| 2006-09-08 00:00:00 | ***** UNSAT ***** |
| | |
| | ** PLEASE SEE MANY ITEMS BELOW ARE NEW |
| | COMMENTS AS MANY ITEMS ON PLANS ARE |
| | BEING SUBMITTED FOR THE FIRST TIME. |
| | |
| | 1) NOTE: PLEASE SUBMIT THE LETTERS FROM |
| | THE ARCHITECT AND ENGINEERS FOR PROJECT |
| | AS ORIGINAL. PLEASE KNOW THE LETTERS |
| | FROM THE ORIGINAL ARCHITECT SHALL BE |
| | ORIGINAL SIGNED, DATED AND SEALED. |
| | PLEASE SEE LETTERS ATTACHED TO PLANS ARE |
| | PHOTO-COPIES AND NONE ARE DATED AND |
| | SEALED. |
| | PLEASE SEE ONLY ONE LETTER FROM THE |
| | ENGINEERING FIRM CONTAINS AN ORIGNAL |
| | SIGNATURE. OTHER TWO LETTERS ARE ALSO |
| | PHOTO-COPIESAND NO LETTERS ARE SEALED |
| | WITH RAISED SEAL O R DATED. |
| | PLEASE SEE NO LETTER FROM THE NEW |
| | ARCHITECT RECORD TAKING RESPONSIBILTY |
| | FOR NEW PLANS / DESIGN AND PROJECT COULD |
| | BE LCATED ON PLANS OR IN SAID PACKAGE. |
| | |
| | ** PLEASE KNOW, ALL LETTERS WHICH ARE |
| | SIGNED, DATED AND SEALED IN FLORIDA, |
| | SHALL BE CORRECTLY NOTARIZED AS REQUIRED |
| | UNDER FS 117.05 WITH ALL INFORMATION AS |
| | REQUIRED BE NOTARY. |
| | PLEASE SEE FS 481 AND 471 FOR |
| | REQUIREMENTS OF NEW DESIGNERS TAKING OVE |
| | OF PROJECT(S). |
| | |
| | 2) NOTE: PLEASE SEE 210.52B1, AS DINING |
| | ROOM AND AREAS OF THE LIKE SHALL BE ON |
| | ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. PLEASE KNOW, EACH CIRCUIT OVER |
| | THE TWO MIN, SHALL ALSO BE FIGURED AT |
| | THE MIN 1500VA EACH. PLEASE SEE DINGIN |
| | IS SHOWN AS 540 AND OTHER APPLIANCE |
| | CIRCUITS ARE SHOWN AS 1200VA. |
| | NOTE**PLEASE VERIFY REFRIGERATOR, IF |
| | LOAD OF FRIG IS OVER 750VA , THEN A |
| | DEDICATED CIRCUIT IS REQUIRED.THIS IS |
| | ONLY NOTED. |
| | PLEASE SEE 210.52B1, 210.11C1,220.16 |
| | |
| | 3) NOTE: PLEASE SEE 220.18 AS LOAD TO BE |
| | FIGURED FOR DRYER SHALL BE 5KW MIN. |
| | PLEASE ALSO ADJUST THE BRANCH CIRCUIT |
| | FOR MIN OF #10 AWG AND 30A OCP. |
| | 240.4,310.16 |
| | PLEASE SEE PLANS ALSO INDICATE THIS AS A |
| | "STACKABLE UNIT" AND NOT SEPARATE UNITS. |
| | |
| | ** THERE IS NOT ENOUGH CLEARNECE FOR |
| | TWO UNITS AS ALL AUTOMATED PANELS ETC |
| | ARE IN SAME AREA. |
| | |
| | 4) NOTE: PLEASE INDICATE CIRCUITING ON |
| | PLANS FOR ALL. PLEASE SEE SD'S. |
| | 408.4, |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE ARC FAULT PROTECTION |
| | IS REQUIRED FOR ALL OUTLETS IN BEDRMS OR |
| | ADAPTABLE SLEEPING ROOMS. |
| | 2002 NEC, 210.12, THIS INCLUDES SD'S, |
| | LTS, RECEPTS ETC. |
| | PLEASE SEE THIS INCLUDES THE "STUDY" |
| | WHICH IS AN ADAPTABLE SLEEPING ROOM. |
| | |
| | 6) NOTE: PLEASE SEE WASHER IS BEING |
| | SHOWN A 220V UNIT ON PANEL SCHEDULE WITH |
| | A 3KW LOAD? PLEASE CORRELATE AS THE |
| | WASHER ON LOAD CALCULATIONS ONLY |
| | INDICATE THIS AS A 1500VA , 120V UNIT?? |
| | 210.11C2, 220.16B. |
| | |
| | 7) NOTE: PLEASE SEE ELECTRICAL PLANS DO |
| | NOT INDICATE OR SHOW ANY ELECTRICAL FOR |
| | CABANA REMODEL. PLEASE SEE MISSIGN ITEMS |
| | ON PANEL SCHEDULES, DEDICATED CIRCUITS |
| | ETC. |
| | ARCHITECTURAL PLANS DO INDICATE THIS |
| | BEING IN SCOPE OF WORK. |
| | |
| | 8) NOTE: PLEASE BE SURE SUITE/ UNIT |
| | NUMBER IS LOCATED ON THE TITLE BLOCKS ON |
| | ALL SHEETS AS REQUIRED PER FAC |
| | 61G1-16.004 AND 61G15-23.002 |
| | ** THIS CAN BE HAND WRITTEN ON TITLE |
| | BLOCKS WHICH ALREADY CONTAIN STAMPS FOR |
| | THE REVIEWS WHICH HAVE PASSED. |
| | |
| | 9) NOTE: PLEASE KNOW, ALL PLANS/SETS AND |
| | ALL SHEETS SHALL CONTAIN THE CODES |
| | CURRENTLY UNDER ADOPTION UNDER FS'S 553 |
| | AND FBC 2004 WHICH ARE RELEVANT TO PLANS |
| | AND DEISGNS SUBMITTED. |
| | PLEASE SEE 2004 FBC, 2002 NFPA-70 (NEC), |
| | 2002 NFPA-72 IS REQUIRED AT A MIN, |
| | INLCUDING 2004 FBC FOR MECH AND PLUMB. |
| | THIS IS REQUIRED ON SHEETS WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 10) NOTE: PLEASE REMOVE ELECTRICAL PLANS |
| | DONE BY ARCHITECTURAL FIRM, AS THE |
| | REVISED PLANS DONE BY THE ENGINEERING |
| | FIRM SEEMS TO BE THE ONES SUBMITTED FOR |
| | SCOPE PF WORK. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |