR PERMIT REQUIRED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-02-20 Cont ID  
Sent By btrobaug Date 2007-02-20 Time 17:18 Rev Time 0.25
Received By btrobaug Date 2007-02-20 Time 17:11 Sent To PC
Notes
2007-02-20 17:18:17 
 NOTE: THE REVISION WAS NOT MARKED FOR AN ELECTRIC
 REVIEW, BUT THE PANEL SCHEDULE HAS CHANGED, PLEASE
 INDICATE IF A REVIEW OF SAME IS REQUESTED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By btrobaug Date 2006-09-29 Time 12:25 Rev Time 0.50
Received By btrobaug Date 2006-09-29 Time 12:25 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By btrobaug Date 2006-09-16 Time 16:07 Rev Time 1.00
Received By btrobaug Date 2006-08-16 Time 14:37 Sent To P
Notes
2006-09-05 00:00:00 
 NONCOMPLIANT
  
 1} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCESAND SPECIFICATIONS FOR THE
 GENERATOR.
  
 2} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 3) 702.8 SIGNS.(A) STANDBY. A SIGN SHALL
 BE PLACED AT THE SERVICE-ENTRANCE
 EQUIPMENT THAT INDICATES THE TYPE AND
 LOCATION OF ON-SITE OPTIONAL STANDBY
 POWER SOURCES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
2006-08-16 00:00:00 

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-07-24 Cont ID  
Sent By mperson Date 2007-07-24 Time 09:44 Rev Time 0.45
Received By mperson Date 2007-07-24 Time 09:26 Sent To PC
Notes
2007-07-24 09:51:54REVISION: AS BUILT INCLUDING EXISTING NAT/GAS SYSTEM
 AND NEW GENERATOR AND STOVE. CHANGED DELIVERY PRESSURE
 TO 2 PSI AND ADDED MP REGULATORS.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-05-15 Cont ID  
Sent By mperson Date 2007-05-15 Time 08:16 Rev Time 0.45
Received By mperson Date 2007-05-15 Time 08:16 Sent To PC
Notes
2007-05-15 08:51:11REVISION DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 NOTE: PLEASE BE AWARE THAT THIS IS A REVISION AND FEES
 ARE DUE ON THIS REVISION AND FEES WILL BE DUE ON THE
 RESUBMITTED REVISION AND THATFUTURE PLAN REVIEWS WILL
 NOT BE DONE UNTIL FEES ARE PAID:
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **OK**
  
 3. **OK**
  
 4. **OK**
  
 THE FOLLOWING ARE NEW CORRECTIONS REQUIRED ON THE
 RESUBMITTED REVISION FOR GAS PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 5. THE RESUBMITTED DRAWINGS NEED TO BE SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL OF RECORD LARRY M.
 SMITH, P.E. # 45997 WITH A TITLE BLOCK FROM SMITH
 ENGINEERING CONSULTANTS, INC. STATE AUTH. # 8228 THAT
 INCLUDES THE ADDRESS AND PHONE NUMBER PER CHAPTER 471,
 FLORIDA STATUTES.
  
 6. PLEASE CORRECT THE TOTAL DISTANCE ON THE
 RESUBMITTED REVISION AS 100'-6" AND DELETE THE TWO
 TOTAL DISTANCES OF 133' AND 138' ON THE RESUBMITTED
 REVISION.
  
 7. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 NOTE: PLEASE INDICATE THESE VALVES ON THE RESUBMITTED
 REVISION.
  
 8. PLEASE NOTE THAT THE SIZING 402.4(32) INDICATED ON
 THE REVISION IS WRONG BECAUSE IT IS FOR 2.0 PSI
 UNDILUTED PROPANE AND THIS GAS SYSTEM IS 2.0 PSI
 NATURAL GAS. THE CORRECT SIZING TABLES FOR THIS SYSTEM
 ARE 402.4(3) SCH 40, 402.4(17) CSST, AND 402.4(21) PE.
 ALSO PLEASE DELETE THE FOLLOWING "3/4" POLYETHYLENE
 PLASTIC PIPE LENGTH (FT) 100' MAX. CAPACITY 1,801,000
 BTUH" BECAUSE IT IS ALSO FOR 2.0 PSI UNDILUTED PROPANE
 AND THIS SYSTEM IS 2.0 PSI NATURAL GAS. PLEASE CORRECT
 AND RESUBMIT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-02-20 Cont ID  
Sent By mperson Date 2007-02-20 Time 13:59 Rev Time 0.45
Received By mperson Date 2007-02-20 Time 13:59 Sent To E
Notes
2007-02-20 14:54:42REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW FOR THE SUBMITTED REVISION:
  
 1. THE GENERATOR BTU LOAD OF 343,000 IS INDICATED
 WRONG ON SHEET E-5 ON THE REVISION, THE CORRECT
 GENERATOR BTU LOAD THAT IS APPROVED FOR THE PERMIT ON
 THE STANDBY GENERATOR OWNER'S MANUAL ON PAGE 6-1,AND
 PRINTS IS 380,000 BTU'S. PLEASE CORRECT AND RESUBMIT.
  
 2. THE MP REGULATOR OF 325-5AL INDICATED ON SHEET E-5
 FOR THE GENERATOR ON THE REVISION IS WRONG. THE CORRECT
 MP REGULATOR FOR THE GENERATOR IS A 325-7L. PLEASE
 REFERENCE THE SUBMITTED MAXITROL MANUFACTURER SHEETS,
 PAGE THREE (3) MAXIMUM INDIVIDUAL LOAD INDICATING THIS.
 PLEASE CORRECT AND RESUBMIT.
  
 3. THE MP REGULATOR OF 325-31 FOR THE STOVE ON SHEET
 E-5 IS WRONG ON THE REVISION. THE CORRECT MP REGULATOR
 FOR THE STOVE IS A 325-3L. PLEASE CORRECT AND
 RESUBMIT.
  
 4. SHEET E-5 GAS ISOMETRIC: PLEASE CLARIFY ON THE
 RESUBMITTED REVISION IF THE GAS PIPE INDICATED FOR THE
 STOVE IS UNDERGROUND OR IF IT IS IN A CRAWL SPACE. IF
 THE GAS PIPE IS UNDERGROUND A SLEEVE IS REQUIRED AND
 NEEDS TO BE INDICATED ON THE RESUBMITTED REVISION PER
 FBC-2004 FUEL GAS, SECTION 404.6 PIPING IN SOLID FLOORS
 AND SECTION 404.11 PIPING UNDERGROUND BENEATH BUILDINGS
 OR IF THE GAS PIPE IS IN A CRAWL SPACE PLEASE INDICATE
 THIS ON THE RESUBMITTED REVISION AND THAT THE PIPE WILL
 BE STRAPPED PER FBC-2004 FUEL GAS, SECTION 407.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-10-06 Cont ID  
Sent By mperson Date 2006-10-06 Time 08:24 Rev Time 0.33
Received By mperson Date 2006-10-06 Time 08:24 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-06 Cont ID  
Sent By mperson Date 2006-09-06 Time 08:59 Rev Time 0.33
Received By mperson Date 2006-09-06 Time 08:57 Sent To M
Notes
2006-09-06 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED ON
 THE ISOMETRIC DRAWING FOR GAS PLAN
 REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 PROPANE 10 PSI.
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 A) GENERATOR
 B) IF PRESSURE IS 2LB, REGULATOR
 8. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 9. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 10. FBC-2004 CHAPTER 1,SECTION
 106.3.4.2: THE PERSON RESPONSIBLE FOR
 THE DESIGN OF THE DRAWING SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-07-25 Cont ID  
Sent By swurafti Date 2006-07-25 Time 15:12 Rev Time 0.00
Received By swurafti Date 2006-07-25 Time 15:12 Sent To  
Notes
2006-07-25 00:00:00HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 10:56 Sent To P
Notes
2007-07-10 10:57:15TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 11:11 Sent To G
Notes
2007-05-08 11:11:43TO "G" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 08:35 Sent To P
Notes
2007-02-15 08:35:29TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 14:32 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 14:32 Sent To E
Notes
2006-09-20 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-14 Cont ID  
Sent By adarroug Date 2006-09-14 Time 15:48 Rev Time 0.00
Received By adarroug Date 2006-09-14 Time 15:48 Sent To Z
Notes
2006-09-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 17:39 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 17:38 Sent To E
Notes
2006-08-01 00:00:00SENT TO "E "GEN/RES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-07 Cont ID  
Sent By alange Date 2006-09-07 Time 13:17 Rev Time 0.00
Received By alange Date 2006-07-27 Time 11:59 Sent To  
Notes
2006-07-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By tgordon Date 2006-09-29 Time 16:21 Rev Time 0.20
Received By tgordon Date 2006-09-29 Time 16:21 Sent To P
Notes
2006-09-29 00:00:00RE-STAMP, CLEARANCES SHOWING ON PLANS
 COMPLY WITH REQUIREMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-06 Cont ID  
Sent By btrobaug Date 2006-08-16 Time 16:09 Rev Time 0.15
Received By tgordon Date 2006-09-06 Time 10:58 Sent To E
Notes
2006-09-06 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By btrobaug Date 2006-09-06 Time 17:18 Rev Time 0.00
Received By mperson Date 2006-09-06 Time 08:55 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By mmclean Date 2006-09-19 Time 18:14 Rev Time 0.00
Received By mmclean Date 2006-09-19 Time 18:14 Sent To I
Notes
2006-09-19 00:00:00APPROVING FOR GENERATOR ONLY

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-30 Cont ID  
Sent By mmclean Date 2006-07-30 Time 12:48 Rev Time 0.00
Received By mmclean Date 2006-07-30 Time 12:47 Sent To I
Notes
2006-07-30 00:00:00DENIED,
 1. THE PROPOSED SITEPLAN DOES NOT
 PROVIDE THE DIMENSION OF THE LOT AND
 SETBACKS OF THE EXISTING STRUCTURE.
 2. PLEASE SUBMIT TWO COPY OF SITEPLANS
 SHOWING THE SETBACKS OF THE EXISITNG
 STRUCTURE & DIMENSION OF LOT.
 3. PLEASE SUBMIT 1 COPY OF CURRENT
 SURVEY.
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved