Plan Review Details - Permit 06070726
Plan Review Stops For Permit 06070726
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-03 Cont ID  
Sent By alange Date 2006-10-03 Time 10:40 Rev Time 0.33
Received By alange Date 2006-10-03 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By alange Date 2006-07-27 Time 08:08 Rev Time 0.33
Received By alange Date 2006-07-27 Time 08:08 Sent To  
Notes
2006-07-27 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 19:45 Sent To M
Notes
2006-10-01 00:00:00*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW NOTES DUE TO REVISED PLANS
 SUBMITTED.
  
 1) NOTE: NO, PLEASE SEE DUE TO REVISED
 RISER, PELASE SEE SPECS NOW INDICATE A
 SE RATED ATS WHICH IS NOW NOT REQUIRED
 OF BEING FED FROM AN EXISTING METER MAIN
 WHICH CONTAINS OCP TO FEED THE PANEL
 "GP". PLEASE INDICATE THE OCP FROM TEH
 METER MAIN PANEL AND PLEASE SEE THE
 CONDUCTORS FROM THE METER MAINS AND TO
 THE PANEL "GP AND FROM GEN ARE UNCLEAR.
 SOME ARE MISSIGN AND THE OTHER
 CONDUCTORS WHICH SEEM TO BE SHOWN FROM
 GEN AND FROM ATS TO THE PANEL "GP" SEEM
 TO BE FUZZY FROM THE COPE?
 ** PLEASE CALL TO GO OVER WHAT IS NEEDED
 IF THAT MAY BE EASIER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARFIY THE USE OF THE
 SE RATED ATS AS THIS ATS CONTAINS A
 SERVICE ENTRANCE RATED MIN WHICH ONLY
 DISCONNECTS POWER ON THE LIN SIDE OF THE
 ATS.?
 PLEASE SEE THE EXISTING SERVICE CONTAIN
 THE REQUIRED "SERVICE ENTRANCE " RATED
 MAIN.
 A STANDARD ATS MAY BE USED AND A
 DISCONNECT IS REQUIRED FOR THE FEEDERS
 COMING FOMR THE GENERATOR GROUPED W/
 EXSITING MAINS OR THE PANEL GP CONTAINS
 A MCB.
 PLEASE CALL TO GO OVER POSSIBLE
 SCENERIOS.
 IFINSTALLING A DISCONNECT, THIS
 DISCONNECT DOES NOT NEED OCP, ONLY A
 DISCONNECTING MEANS.
 225.31-225.39, 230.72,230.2
  
 2) NOTE: NO, ?? PLEASE SEE COULD NOT
 LOCATE ANY INFORMATION WHETHER OR NOT
 THIS COUNDUIT IS FOR BRANCH CIRCUITS OR
 ???
 SIZE? ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE INFORMATION ON
 THE CONDUIT FROM PANEL "B"? IS THIS
 BRANCH CIRCUITS?
  
 3) NOTE: OK, LAYOUT PROVIDED, HOWEVER
 THE LARGER SET OF PLANS IS NOT NEEDED TO
 BE SUBMITTED.
 PLEASE BE SURE THART ALL PLANS SUBMITTED
 DO CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT AND LOCATION OVER VIEW
 , LIKE THE ONES SHOWN ON THE LARGE
 PLANS. AS ONLY THE INFORMATION FOR THE
 GEN NEEDS TO BE SUBMITTED. THIS CAN BE
 ON A 8 1/2 BY 11.
 106.1.2 FBC.
  
 4) NOTE: NO, FROM THE "SITE ALYOUT"
 SUBMITTED THE GEN DOES NOT INDICATE THE
 MINIMUM OF 3FT FROM STRUCTURE AND 5FT
 FOR EXHAUST FROM ANY OPENINGS.PLEASE SEE
 ZONING COMMENTS ALSO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, MIN CLEARENCE OF
 GEN FROM STRUCTURE OR WALL SHALL BE 3FT
 MIN BASED ON LTRS OBTAINED FROM
 MANUFCATURE. IF MIN CLEARNECES ARE LESS,
 PLEASE PROVIDE INFORMATION FROM
 MANUFCATURE. MUST BE ON THE SPECS OR
 FROM THE MANUFACTURE.
  
 ** SEE COMMENTS FROM OTHER TRADES.
  
 ** NEW NOTE **
 PLEASE SEE FS 553.80(2)(B) WHICH IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 09:13 Sent To M
Notes
2006-07-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE CLARFIY THE USE OF TEH
 SE RATED ATS AS THIS ATS CONTAINS A
 SERVICE ENTRANCE RATED MIN WHICH ONLY
 DISCONNECTS POWER ON THE LIN SIDE OF THE
 ATS.?
 PLEASE SEE THE EXISTING SERVICE CONTAIN
 THE REQUIRED "SERVICE ENTRANCE " RATED
 MAIN.
 A STANDARD ATS MAY BE USED AND A
 DISCONNECT IS REQUIRED FOR THE FEEDERS
 COMING FOMR THE GENERATOR GROUPED W/
 EXSITING MAINS OR THE PANEL GP CONTAINS
 A MCB.
 PLEASE CALL TO GO OVER POSSIBLE
 SCENERIOS.
 IFINSTALLING A DISCONNECT, THIS
 DISCONNECT DOES NOT NEED OCP, ONLY A
 DISCONNECTING MEANS.
 225.31-225.39, 230.72,230.2
  
 2) NOTE: PLEASE PROVIDE INFORMATION ON
 THE CONDUIT FROM PANEL "B"? IS THIS
 BRNACH CIRCUITS?
  
 3) NOTE: PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT AND LOCATION OVER VIEW
 , LIKE THE ONES SHOWN ON THE LARGE
 PLANS. AS ONLY THE INFORMATION FOR THE
 GEN NEEDS TO BE SUBMITTED. THIS CAN BE
 ON A 8 1/2 BY 11.
 106.1.2 FBC.
  
 4) NOTE: PLEASE KNOW, MIN CLEARENCE OF
 GEN FROM STRUCTURE OR WALL SHALL BE 3FT
 MIN BASED ON LTRS OBTAINED FROM
 MANUFCATURE. IF MIN CLEARNECES ARE LESS,
 PLEASE PROVIDE INFORMATION FROM
 MANUFCATURE. MUST BE ON THE SPECS OR
 FROM THE MANUFACTURE.
  
 ** SEE COMMENTS FROM OTHER TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By mperson Date 2006-10-02 Time 13:39 Rev Time 0.33
Received By mperson Date 2006-10-02 Time 13:39 Sent To B
Notes
2006-10-02 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. PLEASE BE ADVISED THAT THE GAS PERMIT
 ISSUED FOR SAID ADDRESS IS FOR A FUTURE
 GENERATOR AND A FUTURE POOL HEATER DUE
 TO THE FACT THAT AT THE TIME OF THE GAS
 PERMIT BEING ISSUED A GENERATOR AND POOL
 PERMIT WERE NOT APPLIED FOR. THIS ACTION
 WAS DISCUSSED IN A PHONE CONVERSATION
 WITH BILLY RODRIQUEZ FROM FLORIDA PUBLIC
 UTILITIES CO. BEFORE PERMIT WAS ISSUED.
 A REVISION IS NEEDED TO THE GAS PERMIT
 FOR THE GENERATOR GAS HOOK UP.
 PLEASE REFERENCE THE ATTACHED COPIES OF
 THE APPROVED GAS ISOMETRIC AND PERMIT
 INFORMATION INDICATING THIS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 13:56 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 13:56 Sent To E
Notes
2006-09-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 11:34 Sent To Z
Notes
2006-09-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 11:14 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 11:14 Sent To E
Notes
2006-07-18 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 11:33 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 16:08 Sent To  
Notes
2006-07-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 11:25 Rev Time 0.15
Received By tgordon Date 2006-10-02 Time 11:25 Sent To P
Notes
2006-10-02 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 11:15 Rev Time 0.15
Received By tgordon Date 2006-07-21 Time 11:15 Sent To P
Notes
2006-07-21 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
 2)PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-22 Cont ID  
Sent By mmclean Date 2006-09-22 Time 18:28 Rev Time 0.00
Received By mmclean Date 2006-09-22 Time 18:28 Sent To I
Notes
2006-09-22 00:00:00DENIED,
 1. THE NEW SITEPLAN PROVIDED DOES NOT
 GIVE A FULL LAYOUT OF THE PROPERTY AND
 SHOW ALL THAT IS AT THE PROPERTY, WITH
 DIMENSION OF COMPLETE LOT AND ADDRESS
 ETC.
 2. PLEASE PROVIDE INFORMATION ON THE
 SITEPLAN THAT WAS SUBMITTED (SETBACKS OF
 THE STRUCTURES AND PROPOSED GENERATOR)
 3. PLEASE PROVIDE A COPY OF CURRENT
 SURVEY FOR THIS PROPOSED PROJECT TO BE
 KEPT WITH FILE AS WELL TO VERIFY THE
 INFORMATION SUBMITTED ON SITEPLAN SHOWN
 CORRECTLY ON THE SITEPLAN (SETBACKS, LOT
 DIMENSION ETC).
  
 THANKS.
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 11:14 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 11:14 Sent To I
Notes
2006-07-16 00:00:00DENIED,
 1. NEED TO PROVIDE THE SETBACKS OF THE
 STRUCTURES (HOUSE & ART STUDIO/GUEST
 QUARTERS) ON THE SITE PLAN (2 SETS)
 (FRONT/SIDE/REAR).
 2. PLEASE PROVIDE A COPY OF THE CURRENT
 SURVEY.
  
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A REQUIRED SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720