| 2006-10-01 00:00:00 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG |
| | WITH NEW NOTES DUE TO REVISED PLANS |
| | SUBMITTED. |
| | |
| | 1) NOTE: NO, PLEASE SEE DUE TO REVISED |
| | RISER, PELASE SEE SPECS NOW INDICATE A |
| | SE RATED ATS WHICH IS NOW NOT REQUIRED |
| | OF BEING FED FROM AN EXISTING METER MAIN |
| | WHICH CONTAINS OCP TO FEED THE PANEL |
| | "GP". PLEASE INDICATE THE OCP FROM TEH |
| | METER MAIN PANEL AND PLEASE SEE THE |
| | CONDUCTORS FROM THE METER MAINS AND TO |
| | THE PANEL "GP AND FROM GEN ARE UNCLEAR. |
| | SOME ARE MISSIGN AND THE OTHER |
| | CONDUCTORS WHICH SEEM TO BE SHOWN FROM |
| | GEN AND FROM ATS TO THE PANEL "GP" SEEM |
| | TO BE FUZZY FROM THE COPE? |
| | ** PLEASE CALL TO GO OVER WHAT IS NEEDED |
| | IF THAT MAY BE EASIER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARFIY THE USE OF THE |
| | SE RATED ATS AS THIS ATS CONTAINS A |
| | SERVICE ENTRANCE RATED MIN WHICH ONLY |
| | DISCONNECTS POWER ON THE LIN SIDE OF THE |
| | ATS.? |
| | PLEASE SEE THE EXISTING SERVICE CONTAIN |
| | THE REQUIRED "SERVICE ENTRANCE " RATED |
| | MAIN. |
| | A STANDARD ATS MAY BE USED AND A |
| | DISCONNECT IS REQUIRED FOR THE FEEDERS |
| | COMING FOMR THE GENERATOR GROUPED W/ |
| | EXSITING MAINS OR THE PANEL GP CONTAINS |
| | A MCB. |
| | PLEASE CALL TO GO OVER POSSIBLE |
| | SCENERIOS. |
| | IFINSTALLING A DISCONNECT, THIS |
| | DISCONNECT DOES NOT NEED OCP, ONLY A |
| | DISCONNECTING MEANS. |
| | 225.31-225.39, 230.72,230.2 |
| | |
| | 2) NOTE: NO, ?? PLEASE SEE COULD NOT |
| | LOCATE ANY INFORMATION WHETHER OR NOT |
| | THIS COUNDUIT IS FOR BRANCH CIRCUITS OR |
| | ??? |
| | SIZE? ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE INFORMATION ON |
| | THE CONDUIT FROM PANEL "B"? IS THIS |
| | BRANCH CIRCUITS? |
| | |
| | 3) NOTE: OK, LAYOUT PROVIDED, HOWEVER |
| | THE LARGER SET OF PLANS IS NOT NEEDED TO |
| | BE SUBMITTED. |
| | PLEASE BE SURE THART ALL PLANS SUBMITTED |
| | DO CONTAIN THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS AND DESIGN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE A LAYOUT OF ALL |
| | SERVICE EQUIPMENT AND LOCATION OVER VIEW |
| | , LIKE THE ONES SHOWN ON THE LARGE |
| | PLANS. AS ONLY THE INFORMATION FOR THE |
| | GEN NEEDS TO BE SUBMITTED. THIS CAN BE |
| | ON A 8 1/2 BY 11. |
| | 106.1.2 FBC. |
| | |
| | 4) NOTE: NO, FROM THE "SITE ALYOUT" |
| | SUBMITTED THE GEN DOES NOT INDICATE THE |
| | MINIMUM OF 3FT FROM STRUCTURE AND 5FT |
| | FOR EXHAUST FROM ANY OPENINGS.PLEASE SEE |
| | ZONING COMMENTS ALSO. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, MIN CLEARENCE OF |
| | GEN FROM STRUCTURE OR WALL SHALL BE 3FT |
| | MIN BASED ON LTRS OBTAINED FROM |
| | MANUFCATURE. IF MIN CLEARNECES ARE LESS, |
| | PLEASE PROVIDE INFORMATION FROM |
| | MANUFCATURE. MUST BE ON THE SPECS OR |
| | FROM THE MANUFACTURE. |
| | |
| | ** SEE COMMENTS FROM OTHER TRADES. |
| | |
| | ** NEW NOTE ** |
| | PLEASE SEE FS 553.80(2)(B) WHICH IS ONLY |
| | A NOTICE GIVEN AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |