Plan Review Details - Permit 06070735
Plan Review Stops For Permit 06070735
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-14 Cont ID  
Sent By mawillia Date 2006-09-11 Time 13:32 Rev Time 0.00
Received By lursu Date 2006-09-14 Time 14:43 Sent To  
Notes
2006-09-14 00:00:00ATTACH PERMIT TO EXT #0001 UNDER 210
 PICADILLY ST
2006-07-30 00:00:00NEEDS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-04 Cont ID  
Sent By alange Date 2006-10-04 Time 13:35 Rev Time 0.00
Received By alange Date 2006-10-04 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 14:39 Rev Time 0.00
Received By alange Date 2006-07-31 Time 14:30 Sent To  
Notes
2006-07-31 00:00:00DENIED
  
 1.GAF BITUMEN ROOF IS MISSING PAGES TO
 THE MIAMI-DADE PRODUCT APPROVAL.
 INCLUDE THE PAGES TO THE MIAMI-DADE THAT
 SHOW THE ASSEMBLY USED INCLUDING THE
 APPROPRIATE LIMITATIONS THAT MAY APPLY.
  
 2.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 3.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 4.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 5.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 17:49 Sent To  
Notes
2006-09-28 00:00:00NOTES REDLINED
  
 RECEPTS IN BEDRMS, 1/2 SWITCHED? IF THE
 ENTIRE RECEPT IS SWITCHED, THEN IT WILL
 REQUIRE AN ADDITIONAL.210.52,210.70.
  
 PANEL TO BE INSTALLED AS DETAILED IN
 BUILDING LAYOUT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-30 Cont ID  
Sent By dpalmer Date 2006-07-30 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2006-07-30 Time 18:26 Sent To  
Notes
2006-07-30 00:00:00******* UNSAT *******
  
 1) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE PANE SCHEDULE SHOWS 6
 CIRCUITS FOR GNE LTS AND RECEPTS
 FBC 106.1.2,
 408.4,240.4,310.16
  
 2) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 106.1.2
 PLEASE BE SURE ROOMS AND AREAS ARE
 IDENTIFIED ON PANEL SCHEDULE.
 408.4.
 IE: BEDRM LTS, KLIVING RM RECEPTSETC.
  
 3) NOTE: PLEASE SEE 210.11C1,220.16 A
 THE VA FOR EACH OF THE SMALL APPL
 CIRCUITS SHOULD BE 1500VA. PLEASE SEE 3
 CIRCUITS ARE SHOWN HOWEVER LOAD IS ONLY
 SHOWN FOR TWO.
  
 4) NOTE: PLEASE SEE BATH GFI RECEPT IS
 BEING SHOWN ON A 2POLE 40A BREAKER. THIS
 EXCEEDS RATINGS ETC.
 PLEASE ALSO SEE #6 AWG SHOWN.
 240.4,310.16,210.11C3
  
 5) NOTE: PLEASE SEE THAT A DEDICATED
 WINDOW A/C IS LISTED ON PANEL SCHEDULE,
 HOWEVER PLANS DO NOT SHOW THIS.
 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-09-11 Cont ID  
Sent By mawillia Date 2006-09-11 Time 13:22 Rev Time 0.00
Received By mawillia Date 2006-09-11 Time 12:57 Sent To  
Notes
2006-09-11 00:00:00*****APPROVED*****W/PROVISO
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) THE STORAGE OR DISPOSAL OF ROOFING
 AND(OR) BUILDING MATERIALS/WASTE SHALL
 NOT INTERFERE OR HINDER EMERGENCY
 RESPONDERS ACCESS TO THE STRUCTURE.
  
 3.) VERIFY THAT A NUMERICAL ADDRESS OF
 NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH IS POSTED ON THE BUILDING.
 SUITES/UNITS/APT NUMBERS OR ALPHABETS
 SHALL BE NO LESS THAN 3" IN HEIGHT IN
 THE VICINITY OF THE FRONT ENTRANCE AREA.
  
 4.) SMOKE ALARMS (DETECTORS) SHALL
 RECEIVE THEIR OPERATING POWER FROM THE
 BUILDING SERVICE ALONG WITH BATTERY
 BACK-UP CAPABILITY.
  
  
 PLEASE ADDRESS THE ABOVE IN YOUR
 COMMENTS OR GENERAL NOTES.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 11:43 Rev Time 0.00
Received By adarroug Date 2006-09-13 Time 11:43 Sent To  
Notes
2006-09-26 00:00:00TO "COMM" BD#22
2006-09-13 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-11 Cont ID  
Sent By mawillia Date 2006-09-11 Time 13:33 Rev Time 0.00
Received By mawillia Date 2006-07-17 Time 11:07 Sent To  
Notes
2006-07-28 00:00:00TO COMM BOARD #15 , NOT "BOB"
2006-07-17 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-09-11 Cont ID  
Sent By mawillia Date 2006-09-11 Time 13:32 Rev Time  
Received By mawillia Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-08-10 Cont ID  
Sent By kstevens Date 2006-08-10 Time 06:32 Rev Time 0.00
Received By kstevens Date 2006-08-10 Time 06:32 Sent To  
Notes
2006-08-10 00:00:00 
  
  
  
 NO PLUMBING PLANS REQUIRED, BUT ROUGH
 INSPECTION REQUIRED PRIOR TO COVERING TO
 DETERMING EXTENT OF FIRE DAMAGE, IF ANY,
 TO PIPING IN THE WALLS.
  
  
  
  
 .