Plan Review Details - Permit 06070786
Plan Review Stops For Permit 06070786
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-14 Cont ID  
Sent By lursu Date 2006-07-14 Time 13:29 Rev Time 0.00
Received By lursu Date 2006-07-14 Time 10:00 Sent To  
Notes
2006-07-14 00:00:00NEED EXTENSION FOR CITY OWNED STREET
 LIGHTS BEING INSTALLED BETWEEN FLAGLER
 DR & S OLIVE AVE BETWEEN 260-250 240-230
 220-202 182-162 162-142 PALMETTO LANE
 EXT #0038 AS:126 PALMETTO LN , WAS
 CREATED UNDER THE MAIN ADDRESS 1045
 CHARLOTTE AVE FOR THE FIRST TRANSFORMER
 ON PALMETTO LN BETWEEN THE SITE
 ADDRESSES 122 & 142.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-24 Cont ID  
Sent By rbrown Date 2006-07-24 Time 15:30 Rev Time 0.00
Received By rbrown Date 2006-07-24 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 18:41 Sent To ENG
Notes
2006-07-26 00:00:00STAMPED ELEC SHEET.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 17:18 Sent To ENG
Notes
2006-07-18 00:00:00***** UNSAT *****
  
 ** PLEASE KNOW, PLANS WERE RE-REVIEWED
 AS DESIGN TEAM CALLED AND SAID
 INFORMATION WAS ON PLANS.
  
 ** PLEASE KNOW, ELECTRICAL NOTES PLACED
 ON REVIEW DONE BY MR BILL TROBAUGH STILL
 STAND. PLEASE SEE NOTES AS FOLLOWS FOR
 ANY ELECTRICAL CLARIFICATION AND ALSO
 NEW NOTES DUE TO THIS PLAN REVIEWERS
 OBSERVATION/REVIEW.
  
 1) NOTE: PLEASEPROVIDE LOCATION OF ALL
 LTS POLES ON PLANS.
 PLEASE INDICATE THE CONDUIT SIZES, ALONG
 WITH CONDUCTOR SIZES AND TYPES BEING
 INSTALLED.
 PLEASE INDICATE THE FPL TRANSFORMER
 LOCATION ON PLANS IN WHICH THESE ARE
 BEING CONNECTED. THIS OFFICE IS AWARE OF
 THE "INLINE" FUSES AND HOW THE BILLING
 IS DONE FOR CITY LIGHT POLES. PLEASE
 ONLY INDICATE THE OCP FOR THE "INLINE "
 FUSES AND VOLTAGE BEING CONNECTED.
 FBC ADMIN SECT 106.1.2, NEC
 240.4,310.16, ETC
  
 2) NOTE: PLEASE SEE PLANS ARE NOT
 SIGNED,DATED OR SEALED BY THE DESIGN
 PROFESSIONAL ON SAID TITLE BLOCKS.
 PLEASE DO SO. FS 471.025
  
 3) NOTE: PLEASE SEE WIND LOAD
 CALCUALTIONS WHICH CONTAINED A RAISED
 SEAL OF A SIGNATURE AND DATE WHICH IS
 NOT ORIGINAL AND IS INDEED A
 "PHOTO-COPY" OF SIGNED SHEETS.
 PLEASE SEE FAC 61G15-23.002, FS 471.025
 AS THE SIGNATURE AND DATE SHALL BE
 ORIGINAL WITH RAISED SEAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By btrobaug Date 2006-07-18 Time 09:01 Rev Time 0.50
Received By btrobaug Date 2006-07-18 Time 08:57 Sent To ENG
Notes
2006-07-18 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE CONDUIT AND CONDUCTOR SIZES,
 LOCATION AND SIZE OF OVERCURRENT
 PROTECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-07-31 Cont ID  
Sent By rchokshi Date 2006-07-31 Time 09:08 Rev Time 0.00
Received By rchokshi Date 2006-07-31 Time 09:02 Sent To  
Notes
2006-07-31 00:00:00PASS WITH FOLLOWING CONDITIONS:
 MUST MEET CITY OF WPB CODES &
 REQUIREMENTS, APPLICABLE COUNTY
 REQUIREMENTS, & FLORIDA BUILDING CODES
 IF REQUIRE.
  
 RASIK CHOKSHI 805-6723

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 11:33 Sent To E
Notes
2006-07-25 00:00:00TO "DPALMER" DESK/RESUB--TO BE ROUTED TO
 ENG NEXT.