Plan Review Details - Permit 06070806
Plan Review Stops For Permit 06070806
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-08 Cont ID  
Sent By alange Date 2006-09-08 Time 09:03 Rev Time  
Received By alange Date 2006-09-08 Time 09:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 09:44 Rev Time 0.00
Received By alange Date 2006-07-26 Time 09:44 Sent To  
Notes
2006-07-26 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 3.INSUFFICIENT INFORMATION SUBMITTED
 FOR PLAN REVIEW.SEE FBC 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.SHOW THE FOLLOWING
 INFORMATION ON PLANS...
 CONSTRUCTION TYPE
 SHOW EXISTING AREA AND SHOW AREA OF NEW
 WORK.
 SHOW IF ANY EXTERIOR DOORS OR WINDOWS
 ARE BEING REPLACED OR ADDED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-22 Cont ID  
Sent By dpalmer Date 2006-09-22 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2006-09-22 Time 11:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 07:23 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 20:50 Sent To PC
Notes
2006-09-20 00:00:00**** UNSAT ******
  
 1) NOTE: PLEASE SEE LETTER FROM AMES
 BENNETT MUST BE ORIGINAL. ALL SUBMITTED
 ARE PHOTO-COPIES OF SIGNED, AND
 NOTARIZED LTR. PLEASE SEE NOTARY IS NOT
 CORRECT PER FS 117.05.
 PLEASE OBTAIN ORIGINAL LETTERS WITH
 CORRECT NOTARIZATION.
  
 2) NOTE: PLEASE SEE THAT THE CONTRACTOR
 MUST ALSO WRITE THE ADDRESS AND UNIT
 NUMBER OF JOB ON EACH TITLE BLOCK.
 FAC 61G1-16.004, 61G15-23.002
  
  
 ** PLEASE KNOW, AS NEW REVISED
 ELECTRICAL PLANS WERE NOT SUBMITTED BY
 THE ELECTRICAL ENGINEER FOR THE CABANA
 ELECTRIC, THE SHEETS L100, 200 IN
 ARCHITECTURAL SHEETS HAVE BEEN REMOVED.
 PLEASE SEE SHEET E-100 DONE BY THE
 ARCHITECT WHICH DID NOT CORRELATE TO THE
 ELECTRICAL ENGINEERS PLANS WAS ALSO
 REMOVED.
 ANY ELECTRICAL IN CABANA IS NOT INCLUDED
 IN SCOPE. MUST SUBMIT REVISED PLANS AT A
 LATER DATE OR SEPARATE PERMIT, PLANS AND
 FEES WILL BE DUE FOR THIS.
  
 ** CALLED WAYNE MACK AT 9:05PM ON
 TUESDAY NIGHT AND LEFT A MESSAGE ABOUT
 THE LETTER(S).
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-09-19 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 21:08 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 19:56 Sent To PC
Notes
2006-09-08 00:00:00***** UNSAT *****
  
 ** PLEASE SEE MANY ITEMS BELOW ARE NEW
 COMMENTS AS MANY ITEMS ON PLANS ARE
 BEING SUBMITTED FOR THE FIRST TIME.
  
 1) NOTE: PLEASE SUBMIT THE LETTERS FROM
 THE ARCHITECT AND ENGINEERS FOR PROJECT
 AS ORIGINAL. PLEASE KNOW THE LETTERS
 FROM THE ORIGINAL ARCHITECT SHALL BE
 ORIGINAL SIGNED, DATED AND SEALED.
 PLEASE SEE LETTERS ATTACHED TO PLANS ARE
 PHOTO-COPIES AND NONE ARE DATED AND
 SEALED.
 PLEASE SEE ONLY ONE LETTER FROM THE
 ENGINEERING FIRM CONTAINS AN ORIGNAL
 SIGNATURE. OTHER TWO LETTERS ARE ALSO
 PHOTO-COPIESAND NO LETTERS ARE SEALED
 WITH RAISED SEAL O R DATED.
 PLEASE SEE NO LETTER FROM THE NEW
 ARCHITECT RECORD TAKING RESPONSIBILTY
 FOR NEW PLANS / DESIGN AND PROJECT COULD
 BE LCATED ON PLANS OR IN SAID PACKAGE.
  
 ** PLEASE KNOW, ALL LETTERS WHICH ARE
 SIGNED, DATED AND SEALED IN FLORIDA,
 SHALL BE CORRECTLY NOTARIZED AS REQUIRED
 UNDER FS 117.05 WITH ALL INFORMATION AS
 REQUIRED BE NOTARY.
 PLEASE SEE FS 481 AND 471 FOR
 REQUIREMENTS OF NEW DESIGNERS TAKING OVE
 OF PROJECT(S).
  
 2) NOTE: PLEASE SEE 210.52B1, AS DINING
 ROOM AND AREAS OF THE LIKE SHALL BE ON
 ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE KNOW, EACH CIRCUIT OVER
 THE TWO MIN, SHALL ALSO BE FIGURED AT
 THE MIN 1500VA EACH. PLEASE SEE DINGIN
 IS SHOWN AS 540 AND OTHER APPLIANCE
 CIRCUITS ARE SHOWN AS 1200VA.
 NOTE**PLEASE VERIFY REFRIGERATOR, IF
 LOAD OF FRIG IS OVER 750VA , THEN A
 DEDICATED CIRCUIT IS REQUIRED.THIS IS
 ONLY NOTED.
 PLEASE SEE 210.52B1, 210.11C1,220.16
  
 3) NOTE: PLEASE SEE 220.18 AS LOAD TO BE
 FIGURED FOR DRYER SHALL BE 5KW MIN.
 PLEASE ALSO ADJUST THE BRANCH CIRCUIT
 FOR MIN OF #10 AWG AND 30A OCP.
 240.4,310.16
 PLEASE SEE PLANS ALSO INDICATE THIS AS A
 "STACKABLE UNIT" AND NOT SEPARATE UNITS.
  
 ** THERE IS NOT ENOUGH CLEARNECE FOR
 TWO UNITS AS ALL AUTOMATED PANELS ETC
 ARE IN SAME AREA.
  
 4) NOTE: PLEASE INDICATE CIRCUITING ON
 PLANS FOR ALL. PLEASE SEE SD'S.
 408.4,
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS REQUIRED FOR ALL OUTLETS IN BEDRMS OR
 ADAPTABLE SLEEPING ROOMS.
 2002 NEC, 210.12, THIS INCLUDES SD'S,
 LTS, RECEPTS ETC.
 PLEASE SEE THIS INCLUDES THE "STUDY"
 WHICH IS AN ADAPTABLE SLEEPING ROOM.
  
 6) NOTE: PLEASE SEE WASHER IS BEING
 SHOWN A 220V UNIT ON PANEL SCHEDULE WITH
 A 3KW LOAD? PLEASE CORRELATE AS THE
 WASHER ON LOAD CALCULATIONS ONLY
 INDICATE THIS AS A 1500VA , 120V UNIT??
 210.11C2, 220.16B.
  
 7) NOTE: PLEASE SEE ELECTRICAL PLANS DO
 NOT INDICATE OR SHOW ANY ELECTRICAL FOR
 CABANA REMODEL. PLEASE SEE MISSIGN ITEMS
 ON PANEL SCHEDULES, DEDICATED CIRCUITS
 ETC.
 ARCHITECTURAL PLANS DO INDICATE THIS
 BEING IN SCOPE OF WORK.
  
 8) NOTE: PLEASE BE SURE SUITE/ UNIT
 NUMBER IS LOCATED ON THE TITLE BLOCKS ON
 ALL SHEETS AS REQUIRED PER FAC
 61G1-16.004 AND 61G15-23.002
 ** THIS CAN BE HAND WRITTEN ON TITLE
 BLOCKS WHICH ALREADY CONTAIN STAMPS FOR
 THE REVIEWS WHICH HAVE PASSED.
  
 9) NOTE: PLEASE KNOW, ALL PLANS/SETS AND
 ALL SHEETS SHALL CONTAIN THE CODES
 CURRENTLY UNDER ADOPTION UNDER FS'S 553
 AND FBC 2004 WHICH ARE RELEVANT TO PLANS
 AND DEISGNS SUBMITTED.
 PLEASE SEE 2004 FBC, 2002 NFPA-70 (NEC),
 2002 NFPA-72 IS REQUIRED AT A MIN,
 INLCUDING 2004 FBC FOR MECH AND PLUMB.
 THIS IS REQUIRED ON SHEETS WHETHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 10) NOTE: PLEASE REMOVE ELECTRICAL PLANS
 DONE BY ARCHITECTURAL FIRM, AS THE
 REVISED PLANS DONE BY THE ENGINEERING
 FIRM SEEMS TO BE THE ONES SUBMITTED FOR
 SCOPE PF WORK.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 07:24 Rev Time 0.00
Received By dpalmer Date 2006-07-24 Time 07:10 Sent To  
Notes
2006-07-24 00:00:00******* UNSAT **********
  
 1) NOTE: PLEASE SUBMIT COMPLETE
 ELECTRICAL PLANS FOR REVIEW. PLEASE
 INCLUDE NEW LIGHTING CONTROL SYSTEM
 WHICH IT IS KNOWN TO THIS OFFICE.
 PLEASE SUBMIT SPECIFICATIONS ON SYSTEM.
 PLEASE SEE 2002 NFPA-72 AND 2002 NFPA-70
 PLEASE PROVIDE CIRCUITING AND CORRELATE
 WITH PANEL SCHEDULES TO BE SUBMITTED.
 PLEASE LIST ALL THE REQUIRED CIRUCITS
 ALONG WITH OCP AND AWG SIZES FOR ALL.
  
 215.5,240.4,310.16,220.16,220.31,
 210.52, 210.5211C, 210.8A ETC
  
 2) NOTE: PLEASE CLARIFY TITLE BLOCK AS
 IT LISTE MPERRY DESIGN INC/ AMES BENNET
 PA.IF THIS IS A NEW FIRM PLEASE
 PROVIDE CERTIFICATE OF AUTHORIZATION
 NUMBER AS REQUIRED PER FS 481.219 OR
 PLEASE ADJUST TITLE BLOCKS.
 PLEASE ALSO CLARIFY BRUCE BEIRMAN DESIGN
 INC ALSO FOR REQUIRED LICENSURE. FS
 481.219, FAC 61G1-16.004.
 PLEASE KNOW, ALL FIRMS LISTED ON TITE
 BLOCKS SHALL CONTAIN ALL REQUIRED
 INFORMATION.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE ELECTRICAL
 SPECIFICATION SHEETS WERE STAMPED IN
 ERROR FROM MECHANICAL REVIEWER AND HAVE
 BEEN VOIDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-07 Cont ID  
Sent By mawillia Date 2006-09-07 Time 15:09 Rev Time 0.00
Received By mawillia Date 2006-09-07 Time 15:09 Sent To  
Notes
2006-09-07 00:00:00*****APPROVED****** W/PROVISO
  
  
  
  
  
  
 1.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING ALTERATION.
  
 2.) THE FIRE DEPARTMENT SHALL BE
 NOTIFIED WHEN THE SYSTEM IS SHUT DOWN
 AND WHEN THE SYSTEM IS RETURNED TO
 SERVICE.
  
 3.) WHERE ALTERATION REQUIRES
 MODIFICATION OF A PORTION OF THE FIRE
 PROTECTION SYSTEM (FIRE ALARM,
 SPRINKLER), PROVIDE SEPARATE PERMITS AND
 SHOP PLANS/DRAWINGS FOR REVIEW.
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-02 Cont ID  
Sent By mawillia Date 2006-08-02 Time 15:24 Rev Time 0.00
Received By mawillia Date 2006-08-02 Time 15:23 Sent To  
Notes
2006-08-02 00:00:00***DENIED***
  
  
 1. PLEASE SHOW ON PLANS LOCATION OF
 SMOKE DETECTORS AND INDICATE IF THEY ARE
 EITHER SINGLE OR MULTIPLE STATION
 AND(OR)IF THEY ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM.
  
  
  
  
  
 MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 13:36 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 13:36 Sent To E
Notes
2006-09-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-28 Cont ID  
Sent By adarroug Date 2006-08-28 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 09:57 Sent To  
Notes
2006-08-28 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-02 Cont ID  
Sent By mawillia Date 2006-08-02 Time 15:23 Rev Time 0.00
Received By mawillia Date 2006-07-17 Time 10:00 Sent To  
Notes
2006-07-20 00:00:00TO "BOB"#13
2006-07-17 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-07 Cont ID  
Sent By tgordon Date 2006-09-07 Time 16:08 Rev Time 0.30
Received By tgordon Date 2006-09-07 Time 16:08 Sent To  
Notes
2006-09-07 00:00:00RE-STAMP RETURNED TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 13:43 Rev Time 0.45
Received By tgordon Date 2006-07-21 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-08 Cont ID  
Sent By jleech Date 2006-09-08 Time 07:59 Rev Time 0.00
Received By jleech Date 2006-09-08 Time 07:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By jleech Date 2006-07-24 Time 09:29 Rev Time 0.00
Received By jleech Date 2006-07-24 Time 09:29 Sent To  
Notes
2006-07-24 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE NUMBER
 TWO.
 2.MASTER BATH SANITARY RISER DIAGRAM;
 LAVATORY MISSING. THE LAVATORY VENT
 COULD BE THE VENT FOR THE BATHROOM
 GROUP, THE TUB WOULD NOT NEED A VENT.
 3.OFFICE BATHROOM SANITARY RISER
 DIAGRAM; SHOWER VENT, DRY HORIZONTAL
 VENTS NOT PERMITED. SEE SECTION 905.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695