| 2007-05-01 12:08:16 | *** UNSAT 4TH REVIEW*** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH |
| | STILL NEEDS TO BE CLARIFIED OR ADDRESSED. |
| | AS MANY ITEMS ON PLANS HAVE BEEN REVISED FROM THE LAST |
| | SET OF REVIEWED PLANS THERE ARE SEVERAL NEW COMMENTS |
| | WHICH ARE BASED ON THE REVISIONS MADE TO PLANS WHICH |
| | ARE NOT THE SAME AS PREVIOUSLY SUBMITTED PLANS. PLEASE |
| | SEE SOME OF THE COMMENTS ARE THE SAME FROM PREVIOUS |
| | REVIEW. RECORD AS SHOWN. |
| | |
| | |
| | 1) NOTE: PLEASE SEE SOME CIRCUITS ARE MISSING FROM |
| | PLANS AND SOME OF THE CIRCUITING ON PLANS DOES NOT |
| | COORDINATE WITH THE PANEL SCHEDULE SUBMITTED. PLEASE |
| | SEE SOME OF THE CIRCUITS ON PANEL SCHEDULE ARE |
| | REPEATED. |
| | PLEASE SEE THAT THE USE OF GEN LTS ETC MAY NOT BE USED. |
| | ROOMS AND AREAS ARE TO BE SPECIFIC. PLEASE SEE THE |
| | FOLLOWING TEXT WHICH IS EXTRACTED FROM THE CODE. |
| | ** CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.** |
| | PLEASE SEE THAT THIS CIRCUITING SHALL CORRELATE WITH |
| | THE SUBMITTED PANEL SCHEDULE. 408.4, 310.16 |
| | |
| | |
| | 2) NOTE:PLEASE SEE MISSING REQUIRED DEDICATED |
| | CIRCUITS FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM |
| | CIRCUITS PER 210.52B1, 210.11C1, 220.16 |
| | THIS IS THE SAME COMMENT AS TWO SMALL APPLIANCE |
| | CIRCUITS ARE SHOWN HOWEVER ONLY ONE IN THE KITCHEN AND |
| | ONE IN THE DINING ROOM. THE KITCHEN REQUIRES TWO |
| | CIRCUITS AT A MINIMUM. PLEASE SEE THE DINING AREA IS |
| | PERMITTED TO BE ON ONE OR *MORE* OF THE SMALL APPLIANCE |
| | CIRCUITS.( IF MORE THAN TWO, THEN 1500VA WOULD BE |
| | SHOULD FOR EACH ONE OVER THE TWO MINIMUM) |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM THE NEW J-BOX TO THE NEW PANEL. PLEASE |
| | ALSO NOT ON PLANS, THAT IF THE EXISTING CONDUIT FROM |
| | THE EXISTING METER AND MAIN DOES NOT CONTAIN AN |
| | EQUIPMENT GROUNDING CONDUCTOR, ONE WILL BE REQUIRED TO |
| | BE INSTALLED OR WORDS TO THAT EFFECT. PLEASE KNOW IF |
| | THE EXISTING CONDUIT GROUNDING IN THE STRUCTURE IS |
| | RIGID AND NOT EMT, THEN AN EXISTING PATH TO THIS J-BOX |
| | MAY BE ADEQUATE. |
| | 250.24, 250.110, 250.122. |
| | |
| | 4) NOTE: PLEASE CORRELATE THE ITEMS/CIRCUITS SHOWN ON |
| | LOAD CALCULATIONS WITH THE CIRCUITS AS SHOWN ON PANEL |
| | SCHEDULE. |
| | PLEASE SEE PANEL SCHEDULE IS MISSING THE LAUNDRY |
| | CIRCUIT AS SHOWN ON THE LOAD CALCULATIONS. |
| | PLEASE SEE THE LOAD FOR THE WATER HEATER IS SHOWN AS |
| | 3KW ON LOAD CALCULATIONS AND THE LOAD ON THE PANEL |
| | SCHEDULE IS SHOWN AS 4.5 KW. PLEASE SEE THE NEXT |
| | COMMENT FOR WATER HEATER. |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD ON THE PANEL SCHEDULE AND |
| | LOAD CALCULATIONS BOTH WHICH ARE SHOWN AS 3KW AND 4.5KW |
| | EXCEED THAT OF THE CONDUCTORS, RATING OF THE BREAKER |
| | AND IS ONLY SHOWN AS 120V? |
| | PLEASE SEE 422.13 AS THE MINIMUM SIZING FOR THIS |
| | CIRCUIT MUST BE DONE AT 125% INCLUDING LOAD, OCP AND |
| | CONDUCTOR SIZES. |
| | PLEASE COORDINATE THE ACTUAL WATER HEATER SIZE AND GO |
| | FROM THERE. |
| | |
| | 6) NOTE: PLEASE SEE MISSING RECEPT(S) TO BE LOCATED PER |
| | 210.52 (SEE BEDROOM WALL) |
| | |
| | 7) NOTE:THIS IS THE SAME NOTE: IF THESE ARE 110V, |
| | BATTERY BACK UP DEVICES WHICH ACTUALLY DETECT AND SOUND |
| | AN ALARM, THEN THESE ARE * SMOKE ALARMS* |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS 110V W/ |
| | BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD WHICH |
| | MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72 DEFINITIONS AS |
| | A SMOKE DETECTOR IS IN FACT A DEVICE WHICH ONLY DETECTS |
| | AND IS PART OF A FIRE ALARM SYSTEM. IF THIS DEVICE IS |
| | INDEED A DEVICE WHICH DETECTS AND SOUNDS, THEN THIS |
| | DEVICE SHOULD BE SHOWN AND NOTED AS "SA" AS A SMOKE |
| | ALARM DEVICE. |
| | R313 2004 FBC, NFPA-72 2002 11.5, 11.8 |
| | PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA |
| | THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND |
| | SHALL BE INDICATED AS SUCH. |
| | |
| | 8) NOTE: SAME NOTE, PLEASE SEE ONLY ONE CIRCUIT IS |
| | BEING NOTED AS BEING AFCI PROTECTED WHEN THE SMOKE |
| | DEVICES ALSO REQUIRE PROTECTION. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN FOR |
| | RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI |
| | PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS. |
| | PLEASE LIST CIRCUITS ON PANEL SCHEDULE. |
| | PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM? |
| | |
| | 9) NOTE:PLEASE SEE 210.4 AS THE DISHWASHER AND |
| | DISPOSAL ARE NOW BEING SHOWN ON THE SAME DEVICE, YET ON |
| | TWO DIFFERENT CIRCUITS? PLEASE SEE THE SECTION ABOVE AS |
| | IF BOTH ARE ON THE SAME DEVICE/YOKE, THEN THIS WOULD BE |
| | REQUIRED TO BE A 2-POLE BREAKER. PLEASE REVISE PANEL. |
| | |
| | 10) NOTE: PLEASE SEE THE NEW BATH CIRCUIT WHICH IS |
| | NOTED ON PANEL SCHEDULE INDICATES A LOAD OF 5KW. PLEASE |
| | CLARIFY HOW THIS IS POSSIBLE? |
| | PLEASE ALSO SEE THIS SAME BATH CIRCUIT IS BEING NOTED |
| | AND SHOWN FEEDING THE LIVING ROOM RECEPTACLES WHICH IS |
| | NOT PERMITTED. |
| | PLEASE SEE 210.52D, 210.11C3 AS BATH GFI MAY NOT FEED |
| | OTHER AREAS, ONLY THE BATH. |
| | |
| | 11) NOTE: PLEASE SEE THE OCCUPANCY IS NOTED AS |
| | *ANCILLARY/MAIL ROOM*? |
| | THE R-2 APPEARS TO BE CORRECT HOWEVER NOT SURE WHERE A |
| | MAIL ROOM COMES INTO AFFECT.? |
| | FBC 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |