Plan Review Details - Permit 06070811
Plan Review Stops For Permit 06070811
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-02 Cont ID  
Sent By jleahy Date 2006-10-02 Time 16:01 Rev Time 1.00
Received By jleahy Date 2006-10-02 Time 16:01 Sent To  
Notes
2006-09-24 00:00:00SENT TO JAKE LEAHY FOR REVIEW AT
 REQUEST OF CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 12:09 Sent To PC
Notes
2006-08-09 00:00:00*** UNSAT **
  
 1) NOTE: PLEASE SEE AT THIS TIME CAN NOT
 VERIFY GROUPING OF MAINS. PER 230.72,
 AND 225.34.
 PLEASE CLARIFY IF THE MDP CONTAINS A
 MCB?, THEN ALL MAINS ARE NOT GROUPED. IT
 SEEMS WHICH IF YOU WERE INSIDE AND MDP
 CONTAINED NO MAIN, THEN NEW MAIN FOR THE
 MDP FOR POSSIBLE GENERATOR FEEDERS IS
 OUTSIDE AND WOULD NOT GROUPED WITH OTHER
 MAINS. (HOUSE MAIN, AND MAIN FOR
 SERIVICE.
 PLEASE ALSO SEE GUTTER IS BEING SHOWN
 BELOW EXISTING MAIN WHICH MUST MEET
 110.26. PLEASE VEIRFY THE DEPT OF THE
 MAIN AND THE DEPTH OF THE GUTTER, AS
 GUTTER MAY NOT EXTEN MORE THAN 6" OUT.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 17:21 Sent To PC
Notes
2006-07-16 00:00:00************ UNSAT ************
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION
 MUST CONTAIN AN ORIGINAL SIGNATURE FOR
 QUALIFIER/OR AUTHORIZED AGENT. PLEASE
 SEE APPLICATION IS A COLORED PHOTO-COPY
 OF THE CONTRACTORS SIGNATURE. PLEASE
 ALSO SEE THIS APPLICATION WAS NOTORIZED
 IN VIOLATION OF FS 117.05, AS A NOTORY
 MAY NOT UNDER ANY CIRCUMSTANCES NOTORIZE
 A "PHOTO-COPIED" SIGNATURE.
 APPLICATION IS BEING RETAINED AND TURNED
 OVER TO THE PERMIT/LICENSING MANAGER.
  
 2) NOTE: PLEASE SEE THAT THE
 PLANS/RISER/DRAWING SUBMITTED MUST
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN. THIS IS NOT REQUIRED TO BE
 NOTORIZED, HOWEVER IF IT IS, PLEASE BE
 SURE ALL INFORMATION IS PROVIDED FOR IT
 TO BE LEGALLY NOTORIZED. FS 117.05
  
 3) NOTE: PLEASE SUBMIT MANUFCATURE
 SPECS/CUT SHEETS FOR THE NEW PROPOSED
 MTS.
 PLEASE SEE THAT THE MTS WILL NOT BE
 PERMITTED AS SHOWN ON RISER. IF THE
 INTENTION TO TO PROVIDE CONNECTIONS FOR
 POSSIBLE FUTURE PORTABLE GENERATOR, THEN
 PLEASE MAKE THE CORRECT
 JUNCTION/CONNECTION FOR THIS. AS SHOWN,
 THIS WOULD PLACE THE FEEDERS INTO THE
 SAME GUTTER WITH THE LOAD SIDE OF THE
 MTS. PLEASE CLARIFY INSTALLATION.
 110.3,702.6,ETC.
  
 4) NOTE: PLEASE PROVIDE A SIGNED
 CONTRACT AS VALUE SEEMS LOW FOR PROPOSED
 SCOPE OF WORK. ALL LABOR AND MATERIALS
 SHALL BE INCLUDED EVEN IF ANY IS OWNER
 SUPPLIED.
 FCB 108.3 ADMIN SECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 19:46 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 19:45 Sent To E
Notes
2006-09-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 11:56 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 11:56 Sent To E
Notes
2006-08-03 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-16 Time   Rev Time 0.00
Received By adarroug Date 2006-07-15 Time 09:47 Sent To  
Notes
2006-07-15 00:00:00TO "E" BOX