Plan Review Details - Permit 06070917
Plan Review Stops For Permit 06070917
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By shill Date 2007-06-29 Time 17:13 Rev Time 0.00
Received By shill Date 2007-06-29 Time 11:34 Sent To  
Notes
2007-06-29 17:13:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)ADDRESSED.PLEASE KEEP THE STAMPED SHEET AND
 RECEIPT FOR IMPACT FEES IN THE PACKAGE.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 3-4.) ADDRESSED. PLEASE KEEP THE THRESHOLD INSPECTION
 PLAN (3 ORIGINALS, ONE WITH EACH SET) IN THE PACKAGE AS
 SUBMITTED.
  
 5.) PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 2ND REVIEW - THIS HAS NOT BEEN DONE.PLEASE BE ADVISED
 THAT THE PERMIT CANNOT BE ISSUED THE INSPECTOR AND THE
 INSPECTION PLAN HAS BEEN APPROVED BY HAROLD PISKURA.
  
 6-15.) ADDRESSED.
  
 16.)PARTIALLY ADDRESSED.ARCHITECT HAS ADDRESSED
 THIS COMMENT AND OTHERS BY PROPOSING TO INSTALL A WATER
 CURTAIN INSTALLED IN ACCORDANCE WITH NFPA13.THE
 SPRINKLER HEAD SPECIFICATIONS PROVIDED (UPON REVIEWER'S
 REQUEST, SUBMITTED VIA EMAIL BY KATHY VUYOVICK OF
 TOMAC) REQUIRE A NON-OPERABLE WINDOW.THIS SPEC CAN BE
 SEEN AT WWW.TYCO-FIRE.COM, SPRINKLER TFP620 AND ALSO
 THE SPEC IS ATTACHED.PLEASE NOTE THE FOLLOWING:
  
 A. A NON-OPERABLE WINDOW IS REQUIRED.OPERABLE WINDOWS
 ARE SHOWN ON THE PLAN.
  
 B. WINDOW SPRINKLERS ARE NOT LISTED TO PROTECT WINDOWS
 WHEN INTERMEDIATE HORIZONTAL MULLIONS ARE PRESENT. THIS
 WAS CONFIRMED WITH THE SPRINKLER COMPANY THAT THIS
 APPLIES TO APPLIED MUNTINS AS WELL AS STRUCTURAL
 MULLIONS OR WINDOW MEETING RAILS.SHEET S10 SHOWS
 HORIZONTAL MULLIONS ON ALL WINDOWS.
  
 C. S10, ELEVATIONS CONFLICT WITH FIRE SPRINKLER LAYOUT;
 MULTIPLE HEADS SHOWN PER WINDOW ON THE SPRINKLER PLANS,
 ONLY ONE HEAD SHOWN ON ELEVATIONS.
  
 D. FS2.1, THE WATER CURTAIN SPRINKLER HEADS ARE 3FT
 APART, 6FT DISTANCE REQUIRED UNLESS A MULLION CAN ACT
 AS A BAFFLE.PROVIDE A DETAIL SHOWING THAT THE
 PROPOSED MULLION WILL COMPLY WITH THE REQUIREMENT (FOR
 THE PENDANT VERTICAL SIDEWALL, EXTENDS TO THE BACK OF
 SPRINKLER DEFLECTOR OR, FOR THE HORIZONTAL SIDEWALL,
 MULLION EXTENDS TO THE SPRINKLER WRENCH FLAT).SEE
 PAGE 3 OF THE SPRINKLER SPECIFICATION.
  
 E. FS2.3, SPRINKLER HEADS ARE 4FT AND 5FT APART, NO
 MULLION; 6' DISTANCE REQUIRED.
  
 F. PAGE 3 OF SPRINKLER SPECS, MINIMUM CLEARANCE FROM
 FACE OF GLASS TO COMBUSTIBLE MATERIALS; SHOW COMPLIANCE
 ON THE PLAN AS TO HOW THIS WILL BE ENFORCED.
  
 G. FS2.1, THE WINDOW SPRINKLER HEADS ARE TO BE LOCATED
 A MINIMUM OF 6FT FROM STANDARD SPRINKLER HEADS.SEE
 NORTHWEST CORNER, NORTH SIDE.CHECK ALL.
  
 H. S10 AND ARCHITECTURAL SHEETS SHOW VERTICAL MULLIONS,
 NORTH AND SOUTH ELEVATIONS, WHICH ARE NOT SHOWN ON THE
 FS DRAWINGS.FS DRAWINGS ARE TO BE CONSISTENT IF A
 WATER CURTAIN IS USED.S10 AND ARCHITECTURAL SHEETS
 SHOW WATER CURTAIN SPRINKLER HEADS LOCATIONS ARE
 INCORRECT, SEE FS SHEETS.
  
 17.)PROVIDE CALCULATIONS FOR OPENINGS ALLOWED.I AM
 UNABLE TO DETERMINE HOW YOU?VE ARRIVED AT THE NUMBERS.
 FOR INSTANCE, EAST WALL 4TH AND 5TH FLOORS SHOW 8%
 OPENINGS.THIS WOULD REQUIRE A 625SF WALL BUT THE WALL
 IS APPROXIMATELY 47FT X 10FT.FLOOR/CEILING ASSEMBLIES
 SHOULD BE EXCLUDED FROM WALL AREA, AND THE OPENINGS
 SHOULD BE EQUALLY SPACED, SEE COMMENTARY SENT WITH
 FIRST REVIEW.
  
 A. SEE PREVIOUS LIST, SOUTH ELEVATION, NO OPENINGS
 ALLOWED.SEE FBC EB601.3, FBC TABLE 704.8.THE WATER
 CURTAIN DOES NOT WAIVE THIS LIMITATION.
  
 B. NORTH WALL IS LIMITED TO 25% OF OPENINGS FOR A FULLY
 SPRINKLERED BUILDING.SECOND FLOOR SHOWS 30%, A3.1A.
  
 C. WEST WALL, THE 4TH AND 5TH FLOORS
 APPEAR TO BE BE OVER 30FT FROM THE
 PROPERTY LINE (CENTERLINE OF OLIVE AVE),
 NO LIMITATIONS ON OPENINGS.THE 1ST
 THROUGH 3RD STORY WALL APPEARS TO BE
 APPROXIMATELY 26% OPENINGS, NO
 PROTECTION REQUIRED.
  
 D. EAST WALL, SEE OTHER COMMENTS.NOTE THAT 25%
 OPENINGS ALLOWED FOR FULLY SPRINKLERED BUILDING, FBC
 TABLE 704.8.
  
 18-22.) ADDRESSED.
  
 22.)PARAPET CONSTRUCTION IS TO COMPLY
 WITH FBC704.11.1.SHOW FIRE RESISTANCE
 FOR PARAPETS AS REQUIRED.
  
 2ND REVIEW, THIS WAS ADDRESSED IN THE RESPONSE LETTER,
 BUT WAS A NOTE PLACED ON THE PLAN REGARDING THE
 EXISTING CONDITIONS?IF IT WAS, PLEASE ADVISE AS TO
 HOW THE COMMENT WAS ADDRESSED ON THE PLAN, AND IF NOT,
 PLEASE NOTE ON THE PLAN.
  
 23.) ADDRESSED.
  
 24.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.THIS MUST BE DONE PRIOR TO PERMIT
 ISSUANCE.THIS MAY BE DONE WITH A SHOP DRAWING REVIEW
 STAMP, A LETTER, OR INCORPORATING THE INFORMATION INTO
 THE PLAN.
  
 25.)ALL PRODUCT APPROVALS REQUIRED PRIOR TO PERMIT
 ISSUANCE.
  
 26.)PRODUCT APPROVALS FOR THE LOUVERS, AND MECHANICAL
 STANDS
 WERE NOT SUBMITTED.
  
 THE DAYBAR DOOR PRODUCT APPROVALS ARE NOT PRINTED
 PROPERLY.THE DESIGN PRESSURES OF +-90 WAS CUT OFF.
 SEE THE SPEC SHEETS, INCOMPLETE.PLEASE PROVIDE A
 COMPLETE PRODUCT APPROVAL.
  
 27.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 WILL BE ISSUED USING THE NOA. WWW.FLORIDABUILDING.ORG
  
 NOT ADDRESSED.THIS IS REQUIRED.
  
 THE CGI 360 SINGLE HUNG WINDOW, SHEET 1 OF 6, USES A
 STRESS INCREASE WHICH IS NOT ALLOWED.IF A FLORIDA
 STATE PRODUCT APPROVAL IS NOT AVAILABLE FOR THIS
 PRODUCT, AND YOU WOULD LIKE A LOCAL PRODUCT APPROVAL TO
 BE ISSUED, PROVIDE THE LETTER WHICH THIS MANUFACTURER
 PROVIDED MIAMIDADE TO SHOW COMPLIANCE WITH FBC2004
 (CALCULATIONS WITHOUT THE STRESS INCREASE).
  
 PLEASE PROVIDE MORE INFORMATION IN REGARDS TO THE
 WINDOWS; CONFIGURATION OF WINDOWS WITH MULLIONS.IT IS
 NOT CLEAR FROM THE PLANS IF THE WINDOWS ARE SEPARATED
 BY MULLIONS OR IF THEY ARE APPLIED MUNTINS.
  
 28-30.) ADDRESSED.
  
 31.)FROM PREVIOUS LIST; REMOVABLE SHUTTERS ON THE
 FIRST
 FLOOR MUST BE APPROVED BY THE BUILDING
 OFFICIAL.THE NOTE HAS BEEN REVISED TO STATE THAT
 REMOVABLE SHUTTERS WILL BE USED ON THE FIRST FLOOR
 ONLY.SUBMIT PRODUCT APPROVALS, INSTALLATION SCHEDULE
 (ATTACHED) AND PRIOR TO RESUBMITTAL OF PLANS SUBMIT A
 HURRICANE SHUTTER INSTALLATION PLAN.THIS MUST BE
 APPROVED PRIOR TO PERMIT ISSUANCE.FAILURE TO ADDRESS
 THIS ITEM WILL RESULT IN PERMIT DELAYS.THIS IS NOT
 REQUIRED IF YOU ARE USING IMPACT GLASS ON THE FIRST
 FLOOR AS WELL AS OTHER FLOORS.
  
 32-33.) ADDRESSED.
  
 34.)TENANT BUILDOUTS ARE NOTED AS A
 SEPARATE PERMIT.THIS PERMIT WILL BE AN
 AT RISK PERMIT AS CODE COMPLIANCE FOR
 ALL FLOORS CANNOT BE DETERMINED.SHELL
 BUILDING ONLY.
  
 35.)PROVIDE DESIGN CRITERIA AND A
 DETAIL FOR THE GUARDRAILS ON THE
 BALCONIES (TWO TYPES) AND STAIRS,
 FBC1607.7, FBC1012.
  
 A3.1 DOES NOT SHOW THE OPENING SIZES AT THE BOTTOM AND
 SIDES.IT DOES NOT STATE DESIGN LOAD PER FBC1607.7.
 DESIGNER IS TO STATE DESIGN CRITERIA; SHOPS WILL FOLLOW
 THE DESIGN CRITERIA.12-A2.4, STATE DESIGN CRITERIA
 AND PROVIDE OPENING DIMENSIONS.PROVIDE STAIR GUARD
 DETAIL.S4 CITES A CODE SECTION FOR THE HANDRAIL.
 PLEASE PROVIDE A DETAIL AND STATE DESIGN CRITERIA
 FBC1607.7.
  
 36.)PARTITIONS AND PENETRATIONS ARE TO
 COMPLY WITH FBC1207, SOUND TRANSMISSION.
  
 THERE IS A NOTE STATING THAT THEY ARE TO COMPLY. PLEASE
 STATE DESIGN CRITERIA.
  
 37-39.) ADDRESSED.
  
 40.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1802.2.ORIGINALS REQUIRED (ORIGINAL
 SIGNATURE, PHOTOCOPIES SUBMITTED).
  
 41.)ADDRESSED.
  
 42.)VENTS ARE SHOWN ON THE PLAN, M2.1.
 SEE ABOVE COMMENTS IN REGARDS TO THE
 FIRE RATING OF THE WALL AND REQUIRED
 PROTECTED OPENINGS.THESE VENTS WERE
 NOT CALCULATED IN THE AMOUNT OF
 ALLOWABLE OPENINGS AS THEY ARE NOT SHOWN
 ON THE ELEVATIONS.PLEASE ADDRESS.
  
 2ND REVIEW, NOT ADDRESSED.THE VENTS ARE TO BE SHOWN
 ON THE ARCHITECTURAL DRAWINGS AND INCLUDED IN
 OPENINGS.
  
  
 43.)M5 REFERS TO FBC2001, GOVERNING
 CODE IS FBC2004.
  
 2ND REVIEW, WAS ADDRESSED IN ONE PLACE BUT M5.1 STILL
 STATES 2001.
  
 44.) ENERGY CALCS SHOW AREAS OF 305 AND 260 SF.
 CLARIFY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By shill Date 2006-08-24 Time 13:06 Rev Time 0.00
Received By shill Date 2006-08-23 Time 08:40 Sent To  
Notes
2006-08-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.561-233-5025 FOR MORE
 INFORMATION.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 3.)THIS IS A THRESHOLD BUILDING, "
 THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50
 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 4.) FBC*105.13.1 THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURALINSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 5.) PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 6.)THREE COPIES OF ALL DOCUMENTS
 REQUIRED (JOB, CITY, THRESHOLD
 INSPECTOR).
  
 7.)INCLUDE FBC EXISTING BUILDING CODE
 2004 IN PROJECT INFORMATION.ALSO
 DECLARE LEVEL OF ALTERATION FBC EB 3.
 THIS IS TO COMPLY WITH PROVISIONS FOR
 CHANGE OF OCCUPANCY, ADDITIONS, AND
 ALTERATION LEVEL 3.IS THIS A CHANGE OF
 OCCUPANCY FOR THE FIRST FLOOR, BUSINESS
 TO MERCANTILE?
  
 8.)FBC302.4, SPACES USED FOR DIFFERENT
 PURPOSES.YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE LIVE/WORK LOFTS,
 CORRECT OCCUPANCY CLASSIFICATION APPEARS
 TO BE BUSINESS AND R2, A0.1.
  
 9.)PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY (THREE REQUIRED).
  
 10.)RADON FEES HAVE BEEN ADDED,
 FS553.721.
  
 11.)A0.1 SHOWS 2 HOUR FLOOR
 CONSTRUCTION, SEE FBC601.IS THIS AN
 OCCUPANCY SEPARATION?PLEASE PROVIDE
 CALCULATED FIRE RESISTANCE OR LISTED
 ASSEMBLY FOR THE FLOOR.
  
 12.)FBC TABLE 602, 3 HOUR EXTERIOR
 WALL REQUIRED ON THE INTERIOR (SOUTH)
 SIDE ADJACENT TO THE EXISTING BUILDING,
 2 HOUR WALL ON THE NORTH AND EAST SIDES,
 1 HOUR ON THE WEST SIDE.PROVIDE
 DETAILS; CALCULATED FIRE RESISTANCE OR
 LISTED ASSEMBLY.FIRE RESISTANCE
 REQUIREMENTS ARE TO BE NOTED ON THE
 PLAN.
  
 13.)A0.1 STATES THAT THERE IS A 1 HOUR
 OCCUPANCY SEPARATION.SEE FBC302.3.1
 AND 302.3.2.OCCUPANCY SEPARATIONS IF
 REQUIRED ARE TO COMPLY WITH FBC TABLE
 302.3.2, 2 HOUR REQUIRED.IT APPEARS
 THAT YOU ARE REFERRING TO A 1 HOUR
 TENANT SEPARATION, FBC 708.1.
  
 14.)PROVIDE THE DISTANCE OF THE
 PROPOSED FOURTH AND FIFTH FLOORS FROM
 THE PROPERTY LINE ON THE SITE PLAN.
  
 15.)SHOW COMPLIANCE WITH FBC TABLE
 602.IT APPEARS THAT FIRE RESISTANCE
 FOR EXTERIOR WALLS IS REQUIRED AS
 FOLLOWS; NORTH 2 HOUR (MEASURED TO
 CENTERLINE OF THE ALLEY), SOUTH 3 HOUR,
 EAST 2 HOUR, WEST 1 HOUR.
  
 16.)PROVIDE DIMENSIONS FOR ALL
 OPENINGS.ESTIMATES FOR ALLOWABLE
 OPENINGS WERE DONE BY SCALING THE
 DRAWINGS.NOTE THAT IN SOME CASES A
 WIDTH WAS PROVIDED BUT NOT A HEIGHT.
 ALL DIMENSIONS ARE REQUIRED TO DETERMINE
 COMPLIANCE WITH FBC TABLE 704.8.
  
 17.)OPENINGS IN THE EXTERIOR WALLS ARE
 TO COMPLY WITH FBC TABLE 704.8.SEE
 ALSO FBC704.8.THE COMMENTS BELOW MAY
 CHANGE AS THE REVIEW WAS PERFORMED USING
 THE ELEVATIONS ON S10, BUT THIS DIFFERS
 FROM OTHER SHEETS.NOTE THE FOLLOWING:
  
 A.SOUTH ELEVATION SHOWS WINDOWS ON THE
 3RD THROUGH 5TH FLOORS, BUT NO OPENINGS
 ALLOWED FBC TABLE 704.8.THE SITE PLAN
 SHOWS THE 3RD FLOOR ON THE PROPERTY
 LINE, 4TH AND 5TH FLOORS 1FT FROM THE
 PROPERTY LINE.THE SITE PLAN CONFLICTS
 WITH THE FLOOR PLAN, WHICH SHOWS A
 PORTION OF THE 4TH AND 5TH FLOORS AS
 10FT FROM THE PROPERTY LINE.THE
 PORTION OF THE 4TH AND 5TH FLOORS WITH
 WINDOWS APPEARS TO HAVE 16% OPENINGS;
 LIMITED TO 10% UNPROTECTED OPENINGS, 25%
 PROTECTED.PROVIDE INFORMATION IN
 REGARDS TO THE EXISTING THIRD FLOOR
 WINDOWS, ARE THEY FIRE RATED?SEE FBC
 EB 501.2.
  
 B.NORTH WALL IS LIMITED TO 10%
 PROTECTED, 25% UNPROTECTED.THE FIRST
 THROUGH THIRD FLOORS HAVE APPROXIMATELY
 15% OPENINGS.THE FOURTH AND FIFTH
 FLOOR WINDOW AREA IS APPROXIMATELY 18%,
 SEE ATTACHED COMMENTARY IN REGARDS TO
 EXTERIOR OPENINGS EQUALLY SPACED.
  
 C.WEST WALL, THE 4TH AND 5TH FLOORS
 APPEAR TO BE BE OVER 30FT FROM THE
 PROPERTY LINE (CENTERLINE OF OLIVE AVE),
 NO LIMITATIONS ON OPENINGS.THE 1ST
 THROUGH 3RD STORY WALL APPEARS TO BE
 APPROXIMATELY 26% OPENINGS, NO
 PROTECTION REQUIRED.
  
 D.EAST WALL, MAIN BUILDING, REVIEWED
 AS 7.2 FEET FROM THE PROPERTY LINE AS
 SHOWN ON A0.1, 6% OF OPENINGS BASED ON
 S10 ELEVATION, APPEARS TO BE CODE
 COMPLIANT (10% UNPROTECTED OPENINGS
 ALLOWED).
  
 18.)THE PUMP ROOM IS NOT SHOWN ON THE
 SITE PLAN OR ON EAST ELEVATION S10.IT
 APPEARS TO BE 3 ? FEET FROM THE PROPERTY
 LINE.OPENINGS EXCEED THE 15% OF
 PROTECTED OPENINGS ALLOWED.2 HOUR
 EXTERIOR WALL REQUIRED, FBC TABLE 704.8.
  
 19.)THE EAST ELEVATIONS ON A3.2 AND
 S10 ARE NOT THE SAME.CHECK ALL
 ELEVATIONS FOR CONSISTENCY.ESTIMATES
 OF OPENINGS WAS DONE BASED ON ELEVATIONS
 SHOWN ON S10.IF THIS DIFFERS FROM
 OTHER PAGES IN THE PLAN, THE COMMENTS
 ABOVE MAY BE REVISED.
  
 20.)PROVIDE CALCULATED FIRE RESISTANCE
 OR APPROVED ASSEMBLY FOR ALL FIRE RATED
 WALLS.FIRE RESISTANCE IS TO BE NOTED
 ON THE PLAN.
  
 21.)SHOW ALL REQUIRED PROTECTED
 OPENINGS ON THE PLAN.ALL OPENING
 PROTECTIVES ARE TO COMPLY WITH FBC704,
 FBC TABLE 715.3.
  
 22.)PARAPET CONSTRUCTION IS TO COMPLY
 WITH FBC704.11.1.SHOW FIRE RESISTANCE
 FOR PARAPETS AS REQUIRED.
  
 23.)THE SITE PLAN SHOWS THE EAST WALL
 AS 7.2 FEET FROM THE PROPERTY LINE, S1
 SHOWS THIS AS AN EXISTING ALLEY.PLEASE
 CLARIFY.
  
 24.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 25.)ANY PRODUCT APPROVALS NOT
 SUBMITTED AND REVIEW PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 WITH SEPARATE FEES FOR THOSE ITEMS.
  
 26.)PRODUCT APPROVALS FOR THE OPAQUE
 DOORS, LOUVERS, AND MECHANICAL STANDS
 WERE NOT SUBMITTED.
  
 27.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE, PLEASE ADVISE AND A LOCAL
 WILL BE ISSUED USING THE NOA.
 WWW.FLORIDABUILDING.ORG
  
 28.)FOR THE ROOF PRODUCT APPROVAL,
 SELECT AN APPROVED ASSEMBLY.
  
 29.)MULLION NOA, CIRCLE THE
 APPLICATION FOR THIS JOB ON SHEET 5 OR
 6.NOT ALL ARE COMPLIANT.
  
 30.)THE MULLION PRODUCT APPROVAL
 STATES ON SHEET 1 OF 6 THAT WINDOWS MAY
 BE MULLED TO A MAX OF 5 UNITS, 6 SHOWN
 ON LEFT ELEVATION.IT IS NOT CLEAR; IS
 THERE A STRUCTURAL SEPARATION IN THE
 WINDOW BETWEEN FLOORS OR IS THIS ONE
 OPENING?
  
 31.)THE NOTE ON S10 STATES THAT
 OPENINGS ARE TO BE EITHER IMPACT
 RESISTANCE OR PROTECTED BY IMPACT
 PROTECTIVE SYSTEMS.OPENINGS ABOVE THE
 FIRST FLOOR ARE TO BE IMPACT RESISTANT
 ONLY.REMOVABLE SHUTTERS ON THE FIRST
 FLOOR MUST BE APPROVED BY THE BUILDING
 OFFICIAL.PLEASE REVISE THE NOTE.
  
 32.)OCCUPANT LOAD IS TO BE CALCULATED
 BY THE GREATEST NUMBER, FBC1004 (ROUND
 UP RATHER THAN ROUND DOWN, A0.1).
  
 33.)S7, DESIGN LOAD SCHEDULE, NET WIND
 UPLIFT IS BLANK.
  
 34.)TENANT BUILDOUTS ARE NOTED AS A
 SEPARATE PERMIT.THIS PERMIT WILL BE AN
 AT RISK PERMIT AS CODE COMPLIANCE FOR
 ALL FLOORS CANNOT BE DETERMINED.SHELL
 BUILDING ONLY.
  
 35.)PROVIDE DESIGN CRITERIA AND A
 DETAIL FOR THE GUARDRAILS ON THE
 BALCONIES (TWO TYPES) AND STAIRS,
 FBC1607.7, FBC1012.
  
 36.)PARTITIONS AND PENETRATIONS ARE TO
 COMPLY WITH FBC1207, SOUND TRANSMISSION.
  
  
 37.)SHOW ACCESSIBLE ENTRANCES,
 ACCESSIBLE ROUTE FOR THE RETAIL AREA AND
 FOR THE ELEVATOR LOBBY.PROVIDE
 ELEVATION CHANGE IF ANY.
  
 38.)PROVIDE EXIT DOOR WIDTHS, FBC1008.
  
 39.)THE ELEVATOR IS TO CONFORM WITH
 ASME 17.1, FBC3001.2.
  
 40.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1802.2.
  
 41.)ELEVATOR HOISTWAY VENTING
 REQUIRED, FBC3004.1, FBC3004.2.
  
 42.)VENTS ARE SHOWN ON THE PLAN, M2.1.
 SEE ABOVE COMMENTS IN REGARDS TO THE
 FIRE RATING OF THE WALL AND REQUIRED
 PROTECTED OPENINGS.THESE VENTS WERE
 NOT CALCULATED IN THE AMOUNT OF
 ALLOWABLE OPENINGS AS THEY ARE NOT SHOWN
 ON THE ELEVATIONS.PLEASE ADDRESS.
  
 43.)M5 REFERS TO FBC2001, GOVERNING
 CODE IS FBC2004.
  
 44.) ENERGY CALCS REQUIRED FOR
 CONDITINED SPACES AND FOR SHELL
 BUILDINGS. FBC13-101, FBC13-101.1.6.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-07 Cont ID  
Sent By dpalmer Date 2007-06-07 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2007-06-07 Time 07:52 Sent To  
Notes
2007-06-07 18:43:58*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED
 ON REVISED PLANS OR DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE THIS PERMIT WAS APPLIED FOR BEFORE
 THE NEW CODE CHANGE OF DECEMBER 8TH, 2006. PLEASE SEE
 THE VERSION SUBMITTED WENT INTO AFFECT ON THAT DATE.
 PLEASE SEE THE MISSING SIGNATURE FROM THE OWNER AGENT
 AS PRINTED ON SHEET 2.
 PLEASE SEE THE NUMBER OF FIXTURES, TYPE AND WATTAGE OF
 FIXTURES DOES NOT MATCH WITH PLANS.
 PLEASE SEE PLANS INDICATE AUTOMATED LIGHTING CONTROLS,
 YET CALCULATIONS INDICATE MANUAL ON/OFF. THIS IS NOT
 POSSIBLE WITH CONTROLS AS SHOWN.
 PLEASE SEE ROOMS WHICH ONLY STANDARD SWITCH(S) IS BEING
 SHOWN.
 PLEASE SEE NO EXTERIOR LIGHTING IS ENTERED ON
 CALCULATIONS.
 PLEASE CLARIFY THE LIGHTING AS SHOWN FOR MAXIMUM
 LIGHTING POWER DENSITIES.
 PLEASE SEE THE 2004 FBC W/ 2005 REVISIONS CHAPTER 13.
 13-415.1.ABC.1.1, .1.2, 13-415.1.AB1.1, 13-415.2
  
 2) NOTE: PLEASE SEE MISSING AN EMERGENCY BATTERY BACK
 UP FIXTURE IN THE ELEVATOR EQUIPMENT ROOM. THIS COMMENT
 WAS NOT PLACED ON PREVIOUS REVIEW HOWEVER IS REQUIRED.
 PLEASE INDICATE SOME OF BATTERY BACK UP FIXTURE.
 700.16, 700.12E, LS 101 7.8, 7.9
 AND STATE ELEVATOR CODE.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED
 PHOTO-METRICS FOR STAIRS UNDER NORMAL AND UNDER
 EMERGENCY. PLEASE SEE LEVELS UNDER EMERGENCY WERE THE
 ONLY ONES SUBMITTED. COULD NOT LOCATE LEVELS UNDER
 NORMAL. PLEASE SEE BOTH STAIRS ARE LABELED THE SAME.
 PLEASE SEE THE ONE STAIRWAY DOES NOT MEET THE MINIMUM
 LEVELS REQUIRED PER THE LIFE SAFETY CODE UNDER
 EMERGENCY CONDITIONS. PLEASE SEE AS NO NORMAL LIGHTING
 LEVELS WERE SUBMITTED, NO REVIEW OF THESE COULD BE DONE
 AT THIS TIME.
 LS 101 2003, 7.8.1.3, 7.9.2.2
  
 4) NOTE: PLEASE SEE POWER PLANS ARE STILL SHOWING
 PANELS ON EACH FLOOR, HOWEVER PLEASE SEE THESE ARE NOT
 IDENTIFIED OR ON ELECTRICAL RISER. IF THESE ARE
 "FUTURE" PLEASE INDICATE OR NOTE AS FUTURE. PLEASE
 INCLUDE ANY CONDUITS.
 PLEASE SEE THERE ARE MANY SHEETS SUBMITTED AS *POWER
 PLANS* YET THERE IS NO ACTUAL ELECTRICAL BEING SHOWN ON
 THESE SHEETS ?
 IF THESE ARE GOING TO BE INSTALLED AT THIS TIME, PLEASE
 LABEL AND COMPLETE RISER.
 215.5, 230,240, 310, ETC
 106.1.2 FBC
  
 5) NOTE: PLEASE SEE THE LABELING OF THE PANEL FOR HOUSE
 PANELS DO NOT CORRELATE WITH PLANS AND RISER. PLEASE
 SEE THE RISER WHICH CONTAINS A DIFFERENT DESIGNATION
 FOR EACH. PLEASE SEE THE HOUSE PANEL *HB* AS SHOWN ON
 SCHEDULE INDICATES THIS PANEL FEEDING *HA* WHICH RISER
 ACTUALLY HAS THIS REVERES AND LABELED AS LA AND LB
 PANELS.
 PLEASE SEE THE *HOUSE PANELS* ARE STILL BEING SHOWN IN
 WHAT IS SHOWN AS RETAIL TENANT SPACE WHICH IS NOT
 PERMITTED 240.24. (SEPARATE HOUSE ELECTRIC ROOM CAN BE
 CREATED, MOVE EQUIPMENT, OR SOME OTHER CHANGE)
 PLEASE SEE ALL CIRCUITING ON PLANS FOR EACH OF THESE
 PANELS CAN NOT CORRELATE AT THIS TIME FOR DESIGNATION
 AND EACH PANEL.
 PLEASE SEE THE LIGHTING CONTACTOR PANEL WHICH ALSO
 NEEDS COORDINATION FOR EACH AND CIRCUITING.
 PLEASE SEE 408.4, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE CLARIFY *NOTE #10 * ON THE ELEVATOR
 DISCONNECT AS THIS NOTE PERTAINS TO GROUNDING OF SORTS.
 THIS DOES NOT SEEM TO APPLY AT THIS LOCATION?
 FBC 106.1.2
  
 7) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTOR FROM THE MAIN DISCONNECT FOR HOUSE PANEL
 LAI.
 250.110, 250.122.
  
 8) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC RESPONSE MENTIONS TO SEE NOTE ON
 SHEET E6.1, HOWEVER NO NOTE COULD BE FOUND ON SHEET.
 PLEASE ADJUST.
  
 9) NOTE: PLEASE KNOW *ALLEY WAY* IS TO BE VERIFIED FOR
 VEHICLE TRAFFIC FOR SERVICE DROPS, AS THIS OFFICE HAS
 SEEN VEHICULAR TRAFFIC AND ANY HEIGHT WILL BE AT
 CONTRACTORS RISK AS UPON INSPECTION THIS MAY BE
 REQUIRED TO BE INCREASED IF NOT PREVIOUSLY NOTED ON
 PLANS.
 PLEASE PLACE A NOTE AT MINIMUM ON PLANS FOR 230.24
  
 10) NOTE: PLEASE SEE THE MAIN AIC RATING FOR MCA IS
 NOTED AS 65K, WILL THIS BE THE SAME FOR ALL TENANT
 BREAKERS AS SHOWN?
 110.9.
 FBC 106.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 19:10 Sent To  
Notes
2006-08-07 00:00:00REVIEW IN PROGRESS
 *** UNSAT ***
  
 1) NOTE: PLEASE HAVE PLANS REFERENCE THE
 FOLLOWING SPECIFIC CODES.
 2002 NFPA-70, 2002 NFPA-72 AND 2003
 NFPA-101.
 PLANS SHOULD ALREADY REFLECT THE 2004
 FBC.
  
 2) NOTE: PLEASE SEE MISSING LIGHTING
 REQUIRD FOR MECH RM. 210.70.
  
 3) NOTE: PLEASE SEE 110.26 AS MIN
 CLEARENCES FOR DISCONNECTS IN ELEV
 EQUIPMENT RM DO NOT SEEM TO MEET 110.26
 PLEASE SEE ALSO PLASN ARE SHOWING AN AHU
 IN ELEVATOR EQUIPMENT ROOM. PLEASE SEE
 STATE ELEVATOR CODE FOR EQUIPMENT OTHER
 THAN ELEVATOR EQUIPMENT PERMITTED IN THE
 ELEV EQUIPMENT ROOM.
  
 4) NOTE: PLEASE CLARIFY ELEVATOR LOBBY
 DOES NOT SEEM TO INDICATE AN EM BACK UP
 LIGHTING FOR EGRESS.
 LS 101 7.8,7.9
  
 5) NOTE: PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR STAIR-TOWERS. PLEASE
 SEE UNDER THE 2003 LS 101 7.8.1.3,
 REQUIRES A MIN OF 10FT CANDLES ON NORMAL
 AND IS PERMITTED DOWN TO 1FT CANDLE
 UNDER EM POWER.
 IF BOTH STAIRS ARE THE SAME , A TYPICAL
 DETAIL MAY BE SHOWN.
  
 6) NOTE: PLEASE SEE PLANS ARE SHOWING
 PANELS ON EACH FLR , HOWEVER PLEASE SEE
 THESE ARE NOT IDENTIFIED OR ON
 ELECTRICAL RISER. IF THESE ARE "FUTURE"
 PLEASE INDICATE OR NOTE AS FUTURE>
 IF THESE ARE GOING TO BE INSTALLED AT
 THIS TIME, PLEASE LABEL AND COMPLETE
 RISER.
 106.1.2 FBC
  
 7) NOTE: PLEASE SEE FBC 2004 CHAPTER 13
 FOR MIN LIGHTING CONTROLS REQUIRED FOR
 EACH FLR. PLEASE SEE EACH DEVICE SHOULD
 BE NOTED FOR TIME OF OVER RIDE ETC
 THE LIGHTING MUST BE ABLVE TO BE
 OVERRIDIN WHERE EGRESS INTO SPACE IS
 LOCATED.
 30MINS MAX FOR OCCUPANCY SENSORS TYPES,A
 ND 4 HRS MAX FOR TIMER TYPES.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2,
 .1.3
  
 8) NOTE: PLEASE VERIFY THE HEIGHT
 REQUIRED ON RISER AS THIS AREA BEHIND
 BUILDING (EAST ELEV) MAY BE SUBJECT TO
 VEHICULAR TRAFFICE WHICH WOULD REQUIRE
 RISER TO BE INSTALL HIGH ON EAST WALL.
 THIS IS BROUGHT UP AT THIS TIME AS THE
 MINIMUM CLEARENCES FROM WINDOW OPENINGS
 WILL NEED TO BE CHECKED FOR MIN CLEARENCES.230.24B,
 230.9
  
 9) NOTE: PLEASE SEE PLANS DO NOT
 INDICATE RISER ON THE OUTSIDE OF THE
 BUILDING FOR HOUSE SERVICE. PLEASE ALSO
 KNOW, THE HOUSE SERVICE MAY NOT BE
 LOCATED INSIDE ANY TENANT SPACE OR
 FUTURE TENANT SPACE. PLEASE SEE MAINS
 SHALL BE GROUPED ETC.
 210.25, 230.72,
  
 10) NOTE: PLEASE SEE PLANS NOTE TO
 CONNECT NEW SERVICE GROUNDING ELECTRODE
 CONDUCTOR TO FOOTER STEEL. PLEASE KNOW
 IF THIS WERE A NEW BUILDING, THIS WOULD
 CERTAINLY BE REQUIRED, HOWEVER PLEASE
 KNOW AS THIS BUILDING IS VERY OLD IT MAY
 NOT EVEN CONTAIN STRUCTURAL FOOTER
 STEEL. PLEASE KNOW, CONNECTION TO THE
 FOOTER STEEL WOULD JEOPARDIZE THE
 STRUCTURAL INTEGRITY OF THE EXISITING
 BUILDING AND THERFORE IT IS NOT
 RECOMMENDED, HOWEVER MAY BE DONE. IF
 SHOWN ON PLANS, THIS WILL BE REQUIRED.
 PLEASE KNOW, IF NOT, PLEASE PROVIDE A
 MIN OF 2-GRND RODS.
 250.50,250.56 ETC
  
 11) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%. 215.3,230.42 ETC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 11:10 Sent To  
Notes
2007-07-02 11:19:29***DENIED***
  
 PLEASE NOTE THAT MOST OF THE PREVIOUS FIRE REVIEW
 COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE THE
 FOLLOWING:
  
 1) COMMENT ACKNOWLEDGED HOWEVER PLEASE INDICATE
 LOCATION OF EXTINGUISHERS ON DRAWINGS.
  
 2) OK
  
 3) OK MORE DETAILS REGARDING THE DOUBLE DETCTOR CHECK
 ASSEMBLY WILL BE REQUIRED WITH FIRE SPRINKLER
 SUBMITTAL.
  
 4) OK
  
 5) PLEASE NOTE THAT THE ADOPTED EDITION FOR FIRE PUMPS
 IS 2003. PLANS STILL SHOW 1999.
  
 6) OK
  
 7) OK ADDED
  
 8) OK NEW FIRE DEPARTMENTS CONNECTIONS SHALL HAVE KNOX
 LOCKING CAPS.
  
 9) OK
  
 10) OK
  
 11) OK
  
 12) ACCESSIBLE ENTRY IS CALLED OUT. PLEASE VERIFY IF
 THIS IS A KNOX BOX USING CITY OF WEST PALM BEACH
 STANDARD.
  
 13) OK
  
 14) OK
  
 15) OK
  
 16) OK
  
 PLEASE SEE BUILDING REVIEW COMMENTS REGARDING WATER
 CURTAIN SPRINKLER REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2006-08-31 Time 15:30 Sent To  
Notes
2006-08-31 00:00:00***DENIED***
  
 1) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHERS THAT SHALL BE
 MOUNTED NOT TO EXCEED 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 2) ELEVATOR TO COMPLY WITH ASME A17.1.
  
 3) DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 BE SECURED WITH CHAIN AND LOCK IN
 ADDITION TO ELECTRONIC SUPERVISION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS. PLEASE INCLUDE
 CALCULATION AND MANUFACTURER SPEC
 SHEETS.
  
 5) FIRE PUMP TO COMPLY WITH NFPA 20,
 2003 EDITION UNLESS EXISTING WITH NO
 UPGRADES.
  
 6) STANDPIPES CONNECTIONS SHALL BE 2
 1/2"- 1 1/2" REDUCER WITH CHAINS.
  
 7) FIRE SPRINKLERS APPEAR TO BE MISSING
 AT STAIRWAY #1. SHT FS2.5.
  
 8) PLEASE SHOW LOCATION OF FIRE
 DEPARTMENT CONNECTION.
  
 9) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 10) NOTE #18 ON SHT FA0.1 SHOULD READ
 FIRE ALARM SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 11) SMOKE DETECTOR IS REQUIRED IN AREA
 OF FACP.
  
 12) KNOX BOX IS REQUIRED IF NOT ALREADY
 PROVIDED NEAR FRONT DOOR.
  
 13) THIS PROJECT WOULLD APPEAR TO MEET
 THE DEFINITION OF MIXED OCCUPANCY AND
 THEREBY SHALL COMPLY WITH NFPA 101,
 SECTION 6.1.14.3.
  
 14) PLEASE PROVIDE A LIFE SAFETY PLAN
 THAT ILLUSTRATES MAXIMUM TRAVEL
 DISTANCES.
  
 15) PLEASE PROVIDE NOTE ON ELEVATIONS
 INDICATING THAT ADDRESS SHALL BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO
 THE BACKGROUND.
  
 16) STAIRS TO COMPLY WITH APPLICABLE
 BUILDING CODES AND NFPA 101, 2003
 EDITION SECTION 7.2.2.2.1(A)
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 13:40 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 13:40 Sent To  
Notes
2007-05-31 14:16:31TO "COMM" BD#6/PLANS ON RACK--3 ROLLS
2007-05-10 13:40:16WAITING FOR "COMM" BD/ NEW SHEETS FOR "Z" AND "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-04 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-07-19 Time 09:43 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #62
2006-07-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-21 Cont ID  
Sent By hmoser Date 2007-06-21 Time 14:14 Rev Time 0.00
Received By hmoser Date 2007-06-21 Time 14:14 Sent To  
Notes
2007-06-21 14:20:336/21/07
 BTUH ON ENERGY CALCULATIONS DO NOT MATCH PLANS.
 PLEASE PROVIDE MANUFACTURE INSTALLATION INSTRUCTION ON
 MOTORIZED DAMPER AT ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-04 Cont ID  
Sent By hmoser Date 2006-10-04 Time 17:15 Rev Time 0.00
Received By hmoser Date 2006-10-04 Time 17:15 Sent To  
Notes
2006-10-04 00:00:00PASS PROVISO
 1) PAGE M2.1 AHU #1 PLEASE REFER TO
 SECTION 307.2.3 AUXILIARY AND SECONDARY
 DRAIN SYSTEM.
 2) PLEASE PROVIED MANUFACTURE
 INSTALLATION INSRTUCTIONS FOR MOTORIZED
 DAMPER AT ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-12 Cont ID  
Sent By kstevens Date 2007-06-12 Time 12:33 Rev Time 0.00
Received By kstevens Date 2007-06-12 Time 12:33 Sent To  
Notes
2007-06-12 12:37:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THIS REVIEW IS FOR THE BUILDING SHELL
 ONLY. ALL ISSUES CONCERNING MINIMUM
 FIXTURES REQUIRED, ACCESSIBLILTY AND
 FAIR HOUSING SHALL BE ADDRESSED AT THE
 TIME OF BUILD OUT FOR ALL 5 FLOORS.
 ******INFORMATIONAL ONLY--OK
  
 2. OK
  
 3. SUBMIT A CONDENSATE RISER DIAGRAM.
 SHOW ALL PIPE SIZES, AND SHOW COMPLIANCE
 WITH SECTION 1506.3, DISCHARGE AT LEAST
 1FT AWAY FROM THE STRUCTURE SIDEWALL.
 SECTION 106.3.5.1.3.
 ******RESPONSE NOTED, BUT THE CONDENSATE SHALL EXIT THE
 BUILDING SEPARATELY, AND CAN CONNECT TO THE STORM
 OUTSIDE THE BUILDING, BUT MUST HAVE A RELIEF VENT
 INSTALLED AS THE CONDENSATE EXITS THE BUILDING.
  
 4. OK
  
 5. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By kstevens Date 2006-08-24 Time 14:23 Rev Time 0.00
Received By kstevens Date 2006-08-23 Time 18:52 Sent To  
Notes
2006-08-24 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THIS REVIEW IS FOR THE BUILDING SHELL
 ONLY. ALL ISSUES CONCERNING MINIMUM
 FIXTURES REQUIRED, ACCESSIBLILTY AND
 FAIR HOUSING SHALL BE ADDRESSED AT THE
 TIME OF BUILD OUT FOR ALL 5 FLOORS.
  
 2. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES, AND INDICATE SQUARE
 FOOTAGE. SHOW ALL CLEANOUTS REQUIRED BY
 SECTION 1101.8. SECTION 1106.3.5.1.3.
  
 3. SUBMIT A CONDENSATE RISER DIAGRAM.
 SHOW ALL PIPE SIZES, AND SHOW COMPLIANCE
 WITH SECTION 1506.3, DISCHARGE AT LEAST
 1FT AWAY FROM THE STRUCTURE SIDEWALL.
 SECTION 106.3.5.1.3.
  
 4. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
  
 5. ALL PLUMBING, ELECTRICAL, MECHANICAL,
 FIRE SPRINKLER SHEETS. ENGINEER
 CERTIFICATE OF AUTHORIZATION DOES NOT
 MATCH THE NUMBER SHOWN IN DBPR WEBSIET.
 PLEASE INDICATE CERTIFICATE OF
 AUTHORIZATION IN TITLE BLOCK FOR KAMM
 CONSULTING. (SEE ATTACHED SHEET FROM
 DBPR).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-15 Cont ID  
Sent By mflis Date 2007-06-15 Time 09:57 Rev Time 0.00
Received By mflis Date 2007-06-15 Time 09:57 Sent To  
Notes
2007-06-15 09:59:13ZONING REVIEW: PASSED
  
 * FORWARDED TO HISTORIC PRESERVATION FOR REVIEW
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-09 Cont ID  
Sent By mflis Date 2006-08-09 Time 08:54 Rev Time 0.00
Received By mflis Date 2006-08-09 Time 08:54 Sent To  
Notes
2006-08-09 00:00:00* PLEASE VERIFY ELEVATOR SHAFT WILL NOT
 BE VISIBLE ABOVE ROOFLINE; IF IT WILL,
 PLEASE INDICATE IN ELEVATIONS AND/OR
 SECTIONS.
  
 * FORWARDED TO HISTORIC FOR REVIEW
 08-09-06.
  
 MJF