Plan Review Details - Permit 06070858
Plan Review Stops For Permit 06070858
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-20 Cont ID  
Sent By alange Date 2006-10-20 Time 11:29 Rev Time 0.00
Received By alange Date 2006-10-20 Time 11:29 Sent To  
Notes
2006-10-19 18:39:23NEW SHEETS FOR BLDG, NEEDS REVIEW AND STAMP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-22 Cont ID  
Sent By alange Date 2006-08-22 Time 09:13 Rev Time 0.00
Received By alange Date 2006-08-22 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 13:22 Rev Time 0.00
Received By alange Date 2006-07-26 Time 12:57 Sent To  
Notes
2006-07-26 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW CONSTRUCTION TYPE ON PLANS,
 2004 FBC 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
  
 3.LEVEL OF ALTERATION IS LEVEL 2 PER
 2004 FEBC SECTION 304.
  
 4.SUBMIT A UNITY OF TITLE SHOWING THE
 JOINING OF THE TWO PENTHOUSE UNITS.
  
 5.BLOCKING IN CONSEALED SPACES OF TYPE
 I CONSTRUCTION SHALL BE OF NON
 COMBUSTIBLE MATERIALS.SHOW ON PLANS.
 FBC 717.5
  
 6.DECORATIVE DROP CEILING DETAIL.
 SHOW METHOD OF ATTACHMENT, SPACING AND
 LENGTH OF FASTENERS USED.
 WILL POST-TENTIONING BE LOCATED BY AN
 X-RAY?
  
 7.FLOORING...WILL ONLY CARPETING BE
 REPLACED?IF TILE OR STONE IS INSTALLED
 ADDITIONAL INFORMATION WILL BE REQUIRED
 REGARDING CORK AND POSSIBLE LOAD
 CALCULATIONS.
  
 8.NOTE:VAPOR BARRIOR IS REQUIRED
 BEHIND CEMENT BOARD.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2006-10-19 Time 18:38 Sent To P
Notes
2006-10-19 19:01:03PLANS OK, STAMPED, ELECTRICAL PASSED AND HAND ROUTED TO
 JOHN LEECH FOR RE-STAMPING AS THERE ARE NEW SHEETS IN
 SETS. ONCE PLANS ARE DONE IN PLUMBING, THEY WILL ROUTED
 TO BLDG FOR RE-STAMP ALSO.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 09:51 Sent To  
Notes
2006-08-20 00:00:00*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SHOW ALL NEW/EXISTING
 CIRCUTING ON PLANS FOR LTS, APPLIANCES
 ETC AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE PANEL SCHEDULES NOW SHOW ALL
 THE NEW CIRCUITS, YET THESE ARE NOT ON
 PLANS.
  
 2) NOTE: PLEASE SEE A "PRIVATE PROVIDER'
 AFFIDAVIT IS BEING SUBMITTED STATING
 ELECTRICAL PLANS REVIEWED FOR CODE
 COMPLIANCE BY MR. ERIC WOODS FOR PLANS
 DATED 6/12/06 AND 7/11/06. PLEASE SEE
 NEW PLANS SUBMITTED WHICH WERE REVISED
 BY THE ARCHITECT IS DATED 8/3/06.
 PLEASE SEE ONLY ONE AFFIDAVIT WAS
 SUBMITTED ON ONE COPY OF THE ELECTRICAL
 PLANS FOR THIS.
 PLEASE SEE THE OTHER TWO SETS OF PLANS
 CONTAIN AFFIDAVIT WHICH STATS
 ARCHITECTURAL PLANS DATED 6/16/06 AND
 7/11/06 REVIEWED FOR CODE COMPLIANCE ,
 YET THESE WERE ALSO REVISED WITH NEW
 SHEETS DATED 8/3/06
 IF CONTRACTOR IS GOING TO SUBMIT PLANS
 DONE BY A "PRIVATE PROVIDER" THEN, ALL
 REVISED PLANS MUST GO BACK TO SAID
 PROVDER FOR REVIEW ETC.
 PLEASE ALSO SEE THE PLANS WERE ALSO NOT
 STAMPED BY THE "PROVIDE PROVIDER"
 COMPANY AS DONE ON THE PREVIOUS PLANS,
 "REVIEWED FOR CODE COMPLIANCE".
 PLEASE SEE THE AFFIDAVIT(S) ARE LISTING
 TWO DIFFERENT PERSONS PROVIDING
 SERVICES. PREVIOUS AFFIDAVIT ALSO LISTED
 TWO DIFFERENT PERSONS. THESE AFFIDAVITS
 ARE NOTARIZEDUNDER FS 117.05 AS BEING
 TAKEN UNDER OATHETC.
 THIS AFFIDAVIT IS NOT VALID BASED ON
 STATEMENTS, PLANS, ETC.
 FS 553.79(1).
 ** PLEASE KNOW , ONE SET OF EACH OF THE
 OLD PLANS AND NEW PLANS SUBMITTED ARE
 BEIGN RETAINED BY THIS OFFICE.
  
  
 ** PLEASE KNOW, THE PLANS COULD BE
 STAMPED AND PASSED WITH A "PROVISO" FOR
 ELECTRICAL AND ISSUANCE, HOWEVER SINCE
 PLANS ARE BEING SUBMITTED BY THE
 CONTRACTOR FOR "PRIVATE PROVIDER NOTE #2
 MUST BE ADDRESSED.
  
 ** PLEASE CALL TO GO OVER ANY QUESTIONS,
 OR OPTIONS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 20:48 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 20:25 Sent To  
Notes
2006-07-23 00:00:00****UNSAT ****
  
 1) NOTE: PLEASE PROVIDE CIRCUITING FOR
 NEW ELECTRICAL DEVICES ON PLANS. PLEASE
 LABEL THE APPLIANCES BEING LISTED IN
 LOAD CALCULATIONS.
 PLEASE LIST THE NEW CIRCUIT(S) INCLUDING
 THE DEDICATED BATH(S) RECEPTS AS NOTED
 210.11C3, MUST BE 20A AND #12.
 PLEASE PROVIDE A PANEL SCHEDULE FOR NEW
 CIRCUITINGAND EXISTING. PLEASE LIST
 THE OCP AND CONDUCTOR SIZES FOR NEW
 CIRCUITS AND /OR EIXSITNG CIRCUITS WHICH
 MAY BE UTILIZED.
 240.4,310.16,408.4
 106.1.2 FBC ADMIN SECT AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE NEC 2002 IS BEING
 REFERENCED FOR REQUIREMENTS OF SMOKE
 DETECTORS IN NOTES, WHERE REQUIREMENTS
 ARE FROM NFPA-72. THE CURRENT CODE IN
 EFFECT IS 2002. 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE SEE NOTE FOR CLOSET LT
 MENTIONS SHALL BE OFFSET 6" MINIMUM FROM
 SHELVING, HOWEVER DEPENDING ON FIXTURE
 TYPE, THIS MAY INDEED BE REQUIRED AT
 12". PLEASE LIST PROPOSED FIXTURE AND
 SEE 410.8 FOR REQUIRED FIXTURE TYPES AT
 6".
  
 4) NOTE: PLEASE SEE THE PROVIDE PROVIDER
 NOTICE TO BUIDLINF OFFICAL DOES NOT
 INDICATE IF THIS WILL BE FOR PLAN REVIEW
 OR INSPECTIONS OR BOTH. PLEASE KNOW,
 THESE ARE REQUIRED TO BE INDICATED.
 PLEASE ALSOTHREE DIFFERENT "PROVIDE
 PROVIDERS" ARE LISTED IN PAPERWORK AND
 ONLY ON SIGNIGN AN AFFIDAVIT. PLEASE SEE
 TWO SEPARATE NAME LISTED ON AFFIDAVIT.
 PLEASE CORRELATE AND ADJUST.
  
 ** ONLY A NOTE**
 PLEASE VERIFY THE LOADS SHOWN FOR WATER
 HEATER AS THIS IS NOT A STANDARD HEATING
 ELEMENT SIZE.
 PLEASE ALSO SEE THE LOADS SHOWN FOR
 DOUBLE OVENS AND COOKTOP BOTH SEEM VERY
 LOW. THIS IS A NOTE TO VERIFY AND ADJUST
 AS NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-23 Cont ID  
Sent By mwennerg Date 2006-08-23 Time 14:05 Rev Time 0.00
Received By mwennerg Date 2006-08-23 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-01 Cont ID  
Sent By mwennerg Date 2006-08-01 Time 15:41 Rev Time 0.00
Received By mwennerg Date 2006-08-01 Time 15:40 Sent To  
Notes
2006-08-01 00:00:00***APPROVED***
  
 LIFE SAFETY SHALL COMPLY WITH NFPA 101,
 2003 EDITION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 18:57 Rev Time 0.00
Received By dpalmer Date 2006-10-19 Time 18:57 Sent To M
Notes
2006-10-19 18:59:37PLANS WERE SUBMITTED ON RESUB COVER SHEET UNDER PERMIT
 NUMBER 06070461 IN ERROR.
 PLANS WERE ROUTED TO INCORRECT LOCATION.
 PLANS ARE NOW BEING ROUTED UNDER COORECT NUMBER ,
 HOWEVERBY HAND TO REVIEWERS PER DEWEY PALMER.
 IF THERE ARE ANY QUESTIONS, CALL 805-6717

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 15:32 Sent To  
Notes
2006-08-18 00:00:00TO "COMM" BD#6--EXPEDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-01 Cont ID  
Sent By mwennerg Date 2006-08-01 Time 15:42 Rev Time 0.00
Received By mwennerg Date 2006-07-15 Time 11:01 Sent To  
Notes
2006-07-19 00:00:00TO "BOB"#4
2006-07-15 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-10-19 Cont ID  
Sent By tgordon Date 2006-10-19 Time 16:44 Rev Time 0.20
Received By tgordon Date 2006-10-19 Time 16:44 Sent To E
Notes
2006-10-19 16:45:33NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-21 Cont ID  
Sent By tgordon Date 2006-08-21 Time 13:56 Rev Time 0.20
Received By tgordon Date 2006-08-21 Time 13:56 Sent To  
Notes
2006-08-21 00:00:00*** DENIED ***
 1) NO MECHANICAL DETAIL SUBMITTED WITH
 REVISED PLANS.
  
 2) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06070864 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By tgordon Date 2006-07-19 Time 14:48 Rev Time 0.30
Received By tgordon Date 2006-07-19 Time 14:48 Sent To  
Notes
2006-07-19 00:00:00RELOCATE ONE EXISTING SUPPLY AIR DUCT.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-20 Cont ID  
Sent By jleech Date 2006-10-20 Time 07:10 Rev Time 0.00
Received By jleech Date 2006-10-20 Time 07:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-22 Cont ID  
Sent By jleech Date 2006-08-22 Time 07:26 Rev Time 0.00
Received By jleech Date 2006-08-22 Time 07:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-22 Cont ID  
Sent By jleech Date 2006-07-22 Time 07:06 Rev Time 0.00
Received By jleech Date 2006-07-22 Time 07:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2006-08-23 Cont ID  
Sent By mflis Date 2006-08-23 Time 09:57 Rev Time 0.00
Received By mflis Date 2006-08-23 Time 09:57 Sent To  
Notes
2006-08-23 00:00:00INTERIOR BUILDOUT ONLY; NO ZONING REVIEW
 NECESSARY. MJF