| Plan Review Stops For Permit 06070683 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-08-16 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-16 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-16 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2006-08-16 00:00:00 | OWNER INFO WAS UPDATED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-04-14 |
Time |
14:57 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-04-14 |
Time |
14:57 |
Sent To |
PC |
|
| Notes |
| 2008-04-14 14:59:04 | LETTER EMEMPT LOCATION TO FIRE SPRINKLERS, BUILDING | | | STIPULATION NO MERCHANDISE ON EXTERIOR OF BUILDING. | | | | | | 903.3.1.1.1 EXEMPT LOCATIONS. | | | | | | AUTOMATIC SPRINKLERS SHALL NOT BE REQUIRED IN THE | | | FOLLOWING ROOMS OR AREAS WHERE SUCH ROOMS OR AREAS ARE | | | PROTECTED WITH AN APPROVED AUTOMATIC FIRE DETECTION | | | SYSTEM IN ACCORDANCE WITH SECTION 907.2 THAT WILL | | | RESPOND TO VISIBLE OR INVISIBLE PARTICLES OF | | | COMBUSTION. SPRINKLERS SHALL NOT BE OMITTED FROM ANY | | | ROOM MERELY BECAUSE IT IS DAMP, OF | | | FIRE-RESISTANCE-RATED CONSTRUCTION OR CONTAINS | | | ELECTRICAL EQUIPMENT. | | | (4)IN ROOMS OR AREAS THAT ARE OF NONCOMBUSTIBLE | | | CONSTRUCTION WITH WHOLLY NONCOMBUSTIBLE CONTENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-04-10 |
Time |
07:59 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2008-04-10 |
Time |
07:59 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-05 |
Time |
13:36 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2008-02-05 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-02-05 13:37:01 | REV: 3 & 4 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-07-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-07-30 |
Time |
10:17 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-07-30 |
Time |
10:17 |
Sent To |
PC |
|
| Notes |
| 2007-07-30 10:18:13 | 6901 OKEECHOBEE BLVD. / 06070683 | | | BUILDING PROVISOS: | | | | | | 1) ROOFING PERMIT TO BE A SEPARATE PERMIT WITH | | | ASSOCIATED FEES AND REVIEW, NOTE THE HIGHLIGHTED | | | SUBSYSTEM REQUIRES ENHANCED FASTENING. | | | THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD | | | THE FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, | | | AS DETERMINED BY THEBUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNEDAND SEALED BY A | | | FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT ORREGISTERED ROOF CONSULTANT MAY BE | | | SUBMITTED. PLEASE PROVIDE THE RAS 117 CALCULATIONS FOR | | | ROOFING SUB-PERMIT. | | | | | | 2) RULE 9B-72 REQUIRES TESTING FOR ROOF ACCESS HATCHES, | | | CURRENTLY THERE ARE NO ROOF HATCHES THAT HAVE APPLIED | | | FOR STATE APPROVAL. BEFORE A CERTIFICATE OF COMPLETION | | | WILL BE ISSUED, THE CONTRACTOR SHALL EITHER OBTAIN A | | | PRODUCT APPROVAL THROUGH THE STATE WEBSITE THAT WILL | | | MEET THE | | | WIND PRESSURES OR APPLY AND RECEIVE LOCAL PRODUCT | | | APPROVAL WITHIN THIS JURISDICTION. THE CITY OF WEST | | | PALM BEACH HAS THE SAME 10 CRITERIA AS THE STATE | | | APPROVAL INCLUSIVE OF THIRD PARTY QUALITY ASSURANCE | | | PROGRAM, WITH THE THIRD PARTY BEING APPROVED THROUGH | | | THE STATE. | | | | | | 3)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE | | | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED | | | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. | | | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH | | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE | | | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN | | | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH | | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH | | | WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR | | | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS | | | WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED | | | SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN | | | ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO | | | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE | | | PURSUANT TO SECTION 113 OF THIS CHAPTER. | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-29 |
Time |
13:53 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2007-06-29 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2007-06-29 13:55:34 | CONT:PLAN REVIEW | | | KATIE GRINDEL (913)236-3437 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 4TH REVIEW | | | ACTION: DENIED | | | | | | NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO | | | THE FBC 2004 WITH 2006 REVISIONS. | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3-8) COMPLIED. | | | | | | 10A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A-E) COMPLIED | | | F)ROOFING ASSEMBLIES THERE ARE CURRENTLY SUBMITTED ARE | | | FOUR (4) DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED | | | TO THE CITY: | | | JOHN MANVILLE FL 1037-R1HASTHE BRR | | | ARCHITECTURAL REVIEW STAMP | | | JOHN MANVILLE FL644-R2HASTHE BRR | | | ARCHITECTURAL REVIEW STAMP | | | JOHN MANVILLE FL2948-R1NOT REVIEWED | | | GAF FL618-R1HASTHE BRR | | | ARCHITECTURAL REVIEW STAMP | | | | | | | | | GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED IN | | | THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET THE | | | MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT THE | | | INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE NOT | | | HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND ASSOCIATED | | | PRESSURES WILL BE USED. PAGES 7-19, PLEASE HIGHLIGHT | | | AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF GENERAL | | | LIMITATION # 7 | | | IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING | | | PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF | | | LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN | | | TAKE PLACE. | | | G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN | | | HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA | | | COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED | | | (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED | | | WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH | | | SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES | | | 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES | | | LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND | | | ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE | | | THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS | | | INDICATED NO ENHANCED FASTENING CAN TAKE PLACE. | | | H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE | | | ADVISORY BOARD TECHNICAL ADVISORY | | | I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY | | | THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO | | | PICK FROM WHICH ARE YOU GOING TO USE? | | | | | | | | | JOHN MANSVILLE REPORT FL644-R2 MIAMI-DADE NOA SHEET 11 | | | ISSTARRED, THE MAXIMUM DESIGN PRESSURE IS -52.5 | | | LIMITATION NUMBER (7) REQUIRES AN ENGINEER , ARCHITECT | | | OR REGISTERED ROOFING CONSULTANT TO RUN THE RAS 117 | | | CALCULATION FOR ROOF ZONES 2 & 3.IF THIS PRODUCT IS | | | PICKED PLEASE REMOVE ALL OTHER ROOFING APPROVALS FROM | | | THE PACKAGE. | | | | | | THERE ARE TWO OTHER JOHN MANVILLE PRODUCT APPROVALS | | | WITH NOTHING HIGHLIGHTED. | | | | | | | | | 10B) OUTSWING STEEL DOOR BY REPUBLIC BUILDERS HAS NOT | | | BEEN APPROVED BY THE DESIGNER OF RECORD, PLEASE REVIEW | | | AND STAMP WITH SHOP DRAWING STAMP. | | | | | | 11) COMPLIED. | | | | | | 12) ROOF HATCHES: IF THERE ARE NO STATE OR MIAMI-DADE | | | REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT | | | WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN | | | OPTION. THE ROOF HATCH SUBMITTAL FROM BABCOCK-DAVIS | | | DOES NOT MEET THE REQUIREMENTS FOR A LOCAL PRODUCT | | | APPROVAL THERE HAS TO BE AN INDEPENDENT TEST DONE BY A | | | LAB LISTED ON THE STATE WEB SITE PLUS THETHIRD PARTY | | | QUALITY ASSURANCEENTITY THAT ARE ALSO LISTED ON THE | | | STATE WEBSITE | | | ADDRESS IS FLORIDABUILDING.ORG. | | | NOTE; BILCO HATCH IS CURRENTLY UNDERGOING TESTING AND | | | IS SUPPOSE TO HAVE REPORTS BY THE END OF SUMMER. | | | | | | 13) COMPLIED. | | | | | | 14) COVERSHEET MAXIMUM FLOOR AREA ALLOWABLE REFRENENCES | | | THE 2003 IBC PLEASE CORRECT. | | | | | | 15) COMPLIED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-04-03 |
Time |
08:18 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-04-03 |
Time |
08:18 |
Sent To |
PC |
|
| Notes |
| 2007-06-27 18:57:55 | ADD: 6901 OKEECHOBEE BLVD. | | | CONT:PLAN REVIEW | | | KATIE GRINDEL (913)236-3437 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 4TH REVIEW | | | ACTION: DENIED | | | | | | NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO | | | THE FBC 2004 WITH 2006 REVISIONS. | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3-8) COMPLIED. | | | | | | 10A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A-E) COMPLIED | | | F)ROOFING ASSEMBLIES THERE ARE CURRENTLY SUBMITTED ARE | | | FOUR (4) DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED | | | TO THE CITY: | | | JOHN MANVILLE FL 1037-R1HASTHE BRR | | | ARCHITECTURAL REVIEW STAMP | | | JOHN MANVILLE FL644-R2HASTHE BRR | | | ARCHITECTURAL REVIEW STAMP | | | JOHN MANVILLE FL2948-R1NOT REVIEWED | | | GAF FL618-R1HASTHE BRR | | | ARCHITECTURAL REVIEW STAMP | | | | | | | | | GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED IN | | | THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET THE | | | MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT THE | | | INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE NOT | | | HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND ASSOCIATED | | | PRESSURES WILL BE USED. PAGES 7-19, PLEASE HIGHLIGHT | | | AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF GENERAL | | | LIMITATION # 7 | | | IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING | | | PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF | | | LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN | | | TAKE PLACE. | | | G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN | | | HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA | | | COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED | | | (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED | | | WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH | | | SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES | | | 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES | | | LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND | | | ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE | | | THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS | | | INDICATED NO ENHANCED FASTENING CAN TAKE PLACE. | | | H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE | | | ADVISORY BOARD TECHNICAL ADVISORY | | | I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY | | | THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO | | | PICK FROM WHICH ARE YOU GOING TO USE? | | | | | | | | | JOHN MANSVILLE REPORT FL644-R2 MIAMI-DADE NOA SHEET 11 | | | ISSTARRED, THE MAXIMUM DESIGN PRESSURE IS -52.5 | | | LIMITATION NUMBER (7) REQUIRES AN ENGINEER , ARCHITECT | | | OR REGISTERED ROOFING CONSULTANT TO RUN THE RAS 117 | | | CALCULATION FOR ROOF ZONES 2 & 3.IF THIS PRODUCT IS | | | PICKED PLEASE REMOVE ALL OTHER ROOFING APPROVALS FROM | | | THE PACKAGE. | | | | | | THERE ARE TWO OTHER JOHN MANVILLE PRODUCT APPROVALS | | | WITH NOTHING HIGHLIGHTED. | | | | | | | | | 10B) OUTSWING STEEL DOOR BY REPUBLIC BUILDERS HAS NOT | | | BEEN APPROVED BY THE DESIGNER OF RECORD, PLEASE REVIEW | | | AND STAMP WITH SHOP DRAWING STAMP. | | | | | | 11) COMPLIED. | | | | | | 12) ROOF HAATCHES: IF THERE ARE NO STATE OR MIAMI-DADE | | | REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT | | | WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN | | | OPTION. THE ROOF HATCH SUBMITTAL FROM BABCOCK-DAVIS | | | DOES NOT MEET THE REQUIREMENTS FOR A LOCAL PRODUCT | | | APPROVAL THERE HAS TO BE AN INDEPENDENT TEST DONE BY A | | | LAB LISTED ON THE STATE WEB SITE PLUS THETHIRD PARTY | | | QUALITY ASSURANCEENTITY THAT ARE ALSO LISTED ON THE | | | STATE WEBSITE | | | ADDRESS IS FLORIDABUILDING.ORG. | | | NOTE; BILCO HATCH IS CURRENTLY UNDERGOING TESTING AND | | | IS SUPPOSE TO HAVE REPORTS BY THE END OF SUMMER. | | | | | | 13) COVERSHEET BUILDING TYPE IS AGAIN WRONG, THIS IS | | | NOT A TYPE 5B BUILDING IS A 4HR FIRE WALL A TYPE IIIB | | | MERCANTILE AND OR BUSINESS OCCUPANCY | | | HAS UNLIMITED AREA WHEN FULLY SPRINKLED AND 60 FT | | | CLEARENCE AROUND THE BUILDING. SEE SECTION 507.2 | | | | | | 14) COVERSHEET MAXIMUM FLOOR AREA ALLOWABLE REFRENENCES | | | THE 2003 IBC PLEASE CORRECT. | | | | | | 15) COVERSHEET: TOTAL SQ FT BUILDING SIZELISTED IS | | | 50,790 THIS IS THIS TENANT SPACE, NOT BUILDING SQ FT | | | UNLESS THERE ARE 4 HR WALLS ON EACH SIDE OF THE | | | BUILDING! PLANS DO NOT INDICATE THIS! | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | 2007-04-03 08:20:00 | "PLAN REVIEW" I | | | PERMIT: 06070683 | | | ADD: 6901 OKEECHOBEE BLVD. | | | CONT:PLAN REVIEW | | | KATIE GRINDEL (913)236-3437 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO | | | THE FBC 2004 WITH 2006 REVISIONS. | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3-8) COMPLIED. | | | | | | 10) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A-E) COMPLIED | | | F) GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED | | | IN THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET | | | THE MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT | | | THE INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE | | | NOT HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND | | | ASSOCIATED PRESSURES WILL BE USED. PAGES 7-19, PLEASE | | | HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF | | | GENERAL LIMITATION # 7 | | | IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING | | | PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF | | | LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN | | | TAKE PLACE. | | | G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN | | | HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA | | | COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED | | | (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED | | | WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH | | | SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES | | | 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES | | | LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND | | | ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE | | | THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS | | | INDICATED NO ENHANCED FASTENING CAN TAKE PLACE. | | | H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE | | | ADVISORY BOARD TECHNICAL ADVISORY | | | I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY | | | THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO | | | PICK FROM WHICH ARE YOU GOING TO USE? | | | | | | 11) COMPLIED. | | | | | | 12) ROOF HAATCHES: IF THERE ARE NO STATE OR MIAMI-DADE | | | REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT | | | WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN | | | OPTION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-12-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-12-12 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-12-12 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2006-12-12 14:04:42 | | | | "PLAN REVIEW" I | | | PERMIT: 06070683 | | | ADD: 6901 OKEECHOBEE BLVD. | | | CONT:PLAN REVIEW | | | KATIE GRINDEL (913)236-3437 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO | | | THE FBC 2004 WITH 2006 REVISIONS. | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) COMPLIED. | | | | | | 4A) THE THREE NUMBERS SUPPLIED ON THE PLAN FOR THE | | | CERTIFICATE OF AUTHORIZATION NONE ARE THE COA FOR | | | FLORIDA. | | | PLEASE PROVIDE THIS NUMBER ON ALL SHEETS REQUIRED, | | | AA26001022 | | | | | | 4B) THE OTHER ISSUE WITH THE DBA NAME IS BOICE RAIDL | | | RAIDL ARCHITECTECTS INC. NOT THE BRR. | | | | | | 5) THIS REQUEST IS FOR THE WHOLE BUILDING, NOT TENANT | | | SPACE, UNLESS THE DEMISSING WALLS ARE 4 HR FIRE WALLLS | | | BREAKING THIS TENANT SPACE INTO A SEPERATE BUILDING WE | | | NEED THE AREA FOR THE COMPLETE BUILDINGPLEASE SHOW THE | | | AREA INCREASES ON THE PLANS THE NOTE SUBMITTALS ARE | | | THROWN OUT ONCE THE PERMIT IS ISSUED. TABLE 503. 5) | | | SHEET C-1 BUILDING CODE SUMMARY, TYPE | | | OF CONSTRUCTION, PLANS INDICATE A VB, | | | FOR MERCANTILE TABLE 503 INDICATES AN | | | ALLOWABLE 9,000 SQ FT. PLEASE PROVIDE | | | WHAT INCREASES WERE TAKEN TO ACHIEVE THE | | | 49,960 SQ FT OF ACTUAL BUILDING?PROVIDE | | | CALCULATIONS.NOW THIS IS GOING TO BE FOR | | | THE BUILDING NOT TENANT SPACE!!!!! | | | | | | 6) COMPLIED. | | | | | | 7) COMPLIED. | | | | | | 8) MOST OF THE PRODUCT APPROVALS THAT HAVE FLORIDA | | | REPORTS HAVE BEEN PRINTED. | | | THERE IS A COMMENT ON EACH REPORT THAT STILL REQUIRES | | | FLORIDA APPROVAL COVER SHEETS.PRODUCT APPROVALS | | | SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 9) 2ND REQUEST,THE DESIGN PROFESSIONALS STILL HAVE | | | NOT REVIEWED AND APPROVED ANY REPORTS, | | | )W P B ADMINISTRTIVE CODE 106.3.3* | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | | | | 10) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) OVERHEAD DOORS - COMPLIED. | | | B) STANLEY ACCESS- COMPLIED. | | | C) REPUBLIC BUILDERS PRODUCTS- COMPLIED. | | | D) CURRIES EXTERIOR DOORS- COMPLIED | | | E)CECO DOORS NEED THE MANUFACTURERS RECOMENDED | | | ERECTIION INSTRUCTION, INSPECTOR TO VERIFY THE PSF ON | | | SITE. | | | F) GAF BUILT UP ROOF NO SUBSYSTEM HAS BEEN HIGHLIGHTED | | | AS TO WHICH WILL BE USED, PLEASE NOTE LIMITATIONS.G) | | | JOHNS MANVILEE MODIFIED SAME COMMENT AS ABOVE. H) ROOF | | | HATCHES RULE 9B-72 THE REVISIONS EFFECTIVE 1-01-06 | | | REQUIRE PRE-ENGINEERED | | | ROOF ACCESS HATCHES TO HAVE APPROVALS. ACOPY OF THIS | | | STATEMENT IS ATTACHED. | | | I) PRE-ENGINEERED A/C STANDS- NOT CURBS CURBS ARE SHOWN | | | DETIAL# 3 S-5. | | | | | | 12) DEALS WITH THE REQUIRIMENT FOR PRODUCT APPROVALS | | | SEE 10H AND ATTACHMENT. BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-09-01 |
Time |
13:01 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2006-09-01 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-10 |
Time |
09:37 |
Rev Time |
10.00 |
| Received By |
jwitmer |
Date |
2006-08-10 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2006-08-10 00:00:00 | BUILDING PLAN REVIEW | | | | | | "PLAN REVIEW" I | | | PERMIT: 06070683 | | | ADD: 6901 OKEECHOBEE BLVD. | | | CONT:PLAN REVIEW | | | KATIE GRINDEL (913)236-3437 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) SEE ALL ARCHITECTURAL SHEETS | | | SIGNATURES ARE COPIES, PLANS ARE | | | REQUIRED TO BE ORIGINAL SIGNATURES. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 4) CERTIFICATE OF AUTHORIZATION REQUIRED | | | FOR ARCHITECTURAL FIRM. 481.219 F.S. | | | CERTIFICATE OF AUTHORIZATION.THE TITLE | | | BLOCK FOR ANY SHEET BEARING THE NAME OF | | | AN ARCHITECT PRACTICING UNDER A | | | FICTITIOUS NAME, A CORPORATION, OR A | | | PARTNERSHIP, OFFERING ARCHITECTURAL | | | SERVICES, SHALL INCLUDE THE CERTIFICATE | | | OF AUTHORIZATION | | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 5) SHEET C-1 BUILDING CODE SUMMARY, TYPE | | | OF CONSTRUCTION, PLANS INDICATE A VB, | | | FOR MERCANTILE TABLE 503 INDICATES AN | | | ALLOWABLE 9,000 SQ FT. PLEASE PROVIDE | | | WHAT INCREASES WERE TAKEN TO ACHIEVE THE | | | | | | 49,960 SQ FT OF ACTUAL BUILDING?PROVIDE | | | CALCULATIONS.NOW THIS IS GOING TO BE FOR | | | THE BUILDING NOT TENANT SPACE!!!!! | | | | | | 6) PLANS DO NOT MENTION 2004 EXISTING | | | BUILDING CODE AND THE REQUIREMENT 301.5 | | | 301.5 A DESIGN PROFESSIONAL OR AN | | | OWNER MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO SECTION | | | 303,304 & 305 OF THIS CODE. | | | | | | 7) SOILS REPORT IS A COPY NOT AN | | | ORIGINAL SIGNATURE. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 8) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 9) W P B ADMINISTRTIVE CODE 106.3.3* | | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 10) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) OVERHEAD DOOR WILL REQUIRE FL | | | COVERSHEET AND ASSOCIATED REPORT. | | | B) STANLEY ACCESS TECHNOLOGIES WILL | | | REQUIRE FL COVER SHEET AND ASSOCIATED | | | REPORT. | | | C) GAF MATERIAL REQUIRES FL COVERSHEET. | | | | | | 11)THIS ROOF IS MISSING OR NOT IN | | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | | | | ___ CONTRACTOR DID NOT PROVIDE THE MEAN | | | | | | ROOF HEIGHT. | | | | | | ___ CONTRACTOR DID NOT INDICATE THE ROOF | | | PITCH. | | | | | | __X_ CONTRACTOR FAILED TO INDICATE WHICH | | | SYSTEM TO BE USED. | | | | | | _X__ THE SYSTEM PROVIDED HAS A LOW | | | PRESSURE FOR ZONE ___ . | | | | | | _X__ THE SYSTEM PROVIDED STATES | | | LIMITATION# 7, SHOULD THE FASTENER | | | RESISTANCE BE LESS THAN THAT | | | REQUIRED, AS DETERMINED BY THE | | | BUILDING OFFICIAL, A REVISED | | | FASTENER SPACING, PREPARED , SIGNED | | | AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOF | | | CONSULTANT MAY BE SUBMITTED. | | | | | | ___THE SYSTEM PROVIDED INDICATES | | | LIMITATION# 9, NO ENHANCED | | | FASTENING ALLOWED. | | | | | | 12) ROOF HATCH IS THIS NEW? IF SO | | | PROVIDE PRODUCT APPROVAL FOR UNIT. | | | | | | 13) PROVIDE INFORMATION ON THE | | | ATTACHMENT OF CURBING FOR A/C UNITS. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
F |
Date |
2008-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-13 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-13 |
Time |
15:33 |
Sent To |
PC |
|
| Notes |
| 2008-06-13 15:37:39 | ** DENIED** | | | | | | 1) NOTE: ELECTRICAL PERMIT IS ALREADY CLOSED AND | | | FINALED OUT. NO FURTHER ELECTRICAL REVISIONS MAY BE | | | SUBMITTED, STAMPED OR REVIEWED. MAY APPLY FOR NEW | | | ELECTRICAL PERMIT AND SUBMIT REVISIONS UP UNTIL | | | BUILDING PERMIT IS CLOSED OUT. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2008-03-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-17 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-17 |
Time |
18:26 |
Sent To |
|
|
| Notes |
| 2008-03-17 18:26:25 | REVISIONS OK, | | | STAMPED ELECTRICAL PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-29 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-29 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2008-01-29 09:11:32 | REVISED SHEETS E1,1.1,1.2,2,2.1,4, 4.1,4.2, RE-1, | | | REM-1, EM-1 | | | | | | ** | | | *** FOR INFORMATION FOR THIS REVISION AND ANY OTHER | | | REVISION. PLEASE BE SURE THE SCOPE OF WORK FOR | | | REVISIONS ACTUALLY CORRELATE WITH PLANS. PLEASE SEE FOR | | | EXAMPLE THE SCOPE OF WORK AS SUBMITTED WITH REVISIONS | | | CONTAINS SUBSTANTIALLY LESS ITEMS THAN WHAT IS REVISED | | | ON PLANS. | | | THE ACCURACY OF THIS SCOPE OF WORK CHANGES GREATLY | | | AFFECT THE REVIEW TIMES OF SAID PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-31 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-30 |
Time |
15:29 |
Sent To |
PC |
|
| Notes |
| 2007-07-31 09:34:09 | | | | | | | REDLINED, | | | CONTROL REQUIRED FOR DOCK LIGHTS, 13-415.1.ABC.1.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-10 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-09 |
Time |
20:05 |
Sent To |
I |
|
| Notes |
| 2007-07-10 11:56:19 | 2007-07-10 11:56:19 | | | | | | **** UNSAT 6THREVIEW **** | | | | | | ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. | | | | | | | | | 1) NOTE: PLEASE SEE THERE ARE SOME ITEMS ON THE ENERGY | | | CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS. PLEASE | | | KNOW THAT THIS IS THE FIRST REVIEW OF THE INPUT DATA | | | REPORT AS IT WAS NOT SUBMITTED ON THE LAST REVIEW. THIS | | | WAS NOTED ON PREVIOUS REVIEW. | | | PLEASE BE SURE ALL AREAS WHICH ARE DESIGNATED ON PLANS | | | ARE THAT OF THE SAME AREAS AS DESIGNATED ON THE ENERGY | | | CALCULATIONS. PLEASE SEE SOME OF THESE AREAS ARE | | | MISSING AND/OR DO NOT COORDINATE AT THIS TIME. PLEASE | | | SEE IT IS NOT POSSIBLE FOR THE METHOD OF CONTROL FOR | | | LIGHTING TO BE SHOWN AS *MANUAL ON/OFF* WHEN THE | | | LIGHTING ON PLANS AND AS REQUIRED UNDER CHAPTER 13 OF | | | THE FBC REQUIRES LIGHTING TO BE AUTOMATED. | | | PLEASE SEE SOME SEPARATE SPACES STILL DO NOT INDICATE | | | OVER RIDE DEVICES. PLEASE SEE 13-415.1.ABC1.2 AS THESE | | | AREAS SHALL CONTAIN EITHER OF THE CONTROLS AS SET-FORTH | | | HOWEVER MAY NOT ONLY CONTAIN A SINGLE POLE OR THREE-WAY | | | SWITCH. THE DEVICE MUST BE CAPABLE OF OVER RIDING THE | | | TIMED SCHEDULING WHEN ON THE TIMED SCHEDULE SYSTEM. IF | | | AN AREA IS NOT ON THE SCHEDULED TIMER CONTROLS OR | | | ENERGY MANAGEMENT SYSTEM THEM SEPARATE DEVICES SUCH AS | | | OS TYPE DEVICES ARE PERMITTED. | | | PLEASE SEE AREAS WHICH DO NOT CONTAIN OVER RIDE | | | CONTROLS FOR EXAMPLE: PHARMACY, FAMILY TOILET ROOM (NO | | | CONTROLS) , LIGHTING OUTSIDE OF TOILETS, ETC PLEASE SEE | | | LIGHTS OUTSIDE OF THESE SAME ROOMS AND OTHER AREAS. | | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | 2) NOTE: PLEASE SEE THE COVER SHEET C1 STILL INDICATES | | | THE WRONG CODE FOR ELECTRICAL.. ALL OF THE PREVIOUS | | | REVIEW STATED THE CODES WHICH NEEDED TO BE ON PLANS. | | | PLEASE SEE THE PLANS STILL INDICATE THE 2002 | | | NEC/NFPA-70. THIS SHOULD BE THE 2005 NEC/ NFPA-70. THIS | | | CAN BE REDLINED. | | | | | | 3) NOTE: PLEASE KNOW THAT IT MAY BE POSSIBLE PENDING | | | OTHER TRADE REVIEWS TO PROVIDE WHAT IS KNOWN AS A | | | *PROVISO* FOR THE LIGHTING CONTROL PART OF THE COMMENT | | | ABOVE AND COMMENT NUMBER 2. | | | THE *PROVISO* WOULD SET-FORTH CONDITIONS THAT THE | | | PERMIT CAN BE ISSUED AND THE LIGHTING CONTROLS ON PLANS | | | WOULD NEED TO BE ADDRESSED AND SUBMIT REVISED | | | ELECTRICAL PLANS WITHIN 30DAYS OF PERMIT ISSUANCE. | | | PLEASE KNOW HOWEVER THAT THE ENERGY CALCULATIONS MAY | | | NOT BE DONE AS A *PROVISO* AND MUST BE ADDRESSED AT | | | THIS TIME. | | | PLEASE BE SURE ANY REVISED ENERGY CALCULATIONS WILL BE | | | REQUIRED TO CONTAIN ALL SIGNATURES FROM THE RESPONSIBLE | | | PERSONS OF RECORD INCLUDING THAT OF THE OWNER AGENT. | | | 13-103.1.1.1 | | | *** IMPORTANT , THE REVIEW FROM THE MECHANICAL REVIEWER | | | HAS NOT YET BEEN DONE FOR THE ENERGY CALCULATIONS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-07-09 20:06:07 | 2007-07-09 20:06:07 | | | PLANS REMOVED FROM INCOMING FOR ELECTRICAL REVIEW. | | | PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM | | | BOARD ONCE ELECTRICAL REVIEW IS COMPLETED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-06-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-10 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-10 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2007-06-10 14:07:49 | ** UNSAT 4TH REVIEW ** | | | | | | | | | | | | ********** WAL-MART BUILD -OUT****** | | | | | | 1) NOTE:PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR | | | "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. | | | EVEN WHEN PLANS ARE 100% CODE COMPLIANT, THE REVIEW | | | WILL STILL BE IN FAILED STATUTES AS THE REVIEW OF | | | PERMIT APPLICATION(S), LICENSING ETC WILL STILL TAKE | | | PLACE. | | | | | | 2) NOTE: PLEASE SUBMIT ONLY DOCUMENTS RELEVANT TO | | | PROJECT AND SCOPE OF WORK. PLEASE SEE THE SUBMITTED | | | PACKAGE CONTAINS NUMEROUS DOCUMENTS WHICH ARE NOT | | | RELEVANT OR NO LONGER RELEVANT TO SCOPE OF WORK OR DOES | | | NOT NEED TO BE IN PACKAGE. PLEASE KNOW THAT PRINTING | | | OUT OF ON-LINE NOTES DOES NOT NEED TO PLACED IN PACKAGE | | | FOR OUR REVIEW AS WE ALREADY HAVE THE NOTES, SEVERAL OF | | | THESE WERE SUBMITTED. | | | FBC 106.3 | | | | | | 3) NOTE: PLEASE SEE EFP SHEETS WHICH ARE NOT SEALED AS | | | REQUIRED PER FAC 61G15-23.001. | | | PLEASE SEE FS471.025 | | | ** THIS IS REQUIRE WHETHER OR NOT COMMENT IS MADE BY | | | OTHER TRADES. | | | | | | 4) NOTE: PLEASE SEE MISSING REQUIRED LICENSE | | | INFORMATION ON TITLE BLOCKS FOR EFP SHEETS. PLEASE SEE | | | FS 471.023 WHICH REQUIRES A CERTIFICATE OF | | | AUTHORIZATION NUMBER AND TO BE PLACED ON TITLE BLOCKS. | | | THIS IS FOR SACRAMENTO ENGINEERING. | | | **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | | OTHER TRADES. | | | | | | 5) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW AS | | | THE PLANS WERE NOT CHANGED. PLEASE SEE THE A SHEETS | | | STILL INDICATE TWO CODES. THE FA/EFP SHEETS INDICATE | | | CODES NOT UNDER THE FBC. (IBC,IFC ) | | | | | | **PREVIOUS REVIEW NOTE** | | | PLEASE SEE THE PREVIOUS REVIEWS WHICH MENTIONED THE | | | CODES REQUIRED DEPENDING ON WHEN PERMIT APPLICATION IS | | | MADE. PLEASE SEE THE PLANS NOW LIST BOTH CODES FOR 2005 | | | AND 2002 ARE BEING SHOWN ON PLANS FOR DESIGN ETC?? | | | PLEASE MAKE THE CORRECTIONS. | | | PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS | | | #6 WILL BE REQUIRED. | | | PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH | | | SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED | | | UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES | | | ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS. | | | | | | 6) NOTE:PLEASE SEE THE NOTES WITH RESPECT TO FBC | | | CHAPTER 13 REMAIN IN AFFECT. | | | PLEASE SEE THE ENERGY CALCULATIONS ARE NOT PER | | | 13-415.1.AB.1.1. PLEASE SEE THE PROGRAM OF FLA-COM | | | VERSION 3.0 IS THE LATEST EDITION ADOPTED BY THE STATE | | | AND CHAPTER 13. | | | WHEN THESE ARE DONE, THE ENERGY CALCULATIONS MUST ALSO | | | CONTAIN THE INPUT DATA REPORT TO COINCIDE WITH THE | | | PLANS FOR REVIEW. | | | PLEASE SEE THESE WILL BE REQUIRED TO BE SIGNED, DATED | | | AND SEALED AS PREVIOUSLY NOTED. THE FLA-COM SHEETS HAVE | | | SPACE FOR THIS. | | | PLEASE SEE NOT ALL SEPARATE SPACES WHICH CONTAIN FLOOR | | | TO CEILING HEIGHT PARTITIONS CONTAIN CONTROLS AS | | | REQUIRED PER 13-415.1.ABC.1.1, .1.2. | | | PLEASE SEE SYMBOL LEGEND DOES NOT STATE TIMES OF | | | DEVICES. | | | PLEASE COORDINATE ALL DOCUMENTS. | | | RESPONSE FROM DESIGNER ONLY RESPONDED TO ONE OF THE | | | COMMENTS MADE IN THIS NOTE FROM PREVIOUS REVIEW. | | | | | | ** PREVIOUS REVIEW NOTES** | | | PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED ARE | | | STILL NOT SIGNED, DATED AND SEALED BY THE DESIGNER OF | | | RECORD NOR ARE THEY UNDER THE CORRECT CODE. THEY ARE | | | DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS NOT IN | | | EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH | | | PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1, | | | 13-415.2 AND 13-103.1.1.1. | | | REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT | | | THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006 | | | REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER | | | 13. | | | PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS, | | | WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN | | | COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE | | | SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON | | | OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME | | | SCHEDULING ETC. | | | PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH | | | CHAPTER 13. | | | | | | PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13. | | | PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR | | | FEEDERS AND BRANCH CIRCUITS. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. | | | PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM | | | DETAILS. | | | PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES | | | 415.2.C.1 AND 415.2.B.1. | | | PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED, | | | DATED AND SEALED BY THE DESIGNER(S) OF RECORD. | | | | | | 7) NOTE:PLEASE SEE THIS WAS THE NOTE FROM PREVIOUS | | | REVIEW. THIS REMAINS, AS ONLY SOME SHEETS WERE REVISED | | | TO CHANGE DOOR SWING. PLEASE SEE SHEETS WHICH WERE NOT | | | REVISED STILL INDICATE INWARD SWING ON DOOR. | | | ** PREVIOUS REVIEW NOTE ** | | | THIS IS TAKEN FROM PREVIOUS REVIEW AS NO CHANGES TO | | | ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE SEE THE MAIN | | | ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND UNOBSTRUCTED | | | PATH WHICH IT DOES NOT. THERE IS A WALL CLEARLY SHOWN | | | WHICH WOULD IMPEDE THE EGRESS OUT OF THE ROOM IN AN | | | EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS, AN | | | ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND | | | THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT | | | ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR | | | WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED | | | TO CONTAIN PANIC HARDWARE. | | | 110.26, 90.4 | | | | | | 8) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR | | | EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1, | | | .2, AND .3(4). | | | PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES | | | AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION | | | SHEETS WHICH ARE FROM TWO CODE CYCLES AGO. | | | PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE | | | 2002 NFPA-72 | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-02-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-20 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-19 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2007-02-20 15:17:50 | | | | ********** UNSAT 3RD REVIEW ************* | | | | | | ********** WAL-MART BUILD -OUT****** | | | | | | ** PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR "PLAN | | | REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. | | | | | | 1 NOTE: PLEASE KNOW THAT IT IS MOST HELPFUL FOR A | | | REVIEW IF A RESPONSE LETTER OF SOME TYPE IS SUBMITTED | | | BY THE DESIGNER OF RECORD. PLEASE SEE THE RESPONSE | | | LETTER CONTAINS TWO RESPONSES WHICH ARE BOTH LISTED AS | | | ITEM #1 AND DO NOT INDICATE WHAT THEY ARE BEING | | | RESPONDED TO?? | | | | | | 2) NOTE:PLEASE SEE THE PREVIOUS REVIEWS WHICH | | | MENTIONED THE CODES REQUIRED DEPENDING ON WHEN PERMIT | | | APPLICATION IS MADE. PLEASE SEE THE PLANS NOW LIST BOTH | | | CODES FOR 2005 AND 2002 ARE BEING SHOWN ON PLANS FOR | | | DESIGN ETC?? PLEASE MAKE THE CORRECTIONS. | | | PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS | | | #6 WILL BE REQUIRED. | | | PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH | | | SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED | | | UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES | | | ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS. | | | | | | 3) NOTE:PLEASE SEE THAT THE ENERGY CALCULATIONS | | | SUBMITTED ARE STILL NOT SIGNED, DATED AND SEALED BY THE | | | DESIGNER OF RECORD NOR ARE THEY UNDER THE CORRECT CODE. | | | THEY ARE DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS | | | NOT IN EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH | | | PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1, | | | 13-415.2 AND 13-103.1.1.1. | | | REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT | | | THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006 | | | REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER | | | 13. | | | PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS, | | | WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN | | | COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE | | | SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON | | | OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME | | | SCHEDULING ETC. | | | PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH | | | CHAPTER 13. | | | | | | PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13. | | | PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR | | | FEEDERS AND BRANCH CIRCUITS. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. | | | PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM | | | DETAILS. | | | PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES | | | 415.2.C.1 AND 415.2.B.1. | | | PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED, | | | DATED AND SEALED BY THE DESIGNER(S) OF RECORD. | | | | | | 4) NOTE: THIS IS TAKEN FROM PREVIOUS REVIEW AS NO | | | CHANGES TO ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE | | | SEE THE MAIN ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND | | | UNOBSTRUCTED PATH WHICH IT DOES NOT. THERE IS A WALL | | | CLEARLY SHOWN WHICH WOULD IMPEDE THE EGRESS OUT OF THE | | | ROOM IN AN EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS, | | | AN ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND | | | THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT | | | ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR | | | WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED | | | TO CONTAIN PANIC HARDWARE. | | | 110.26, 90.4 | | | | | | 5) NOTE: PLEASE SEE THAT THE PANEL LRX WHICH IS STILL | | | BEING SHOWN IN A STORAGE ROOM. PLEASE RELOCATE. THIS IS | | | A LIFE SAFETY AND PROPERTY SAFETY ISSUE AND WILL NOT BE | | | PERMITTED IN THIS ROOM. | | | PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY | | | TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY | | | IGNITABLE MATERIALS ETC. | | | | | | 6) NOTE: PLEASE SEE PLANS STILL FOR A KIRK KEY | | | INTERLOCK WHICH DOES NOT PROVIDE A *FAIL SAFE* | | | OPERATION. THIS OFFICE HAS REVIEWED DOCUMENTATION | | | PROVIDED. THIS OFFICE HAS NOT MENTIONED THAT A LISTED | | | TRANSFER SWITCH IS REQUIRED HOWEVER WE ARE REQUIRING | | | THE DEVICE IS LISTED FOR USE AND THAT IT PROVIDES | | | COMPLETE FAIL SAFE OPERATION. | | | DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT. | | | PLEASE SEE 110.3, 90.7, 702.6 ETC. | | | PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS. | | | | | | 7) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR | | | EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1, | | | .2, AND .3(4). | | | PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES | | | AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION | | | SHEETS WHICH ARE FROM TWO CODE CYCLES AGO. | | | PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE | | | 2002 NFPA-72 | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-02-19 10:37:32 | 2007-02-19 10:37:32 | | | REVIEW TO CONTINUE ON 2/20 NOTES TO FOLLOW , PLANS WILL | | | BE PLACED INTO A "F" STATUS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-07 |
Time |
19:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-07 |
Time |
17:45 |
Sent To |
|
|
| Notes |
| 2006-12-07 19:12:27 | ********** UNSAT 2ND REVIEW ************* | | | | | | ********** WAL-MART NEW /REMODEL****** | | | | | | ** PLEASE SEE PLANS WERE ONLY SUBMITTED FOR "PLAN | | | REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE | | | KNOW THAT AT THIS TIME AS OF DECEMBER 8TH, 2006 THE | | | STATE OF FLORIDA ADOPTS NEW CODES AND THESE WILL CHANGE | | | AND AFFECT DESIGNS SUBMITTED ON PLANS. PLEASE KNOW THAT | | | AS THE PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT | | | APPLICATION BEFORE THE END OF TODAY'S DATE, ALL PLANS | | | WILL BE REQUIRED TO BE REDESIGNED UNDER THE NEW | | | CODE(S). | | | | | | ** PLEASE SEE SOME COMMENTS BELOW WHICH STILL NEED TO | | | BE ADDRESSED. PLEASE SEE SOME OF THESE ARE NOTED WITH A | | | "NO" OR "OK". THOSE OF WHICH MAY CONTAIN AN "OK/NO" | | | MEANS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED. | | | | | | ** PLEASE SEE THERE ARE ALSO SOME NEW NOTES. | | | | | | 1) NOTE: OK. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE:NO/OK. PLEASE SEE MISSING INFORMATION IS | | | STILL REQUIRED FOR THE ARCHITECTURAL FIRM. PLEASE SEE | | | THE NUMBER WHICH WAS ADDED TO THE TITLE BLOCKS IS THAT | | | OF THE STATE OF FLORIDA'S CORPORATION NUMBER WHICH IS | | | NOT THE CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE | | | THE NUMBER NEEDED FOR DOING BUSINESS AS AN | | | ARCHITECTURAL FIRM IS ISSIED FROM THE DEPARTMENT OF | | | BUSINESS AND PROFESSIONAL REGULATION. | | | THIS IS REQUIRED FOR ALL "A" SHEETS WHETHER OR NOT | | | COMMENT IS MADE BY OTHER TRADES. | | | THE MEP SHEETS SEEM TO HAVE BEEN ADJUSTED TO INCLUDE | | | ONLY THE PE'S AS INDIVIDUALS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE | | | BLOCKS FOR ARCHITECTURAL AND ENGINEERING FIRMS. PLEASE | | | SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA | | | STATUES 481.219 FOR THE ARCHITECTURAL FIRM AND PLEASE | | | SEE FAC61G15-23.002 AND FS 471.023 FOR THE ENGINEERING | | | FIRM. | | | PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER'S | | | FOR INDIVIDUAL DESIGNERS OF RECORD. | | | PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED FOR BOTH FIRMS REQUIRED | | | ON TITLE BLOCKS ALSO. | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR | | | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | 4) NOTE:NO, PLEASE SEE THE CODES WERE ADDED AS | | | REQUESTED, HOWEVER SINCE A PERMIT HAS NOT BEEN APPLIED | | | FOR THE FOLLOWING CODES WILL BE THE NEW RELEVANT CODES | | | IN EFFECT TO THE NEW DESIGN. PLEASE SEE THE 2005 | | | NFPA-70 AND THE 2004 FBC REVISIONS #6 WILL BE | | | REQUIRED. | | | THE OTHER CODES AS NOTED BELOW WILL REMAIN. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A | | | MINIMUM. | | | PLEASE SEE PLANS MENTIONS THE 2004 | | | FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER | | | 27 OF THE 2004 FBC ADOPTED THE 2002 | | | NFPA-70 (NEC). | | | PLEASE ALSO LIST THE FOLLOWING. | | | NFPA-72 2002, NFPA-101 2003. | | | | | | 5) NOTE:NO, PLEASE SEE AS THE CODE HAS CHANGED THERE | | | ARE NOW NEW REQUIREMENTS IN THE SAME SECTIONS AS NOTED | | | BELOW. PLEASE SEE HOWEVER THAT THE COMPLETED | | | INFORMATION FROM THE PREVIOUS REVIEW WAS NOT ADDRESSED | | | AS NEEDED ON PLANS. PLEASE SEE ENERGY CALCULATIONS | | | SUBMITTED ARE NOT COMPLETE AS NEEDED. THESE ARE ALSO | | | REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER | | | OF RECORD. PLEASE SEE NO LIGHTING POWER DENSITIES WERE | | | SUBMITTED. PLEASE SEE BATH ROOMS WHICH ARE NOT A SINGLE | | | STALL, WILL REQUIRE A DIFFERENT TYPE OF OCCUPANCY | | | SENSOR TYPE DEVICE. THESE SHALL BE THE TYPE WHICH WILL | | | ACTIVATE UNDER OTHER CONDITIONS OTHER THAN MOTION. | | | PLEASE SEE AS NO TIMES ON OVER RIDES COULD NOT BE | | | LOCATED THERE ARE ITEMS WHICH CAN NOT BE REVIEWED FOR | | | COMPLIANCE AT THIS TIME. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 2004 FBC CHAPTER 13. | | | PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR | | | FEEDERS AND BRANCH CIRCUITS. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. | | | PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM | | | DETAILS. | | | PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES | | | 415.2.C.1 AND 415.2.B.1. | | | PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED, | | | DATED AND SEALED BY THE DESIGNER(S) OF RECORD. | | | | | | 6) NOTE: OK. | | | | | | 7) NOTE:NO, PLEASE SEE THE MAIN ELECTRICAL ROOM SHALL | | | CONTAIN A CLEAR AND UNOBSTRUCTED PATH WHICH IT DOES | | | NOT. THERE IS A WALL CLEARLY SHOWN WHICH WOULD IMPEDE | | | THE EGRESS OUT OF THE ROOM IN AN EMERGENCY. IN THE CASE | | | OF FIRE OR BLINDNESS, AN ELECTRICIAN OR OTHER PERSON | | | COULD BECOME TRAPPED AND THIS SCENARIO CREATES A LIFE | | | SAFETY ISSUE WHICH IS NOT ACCEPTABLE TO THIS AHJ. | | | PLEASE ALSO SEE THAT THE DOOR WILL BE REQUIRED TO OPEN | | | OUTWARD AND WILL BE REQUIRED TO CONTAIN PANIC | | | HARDWARE. | | | 110.26, 90.4 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS SHALL BE | | | REQUIRED FOR MAIN ELECTRICAL ROOM. PLEASE ALSO SEE | | | PANIC HARDWARE AND DOORS CHANGES WILL BE REQUIRED FOR | | | NEW EQUIPMENT. | | | | | | 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS | | | STORAGE WILL NOT BE PERMITTED, HOWEVER THIS OFFICE | | | INCLUDING THE FIRE MARSHAL?S OFFICE HAS BEEN IN TOO | | | NUMEROUS STORAGE ROOMS WHICH MATERIALS ARE PLACED | | | IN-FRONT OF EQUIPMENT ETC. THIS IS ALSO A LIFE SAFETY | | | HAZARD AND WILL REQUIRE THIS PANEL TO BE RELOCATED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE PANEL WHICH IS BEING SHOWN IN STORAGE ROOM | | | SHALL BE A DEDICATED ELECTRICAL/EQUIPMENT ROOM OR | | | PLEASE RELOCATE PANEL. | | | PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY | | | TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY | | | IGNITABLE MATERIALS. | | | | | | 9) NOTE: NO, PLEASE SEE AS OF THE MANUFACTURES | | | SPECS/CUT SHEETS SUBMITTED THE EQUIPMENT BEING PROPOSED | | | IS NOT ACCEPTABLE TO THIS AHJ AS BEING USED OR | | | PROVIDING ANY FAIL SAFE OPERATION OR PROVIDES | | | INADVERTENT OPERATION. PLEASE SEE UL LISTING 1081 ETC. | | | PLEASE SEE OTHER LISTINGS WHICH WILL REQUIRE THIS | | | EQUIPMENT BEING SERVICE ENTRANCE RATED, AND MUST MEET | | | SECTIONS GIVEN. | | | PLEASE SEE 110.3, 90.7, 702.6 ETC. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT ACTUALSPEC/MANUFACTURES CUT SHEETSFOR | | | THE MAIN SW BD AND PROPOSED"KIRK KEY INTERLOCK". | | | PLEASE KNOW, THIS OFFICE HAS SEEN SOME SYSTEMS WHICH DO | | | NOT MEET THE CODE WITH RESPECT TO TRANSFER EQUIPMENT | | | AND LISTED FOR THE INTENDED USE. | | | 702.6, 110.3 | | | | | | 10) NOTE: OK. | | | | | | 11) NOTE: OK. | | | | | | ** NEW NOTE ** | | | | | | 1) NOTE: PLEASE SHOW ANY STROBES/HORN DEVICES NEW OR | | | EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1, | | | .2, AND .3(4). | | | THIS WAS NOT IN PREVIOUS REVIEW AS IT HAS NOW BECOME A | | | REQUIRED REVIEW FOR THE ELECTRICAL PLAN REVIEW STAFF. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-03 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-30 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2006-08-03 00:00:00 | ********** UNSAT ************* | | | | | | **********WAL-MART NEW /REMODEL****** | | | | | | ** PLEASE SEE PLANS WERE ONLY SUBMITTED | | | FOR "PLAN REVIEW" AND HAVE NOT BEEN | | | SUBMITTED FOR PERMIT. | | | | | | | | | 1) NOTE: PLEASE SEE ALL ARCHITECTURAL | | | SHEETS CONTAIN A RAISED SEAL OVER A | | | "PHOTO-COPIED" SIGNATURE OF THE | | | ARCHITECT OF RECORD. PLEASE KNOW UNDER | | | FS 481.221 AND FAC 61G1-16.004 THE | | | SIGNATURE SHALL BE ORIGINAL. SEALED | | | PHOTO-COPIED PLANS ARE NOT ACCEPTABLE. | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL | | | TRADES AND FOR ALL SHEETS WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 2) NOTE: PLEASE ALSO SEE "S-1, S-2, AND | | | S-3, AS THESE ALSO CONTAIN A RAISED SEAL | | | OVER A PHOTO-COPIED SIGNATURE> | | | PLEASE SEE FS 472.025, FAC 61G17 | | | REQUIRED FOR BOTH SETS AND WHETHER OR | | | NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | 3) NOTE: PLEASE SEE MISSING REQUIRED | | | INFORMATION ON TITLE BLOCKS FOR | | | ARCHITECTURAL AND ENGINEERING FIRMS. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | 61G1-16.004 AND FLORIDA STATUES 481.219 | | | FOR THE ARCHITECTURAL FIRM AND PLEASE | | | SEE FAC61G15-23.002 AND FS 471.023 FOR | | | ENGINEERING FIRM. | | | PLEASE SEE MISSING PRINTED NAME AND | | | LICENSE NUMBER'S FOR INDIVIDUAL | | | DESIGNERS OF RECORD. | | | PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED FOR BOTH | | | FIRMS REQUIRED ON TITLE BLOCKS ALSO. | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL | | | SHEETS AND FOR ALL TRADES WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 4) NOTE: PLEASE BE SURE PLANS REFLECT | | | THE FOLLOWING CODES AT A MINIMUM. | | | PLEASE SEE PLANS MENTIONS THE 2004 | | | FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER | | | 27 OF THE 2004 FBC ADOPTED THE 2002 | | | NFPA-70 (NEC). | | | PLEASE ALSO LIST THE FOLLOWING. | | | NFPA-72 2002, NFPA-101 2003. | | | | | | 5) NOTE: PLEASE SEE 2004 FBC CHAPTER 13. | | | PLEASE SEE 13-413.1ABC.1, PROVIDE WORST | | | CASE FOR FEEDERS AND BRANCH CIRCUITS. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. | | | PLEASE PROVIDE LIGHTING CONTROL/ ENERGY | | | MANG SYSTEM DETAILS. | | | PLEASE SEE 13-415.1.AB.1 , | | | 13-415.2.ABC.1 FOR TABLES 415.2.C.1 AND 415.2.B.1. | | | PLEASE ALSO BE SURE ALL ENERGY | | | CALCULATIONS ARE SIGNED, DATED AND | | | SEALED BY THE DESIGNER(S) OF RECORD. | | | | | | 6) NOTE: PLEASE SEE PANELS IN | | | DELI/BAKERY ARE WHICH DO NOT SEEM TO | | | MEET 110.26 FOR MIN CLEARANCES. | | | | | | 7) NOTE: PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS | | | SHALL BE REQUIRED FOR MAIN | | | ELECTRICAL ROOM. PLEASE ALSO SEE PANIC | | | HARDWARE AND DOORS CHANGES WILL BE | | | REQUIRED FOR NEW EQUIPMENT. | | | | | | 8) NOTE: PLEASE SEE PANEL WHICH IS BEING | | | SHOWN IN STORAGE ROOM SHALL BE A | | | DEDICATED ELECTRICAL/EQUIPMENT ROOM OR | | | PLEASE RELOCATE PANEL. | | | PLEASE SEE 110.26,408.7, AND 240.24 AS | | | STORAGE OF ANY TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF | | | EASILY IGNITABLE | | | MATERIALS. | | | | | | 9) NOTE: PLEASE SUBMIT ACTUAL | | | SPEC/MANUFACTURES CUT SHEETSFOR THE | | | MAIN SW BD AND PROPOSED"KIRK KEY | | | INTERLOCK". PLEASE KNOW, THIS OFFICE HAS | | | SEEN SOME SYSTEMS WHICH DO NOT MEET THE | | | CODE WITH RESPECT TO TRANSFER EQUIPMENT | | | AND LISTED FOR THE INTENDED USE. | | | 702.6, 110.3 | | | | | | 10) NOTE: PLEASE CLARIFY OF ALL | | | CONTINUOUS LOADS AND LARGEST MOTOR LOADS | | | ARE ALREADY SHOWN AT 125%. | | | 215.3,230.42 ETC | | | PLEASE PROVIDE DETAIL ON LOAD | | | CALCULATIONS. | | | 220. | | | | | | 11) NOTE: PLEASE CLARIFY RECEPTS IN | | | BATH(S) AS GFI PROTECTED OR NOT. | | | PLEASE SEE PANEL SCHEDULE DOES NOT SEEM | | | TO INDICATE THE REQUIRED GFI PROTECTION. | | | 210.8B1 | | | | | | ** PLEASE BE SURE TO SEE ANY POSISBLE | | | COMMENTS FROM OTHER TRADES WHICH MAY | | | AFFECT ELECTRICAL PLANS/DESIGN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTRUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | 2006-08-02 00:00:00 | PLANS WILL BE GOING INTO A "F" STATUS, | | | NOTES TO FOLLOW. | | 2006-07-30 00:00:00 | IN ELECTRIC FOR REVIEW, |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2007-02-08 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-02-08 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-02-08 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-01-18 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-01-18 |
Time |
10:32 |
Sent To |
B |
|
| Notes |
| 2007-01-18 10:48:48 | FAILED FOR FOLLOWING REASONS: | | | | | | I. ENG REVIEW DWGS ARE NOT SEALED BY P E | | | 2.PLEASE SHOW POLLUTION PREVENTION SILT FENCE AROUND | | | THE CONSTRUCTION SITE ON THE DRAWINGS. | | | 3.IT APPEARES THAT YOU ARE GOING TO USE THE EXISTING | | | DRAINAGE SYSTEM FOR STORM WATER. IS THAT TRUE? AREYOU | | | ADDING ANY DRAINAGE STORM WATER PIPE, OR EXFILTRATION | | | TRENCH, OR POND?ALL STORM WATER GO IN THE POND? | | | PLEASE EXPLAIN ANY CHANGES IN STORM WATER DRAINAGE | | | SYSTEM. DO YOU HAVE ANY STORM WATER OUTLET GOING IN | | | CITY SYSTEM OR SFWMD CANAL? | | | PLEASE PROVIDE EACH ITEM SEPARATELY TO EXPEDITE THE | | | PERMITTING PROCESS. THANKS | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-09-01 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-09-01 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2006-09-01 00:00:00 | FAILED: | | | | | | 1. NEED POLLUTION PREVENTION | | | PLANS,BEFORE,DURING,& AFTER. DUMPSTER | | | ENCLOSURE DETAILS PER CITY OF WPB MUST | | | BE INCLUDED IN THE DRAWINGS | | | 2. PRE & POST CONST. PERVIOUS,IMPERVIOUS | | | AREA, STORM WATER CAL.,CRITERIA FOR | | | RUNOFF CAL.,CONTROL STUCTURES DETAILS IF | | | ANY, EXFILTRATION TRENCHES, PIPES ETC., | | | CAL.,WET-DRY RETENTION POND AREAES ETC. | | | IF ANY, WE LIKE TO KNOW HOW YOU ARE | | | GOING TO TAKE CARE OF STORM WATER. SFWMD | | | PERMIT, GEOTECHNICAL REPORT ETC, | | | 3. UTILITY REVIEW MUST BE APPROVED FROM | | | 45TH STREET (MANNY G.) BEFORE WE | | | APPROVE. | | | 4. CITY OF WPB DETAIS STANDARDS MUST BE | | | INCLUDED IN THE DRAWINGS FOR SIDEWALK, | | | PARKINGS,HANDICAP PARKINGS PER ADA | | | STANDARDS MUST BE INCLUDED IN THE | | | DRAWINGS, | | | 5. SITE ELEVATIONS, CENTER OF ROAD | | | ELEVATIONS,SIDEWALK AND FIRST FLOOR | | | ELEVATIONS MUST BE PER FLORIDA CODES & | | | FIRST FLOOR ELE MUST BE HIGH ENOUGH SO | | | NOT BE FLOODED. | | | | | | PLEASE RESPOND EACH ITEM SEPARATELY | | | UNDER ENGINEERING REVIEW. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-04-04 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-04 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2008-04-04 15:27:53 | *****02/27/08 REVISION, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A7,E1, AND E1.1 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2008-02-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-07 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-07 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2008-02-07 14:05:47 | ****08/24/07 REVISION, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A7. A7A, FP2, FP2.3, E1, AND E1.1 | | | WERE STAMPED, INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-18 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-18 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2007-07-18 17:33:47 | *****APPROVED***** | | | | | | NO OTHER FIRE PLAN REVIEW REQUIRED UNLESS THERE HAVE | | | BEEN CHANGES TO THE FLOOR PLAN, LIFE SAFETY, LIGHTING, | | | OR FIRE PROTECTION SHEETS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-03 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-03 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-22 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-22 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2007-03-22 15:47:07 | ******UNSAT****** | | | | | | *PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE | | | PREVIOUS FIRE PLAN REVIEW: | | | | | | | | | | | | 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND | | | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. | | | ADD THIS COMMENT TO SHEET EFP2 | | | | | | 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | MAKE THE NECESSARY CORRECTIONS ON SHEET EFP2, UNDER | | | AHJ/COMPLIANCE NOTE #8 AND ALSO IN THE SEQUENCE OF | | | OPERATIONS DETAIL,TO REFLECT THIS OPERATION. | | | | | | *NEW CMMENT: | | | | | | | | | 1.IN REGARDS TO NFPA 72, NATIONAL FIRE ALARM CODE, | | | THE 2002 EDITION (NOT 1996) SHOULD BE REFERENCED.MAKE | | | THE NECESSARY CORRECTIONS ON SHEET EFP2. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-01-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-25 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-25 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2007-01-25 12:47:38 | ******UNSAT****** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE | | | PREVIOUS FIRE PLAN REVIEW (10/10/2006) WHICH HAVE NOT | | | BEEN MARKED APPROVED.IN ADDITION SEE NEW COMMENT. | | | | | | | | | | | | 01.)NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED.(APPROVED) | | | | | | 02.)CONSTRUCTION, ALTERATION, AND DEMOLITION | | | OPERATIONS SHALL COMPLY WITH NFPA 241. (APPROVED) | | | | | | 03)ON THE APPROPIATE EXTERIOR ELEVATION SHEET, | | | SHOW/DISPALAY THE SUITE UNIT NUMBER OF THIS 6901 | | | OKEECHOBEE BOULEVARD SHOPPING PLAZA.AS PER WEST PALM | | | BEACH CODE, CHARACTERS ( NUMBERS AND/OR LETTERS) SHALL | | | BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. | | | (APPROVED) | | | | | | 04.)SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED | | | FOR FIRE SPRINKLER SYSTEM (APPROVED)AND FIRE ALARM | | | SYSTEM.(SEE NEW COMMENT) | | | | | | 05.)FIRE SPRINKLER SHALL BE MAINTAINED OPERATIONAL | | | UNTIL SUCH SUCH TIMETHAT THE SYSTEM IS DEMOLISHED. | | | PRIOR TO THE SPRINKLER SYSTEM BEING TAKEN OUT OF | | | SERVICE, NOTIFICATION AND APPROVAL SHALL BE ATTAINED | | | FROM THE FIRE PREVENTION BUREAU.(APPROVED) | | | | | | 06.)DEMOLITION OPERATIONS INVOLVING THE USE OF | | | CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITH | | | NFPA 51B.(APPROVED) | | | | | | 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND | | | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. (SEE | | | NEW COMMENT) | | | | | | 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. (SEE | | | NEW COMMENT) | | | | | | 09.)LOCK-BOX ENTRY KEY SYSTEM WILL BE REQUIRED.SHOW | | | THE LOCATION OF THIS DEVICE ON THE APPROPIAITE PLAN | | | SHEET(S).(APPROVED) | | | | | | 10.)INTERIOR FINISH FOR WALLS AND CEILINGS SHALL BE | | | CLASS "A" OR CLASS "B". | | | | | | 11.)ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA | | | 80. | | | | | | 12.)PANIC HARDWARE TO BE INSTALLED ON EXIT DOORS WITH | | | AN OCCUPANT LOAD OF ONE HUNDRED PERSONS OR MORE.IN | | | RELATION TO POWERED DOORS, REFERENCE NFPA 101, 7.2.1.9 | | | | | | 13.)SHOW ON THE APPROPIATE FIRE PROTECTION PLAN | | | SHEET(S) THE LOCATION OF THE 2A10BC RATED FIRE | | | EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT.(APPROVED) | | | | | | NEW | | | | | | 14.CLASS A MERCANTILE OCCUPANCIES (GREATER THAN | | | 30,000 SQ. FT.) SHALL BE PROVIDED WITH A FIRE ALARM | | | SYSTEM.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-10 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-10 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2006-10-10 15:14:52 | ******DENIED****** | | | | | | | | | | | | 01.)NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 02.)CONSTRUCTION, ALTERATION, AND DEMOLITION | | | OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 03)ON THE APPROPIATE EXTERIOR ELEVATION SHEET, | | | SHOW/DISPALAY THE SUITE UNIT NUMBER OF THIS 6901 | | | OKEECHOBEE BOULEVARD SHOPPING PLAZA.AS PER WEST PALM | | | BEACH CODE, CHARACTERS ( NUMBERS AND/OR LETTERS) SHALL | | | BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. | | | | | | 04.)SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED | | | FOR FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM | | | MODIFICATION. | | | | | | 05.)FIRE SPRINKLER SHALL BE MAINTAINED OPERATIONAL | | | UNTIL SUCH SUCH TIMETHAT THE SYSTEM IS DEMOLISHED. | | | PRIOR TO THE SPRINKLER SYSTEM BEING TAKEN OUT OF | | | SERVICE, NOTIFICATION AND APPROVAL SHALL BE ATTAINED | | | FROM THE FIRE PREVENTION BUREAU. | | | | | | 06.)DEMOLITION OPERATIONS INVOLVING THE USE OF | | | CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITH | | | NFPA 51B. | | | | | | 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND | | | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. | | | | | | 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL | | | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 09.)LOCK-BOX ENTRY KEY SYSTEM WILL BE REQUIRED.SHOW | | | THE LOCATION OF THIS DEVICE ON THE APPROPIAITE PLAN | | | SHEET(S). | | | | | | 10.)INTERIOR FINISH FOR WALLS AND CEILINGS SHALL BE | | | CLASS "A" OR CLASS "B". | | | | | | 11.)ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA | | | 80. | | | | | | 12.)PANIC HARDWARE TO BE INSTALLED ON EXIT DOORS WITH | | | AN OCCUPANT LOAD OF ONE HUNDRED PERSONS OR MORE. | | | | | | 13.)SHOW ON THE APPROPIATE FIRE PROTECTION PLAN | | | SHEET(S) THE LOCATION OF THE 2A10BC RATED FIRE | | | EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2008-06-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-05 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-05 |
Time |
13:52 |
Sent To |
M |
|
| Notes |
| 2008-06-05 13:52:30 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-21 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-21 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2008-05-27 15:55:28 | TO "COMM" BD#5 | | 2008-05-21 09:28:22 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-04-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-11 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-11 |
Time |
10:30 |
Sent To |
B |
|
| Notes |
| 2008-04-11 10:30:50 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-04-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-08 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-08 |
Time |
16:25 |
Sent To |
FIRE |
|
| Notes |
| 2008-04-08 16:25:40 | TO"F" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-06 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-06 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2008-03-06 16:08:29 | TO "COMM" BD#45 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-06 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-06 |
Time |
15:11 |
Sent To |
P |
|
| Notes |
| 2008-03-06 15:12:07 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-08 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-08 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2008-01-08 16:17:06 | TO "COMM" BD#40 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-30 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-30 |
Time |
15:29 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-09 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-09 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2007-07-18 15:49:20 | TO "COMM" BD#30/PLANS ON RACK--LARGE ROLLED PLANS AND | | | PAPERWORK | | 2007-07-09 16:17:25 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-16 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-16 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2007-06-05 13:53:14 | TO "COMM" BD#51--PLANS ON RACK--LARGE FOLDED | | 2007-05-16 14:16:14 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-02-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-07 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-07 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2007-02-19 07:44:10 | TO COMM BOARD SPACE #59 | | 2007-02-07 11:13:51 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2006-11-29 15:13:21 | TO COMM BOARD #39 | | 2006-11-21 08:24:01 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-10 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-07-14 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2006-08-11 00:00:00 | 8/11/06-MOVED TO "COMM" BD#60 | | 2006-07-28 00:00:00 | TO COMM BOARD # 43 | | 2006-07-14 00:00:00 | WAITING FOR "COMM" BD-CHANGING FROM | | | WINN-DIXIE TO WALMART, MAY NEED ZONING | | | FOR CHANGE OF USE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-06-25 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-06-25 |
Time |
13:31 |
Sent To |
PC |
|
| Notes |
| 2008-06-25 13:56:01 | REVISED M2, R2, R3 AND ENERGY CALCS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
F |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-03-20 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-03-20 |
Time |
17:38 |
Sent To |
|
|
| Notes |
| 2008-03-20 17:44:41 | PLAN DENIED | | | PAGE R-2 NOT STAMPED BY ARCHITECT | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-01-23 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-23 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2008-01-23 16:13:14 | REVISED PG M1, R1, R2, R3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-01-23 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-23 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2008-01-23 14:32:26 | REVISION 3 PG M2: DENIED | | | | | | NOTE: A FOUR PAGE SCOPE-OF-WORK REPORT WAS PROVIDED TO | | | SHOW NATURE AND LOCATION OF CHANGES. THIS REPORT DOES | | | NOT INDICATE ANY MECHANICAL PLANS AS PART OF THIS | | | REVISION. HOWEVER, PAGES M1, M2, R1, R2 AND R3 ARE ALL | | | INCLUDED IN THIS REVISION. | | | | | | 1. PG M2: ROOFTOP UNIT SCHEDULE HAS BEEN REVISED TO | | | REFLECT THE NEW OWNER-SUPPLIED EQUIPMENT. IN | | | CONJUNCTION WITH THAT CHANGE, NOTE #9 HAS BEEN UPDATED | | | TO REFLECT THE EFFICIENCY RATINGS OF THE NEWLY | | | SPECIFIED EQUIPMENT. THE EFFICIENCIES LISTED IN THIS | | | NOTE DO NOT CORRESPOND WITH THE CURRENT PERMIT ENERGY | | | CALCULATIONS. IN MOST CASES, THE EFFICIENCIES HAVE GONE | | | DOWN. PROVIDE REVISED ENERGY CALCULATIONS WHICH | | | INCORPORATE THE NEW EQUIPMENT EFFICIENCIES. | | | | | | 2. PG M2: THE 5 TON UNIT SHOWS AN EFFICIENCY RATING OF | | | 12.6 SEER. THE MINIMUM EFFICIENCY REQUIRED FOR A UNIT | | | THIS SIZE IS 13.0 SEER IN ACCORDANCE WITH FBC TABLE | | | 13-407.1.ABC.3.2A. THIS IS A PRESCRIPTIVE MINIMUM | | | REGARDLESS OF WHAT PASSES ON THE CALCULATIONS IN | | | ACCORDANCE WITH FBC 13-400.1. PG M2 WILL NOT PASS | | | REVIEW UNTIL THE NEW INFORMATION IS COORDINATED WITH | | | REVISED ENERGY CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-07-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-17 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-17 |
Time |
17:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-09 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-09 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2007-06-09 15:26:49 | PLAN CHECK ONLY. THIS PLAN WAS REVIEWED UNDER THE 2004 | | | FBC BEFORE THE EFFECTIVE DATE OF THE 2006 REVISIONS | | | (DECEMBER 8,2006). UPON RESUBMITTAL FOR PERMIT, THE | | | PLANS WILL NEED TO BE REVIEWED TO VERIFY COMPLIANCE | | | WITH THE LATEST EDITION OF THE FBC IN EFFECT AT THE | | | TIME OF ACTUAL PERMIT APPLICATION. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-03-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-17 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-17 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2007-03-17 11:15:24 | *******3RD PLAN CHECK ONLY******* | | | | | | THESE COMMENTS ARE NUMBERED TO CORRESPOND WITH PREVIOUS | | | CPMMENTS AND RESPONSES DATED12/13/06 FOR THE PURPOSE OF | | | CONTINUITY. | | | | | | 1. PLEASE HAVE THE ENGINEER OF RECORD AFFIX HIS OR HER | | | OFFICIAL SEAL ALONG WITH SIGNATURE AND DATE PER FBC | | | 106.1 | | | | | | 2. OK | | | | | | 3. OK | | | | | | 4. PLEASE INCORPORATE OUTSIDE AIR CALCULATIONS (LABELED | | | 'VENTILLATION SUMMARY') ON TO PLANS AND/OR HAVE THE | | | ENGINEER OF RECORD AFFIX HIS OR HER OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID ACCOMPANYING DATA PER FBC | | | 106.1 | | | | | | 5. OK | | | | | | NOTE: SEPARATE PERMITS/APPLICATIONS WILL BE REQUIRED | | | FOR WALK-IN COOLERS/FREEZERS, HITCHEN HOODS, HOOD | | | SUPPRESSION SYSTEMS. | | | | | | IF YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS OR | | | IF YOU FIND THEM TO BE UNCLEAR IN ANY WAY, PLEASE FEEL | | | FREE TO CONTACT ME VIA PHONE OR EMAIL. MY CONTACT | | | INFORMATION IS LISTED BELOW. | | | | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-13 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-13 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2006-12-13 15:31:02 | ********2ND PLAN CHECK ONLY******* | | | | | | | | | 1.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE | | | WITH 2004 FBC CHAPTER 13 SECTION 13-101.1.3. | | | | | | 2.PLEASE PROVIDE ANCHORING DETAILS FOR THE CURBS TO | | | THE ROOF DECK.PLEASE NOTE CURBS SHALL BE A MINIMUM OF | | | 8"ABOVE THE ROOF SURFACE PER 2004 FBC 1509.7. | | | | | | 3.EQUIPMENT STANDS LOCATED ON THE ROOF IN WHICH THE | | | ROOFING MATERIAL IS REQUIRED UNDER THE STAND, THE | | | CLEARANCE REQUIRED BETWEEN THE ROOF SURFACE AND THE | | | BOTTOM OF THE SUPPORT RAIL SHALL BE IN ACCORDANCE WITH | | | 2004 FBC TABLE 1509.7.PLEASE NOTE, PRODUCT APPROVALS | | | REQUIRED FOR EQUIPMENT STANDS LOCATED ON THE ROOF. | | | | | | 4.PLAN SHEET M2 OUTSIDE AIR IS INDICATED ON THE | | | ROOFTOP UNIT SCHEDULE.PLEASE INDICATE OUTSIDE AIR | | | CALCULATIONS IN ACCORDANCE WITH 2004 FMC TABLE 403.3. | | | | | | 5.PLAN SHEET M2 ROOFTOP UNIT SCHEDULE DOES NOT | | | INDICATE DUCT SMOKE DETECTOR ON UNITS 1,2, 9, 11 & 12. | | | PER 2004 FMC 606.2.1 SMOKE DETECTORS SHALL BE INSTALLED | | | INSUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER | | | THAN 2,000 CFM.WHERE MULTIPLE AIR HANDLING SYSTEMS | | | WHERE THE AGGREGATE AIR IS GREATER THAN 2,000 CFM, DUCT | | | SMOKE DETECTORS WILL BE REQUIRED IN ALL UNITS | | | REGARDLESS OF THE THE CAPACITY, 2004 FMC 606.2.2. | | | | | | PLEASE NOTE, ADDITIONAL PERMITS & PLANS REQUIRED FOR | | | THE HOOD, GREASE DUCT & FIRE SUPPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-06 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-06 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2006-10-06 00:00:00 | PROVISO:PLAN CHECK ONLY | | | | | | 1.PLAN SHEET M1, THE ROOFTOP EQUIPMENT | | | PIPING RUNOUT INDICATES 3/4" FOR ALL | | | UNITS.PLEASE NOTE, CONDENSATE SHALL BE | | | INSTALLED PER MANUFACTURER'S | | | SPECIFICATIONS, FULL LINE SIZE FOR | | | PROPER DRAINAGE. | | | | | | 2.ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPPRESSION & WALK-IN | | | COOLERS.PLEASE PROVIDE MANUFACTURER'S | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-06-04 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-06-04 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2008-06-04 18:11:36 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | 1. SHT P3 VENT FOR FIXTURE MG07 NOT APPROVED. VENT | | | SHALL NOT OFFSET HORIZONTALLY UNTILL 6" ABOVE THE FLOOD | | | RIM LEVEL OF THE FLOOR SINK. SECTION 905.4. | | | | | | 2. SHT P3 VENT FOR FLOOR SINK SHALL CONNECT ABOVE THE | | | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION 905.3. | | | (FLOOR SINK BY COL. LINE 6/E-D. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-06-04 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-06-04 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2008-06-04 18:07:02 | REVISION OK--SHTS P1 & P2 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2008-03-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-29 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-29 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-03-29 14:00:08 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVISION REVIEW: | | | | | | 1. SHT P1 INDICATES THAT EWC-1 IS DELETED. SHT C1 | | | PLUMBING FIXTURE COUNT INDICATES THAT 2 DRINKING | | | FOUNTAINS ARE REQUIRED. DELETING 1 DRINKING FOUNTAIN | | | ONLY LEAVES 1 DRINKING FOUNTAIN. THIS DOES NOT COMPLY | | | WITH TABLE 403.1. PLEASE CLARIFY. | | | ****RESPONSE NOTED, BUT PER SECTIONS 606.2(1) AND | | | 1002.1. EACH FIXTURE SHALL HAVE IT OWN SHUT OFF VALVE | | | AND ITS OWN TRAP. THE HI/LOW DRINKING FOUNTAIN HAS ONLY | | | ONE WATER SUPPLY AND ONE TRAP AND AS SUCH IS ONLY ONE | | | FIXTURE. | | | | | | 2. SHT P2 INDICATES THE WATER SUPPLY FOR THE DRINKING | | | FOUNTAIN EWC-1 HAS BEEN DELETED. THIS IS REQUIRED PER | | | TABLE 403.1. PLEASE CLARIFY. | | | ****RESPONSE NOTED, BUT PER SECTIONS 606.2(1) AND | | | 1002.1. EACH FIXTURE SHALL HAVE IT OWN SHUT OFF VALVE | | | AND ITS OWN TRAP. THE HI/LOW DRINKING FOUNTAIN HAS ONLY | | | ONE WATER SUPPLY AND ONE TRAP AND AS SUCH IS ONLY ONE | | | FIXTURE. | | | | | | 3. SHT P3 THE WATER RISER DIAGRAM AND THE SANITARY | | | RISER DIAGRAM SHOWS THE SANITARY AND WATER HAVE BEEN | | | DELETED FOR EWC-1 (DRINKING FOUNTAIN). THIS IS REQUIRED | | | PER TABLE 403.1. PLEASE CLARIFY. | | | ****RESPONSE NOTED, BUT PER SECTIONS 606.2(1) AND | | | 1002.1. EACH FIXTURE SHALL HAVE IT OWN SHUT OFF VALVE | | | AND ITS OWN TRAP. THE HI/LOW DRINKING FOUNTAIN HAS ONLY | | | ONE WATER SUPPLY AND ONE TRAP AND AS SUCH IS ONLY ONE | | | FIXTURE. | | | | | | 4. OK | | | 5. OK | | | | | | **********NEW COMMENT********** | | | | | | 1B. NEW SHT P3 SUBMITTED SHALL INCLUDE THE DATE THE | | | SIGNATURE AND SEAL IS AFFIXED AS | | | REQUIRED61G15-23.002(1) & FS 471.025. | | | | | | 2B. IF REVISING SHTS P-1 & P-2, THREE COPIES OF EACH | | | SHEET TO BE REVISED SHALL BE SUBMITTED. SECTION 106.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-04 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-04 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2008-02-04 15:53:18 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | 1. SHT P1 INDICATES THAT EWC-1 IS DELETED. SHT C1 | | | PLUMBING FIXTURE COUNT INDICATES THAT 2 DRINKING | | | FOUNTAINS ARE REQUIRED. DELETING 1 DRINKING FOUNTAIN | | | ONLY LEAVES 1 DRINKING FOUNTAIN. THIS DOES NOT COMPLY | | | WITH TABLE 403.1. PLEASE CLARIFY. | | | | | | 2. SHT P2 INDICATES THE WATER SUPPLY FOR THE DRINKING | | | FOUNTAIN EWC-1 HAS BEEN DELETED. THIS IS REQUIRED PER | | | TABLE 403.1. PLEASE CLARIFY. | | | | | | 3. SHT P3 THE WATER RISER DIAGRAM AND THE SANITARY | | | RISER DIAGRAM SHOWS THE SANITARY AND WATER HAVE BEEN | | | DELETED FOR EWC-1 (DRINKING FOUNTAIN). THIS IS REQUIRED | | | PER TABLE 403.1. PLEASE CLARIFY. | | | | | | 4. SHT P3 SANITARY RISER DIAGRAM SHOWS A DRY HORIZONTAL | | | VENT FOR THE FLOOR SINK WITH A VENT AT FIXTURE R32: | | | REACH IN FROZEN. SECTION 905.3. PLEASE SHOW | | | COMPLIANCE. | | | | | | 5. SHT P3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE | | | CHANGES SHOWN ON SHT P1 AT THE GREASE INTERCEPTORS. | | | SECTION 106.1.1 AND SECTION 901.2.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-04 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-04 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-02 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-01 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-01-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-13 |
Time |
06:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-13 |
Time |
06:33 |
Sent To |
|
|
| Notes |
| 2007-01-13 07:23:58 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS DESIGNED BY THE REGISTERED ARCHITECT. THE | | | ORIGINAL SIGNATURE IS | | | REQUIRED ON THE SEAL, AND THE BUSINESS | | | LICENSE NUMBER, (CERTIFICATE OF | | | AUTHORIZATION), IS REQUIRED IN THE TITLE | | | BLOCK OF EACH SHEET. 61G1-16.004(1)(5) | | | AND FS 481.219 481.2055. | | | ****RESPONSE NOTED, BUT THE CERTIFICATE OF | | | AUTHORIZATION IS NOT INDICATED IN THE TITLE BLOCK OF | | | THE ARCHITECT. (SEE ATTACHED SHEET FROM THE DBPR | | | WEBSITE INDICATE PROPER BUSINESS NUMBER). | | | | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | | | | 7. A5.3 FAMILY TOILET ROOM, (129), | | | WOMENS TOILET ROOM, (130), MEN'S TOILET | | | FOOM, (127). SHALL BE ACCESSIBLE. SUBMIT | | | THE FOLLOWING: | | | FOR W/C'S... | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | FOR STALLS.... | | | A. 11-4.17.3 EXCEPTION 2 THE ACCESSIBLE | | | W/C SHALL BE LOCATED IN THE CORNER, | | | DIAGONAL TO THE DOOR. (SEE MENS TOILET | | | ROOM). | | | ****NOT ADDRESSED | | | FOR URINALS... | | | A. OK | | | B. 11-4.18.4 FLUSH CONTROLS | | | ****NOT ADDRESSED | | | FOR LAVS.... | | | A. OK | | | B. OK | | | C. 11-4.19.5 FAUCETS | | | ****NOT ADDRESSED | | | D. OK | | | | | | 8. OK | | | 9. OK | | | | | | 10. ALL PME & REFRIG. SHEETS. ENGINEERS | | | SHALL LEGIBLY INDICATE THEIR NAME, AND | | | LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS AND CERTIFICATE OF AUTHORIZATION | | | NUMBER OF THE ENGINEERING BUSINESS ON | | | EACH SHEET. 61G15-23.002(2) & FS 471.025. | | | ****RESPONSE NOTED, BUT THE LICENSE NUMBER IS NOT | | | INDICATED IN THE TITLE BLOCK. | | | | | | 11. SHT P1 GREASE INTERCEPTORS SHALL BE | | | SIZED BY THE UTILITY DEPT. ENVIRONMENTAL COMPLIANCE | | | MGR. PLEASE CONTACT LYNN | | | MASSON, (561) 822-2271, FAX (561) | | | 822-2279, OR E-MAIL [email protected] FOR | | | A DETERMINATION ON INTERCEPTOR SIZE. | | | WASTE ORDINANCE #3434. | | | ****RESPONSE NOTED, WAITING FOR A DETERMINATION FROM | | | MR. WILLIAMS. NO MORE ACTION REQUIRED BY THE | | | CONTRACTOR. | | | | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | 15. SHT P-3 WATER HAMMER ARRESTORS ARE | | | REQUIRED AT ALL QUICK CLOSING VALVES, | | | SUCH AS DISH WASHERS, ICE MAKERS, ETC. | | | PLEASE SHOW ONE AT THE ICE MAKER. ALL | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURES, IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN AT | | | THE LAVS IN MENS AND WOMENS TOILET ROOM. | | | SECTION 604.9 AND PDI-WH 201. | | | ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS | | | REQUIRED AT FIXTURE MG07 ICE MAKER. | | | | | | 16. OK | | | 17. OK | | | 18. OK | | | 19. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-08-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-19 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-19 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2006-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS DESIGNED BY THE REGISTERED ARCHITECT. THE | | | ORIGINAL SIGNATURE IS | | | REQUIRED ON THE SEAL, AND THE BUSINESS | | | LICENSE NUMBER, (CERTIFICATE OF | | | AUTHORIZATION), IS REQUIRED IN THE TITLE | | | BLOCK OF EACH SHEET. 61G1-16.004(1)(5) | | | AND FS 481.219 481.2055. | | | | | | 2. SHT D1 DEMO REQUIREMENTS #'S 2 & 3 | | | DEAD ENDS ARE NOT ALLOWED. SECTION | | | 704.5. | | | | | | 3. SHT D1 GREASE INTERCEPTORS SHALL BE | | | PUMPED OUT AND WASHED DOWN PRIOR TO | | | REMOVING. | | | | | | 4. SHTS A1, A5.2 & A9 BREAK ROOM SINK | | | SHALL BE ACCESSIBLE. PLEASE SUBMIT A | | | DETAIL SHOWING THE FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD | | | APPROACH REQUIRED. NO CABINET DOORS | | | ALLOWED IN CLEAR FLOOR SPACE). | | | D. 11-4.24.7 FAUCETS | | | | | | 5. SHT A5.3 DRINKING FOUNTAIN TO BE | | | ACCESSIBLE. SUBMIT A DETAIL SHOWING THE FOLLOWING: | | | A. 11-4.15.2 SPOUT HEIGHT | | | B. 11-4.15.5 CLEARANCES AND CLEAR FLOOR | | | SPACE. (FORWARD APPROACH REQUIRED). | | | | | | 6. SHT A5.2 DETAIL 1 INDICATES A SINK | | | WITH AN EYEWASH STATION. MORE | | | INFORMATION REQUIRED. PLEASE SUBMIT A | | | DETAIL AND MANUFACTURE SPECIFICATION & INSTALLATION | | | SHEETS. | | | | | | 7. A5.3 FAMILY TOILET ROOM, (129), | | | WOMENS TOILET ROOM, (130), MEN'S TOILET | | | FOOM, (127). SHALL BE ACCESSIBLE. SUBMIT | | | THE FOLLOWING: | | | FOR W/C'S... | | | A. 11-4.16.3 HEIGHT | | | B. 11-4.16.4 GRAB BARS | | | C. 11-4.16.5 FLUSH CONTROLS | | | D. 11-4.16.6 DISPENSERS | | | FOR STALLS.... | | | A. 11-4.17.3 EXCEPTION 2 THE ACCESSIBLE | | | W/C SHALL BE LOCATED IN THE CORNER, | | | DIAGONAL TO THE DOOR. (SEE MENS TOILET | | | ROOM). | | | FOR URINALS... | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.4 FLUSH CONTROLS | | | FOR LAVS.... | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | D. 11-4.19.6 MIRRORS | | | | | | 8. SHT A5.3 DETAIL 6 TOILET ELEVATION | | | FOR THE ACCESSIBLE STALL DOES NOT SHOW | | | THE LAV. SECTION 106.1.1. | | | | | | 9. SHT A5.3 FAMILY TOILET, W/C TO BE 18" | | | OFF THE WALL TO CENTERLINE OF THE | | | FIXTURE. SEE FIG. 28. | | | | | | 10. ALL PME & REFRIG. SHEETS. ENGINEERS | | | SHALL LEGIBLY INDICATE THEIR NAME, AND | | | LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS AND CERTIFICATE OF AUTHORIZATION | | | NUMBER OF THE ENGINEERING BUSINESS ON | | | EACH SHEET. 61G15-23.002(2) & FS 471.025 | | | | | | 11. SHT P1 GREASE INTERCEPTORS SHALL BE | | | SIZED BY THE UTILITY DEPT. ENVIRONMENTAL COMPLIANCE | | | MGR. PLEASE CONTACT LYNN | | | MASSON, (561) 822-2271, FAX (561) | | | 822-2279, OR E-MAIL [email protected] FOR | | | A DETERMINATION ON INTERCEPTOR SIZE. | | | WASTE ORDINANCE #3434. | | | | | | 12. SHT P1 CLEANOUTS REQUIRED PER | | | SECTIONS 708.3.1, 708.3.3, & 708.3.5 | | | REQUIRED ON THE SANT., GREASE, AND | | | CONDENSATE SYSTEMS. | | | | | | 13. SHT P1 INDICATES REMOVAL OF ALL | | | FLOOR DRAINS. IN THE INSTALLATION OR | | | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM | | | DEAD ENDS SHALL BE PROHIBITED. SECTION | | | 704.5. | | | | | | 14. SHT P1 MINIMUM FACILITIES REQUIRES | | | TWO DRINKING FOUNTAINS. ONLY A HI/LOW | | | DRINKING FOUNTAIN IS SHOWN. IF A FIXTURE | | | HAS ONLY ONE DRAIN LINE AND ONE SUPPLY | | | LINE IT IS CONSIDERED ONE FIXTURE. | | | PLEASE INDICATE THE LOCATION OF EWC-1 AS | | | SHOWN ON SHT P4 PLUMBING FIXTURE | | | SCHEDULE. TABLE 403.1. | | | | | | 15. SHT P-3 WATER HAMMER ARRESTORS ARE | | | REQUIRED AT ALL QUICK CLOSING VALVES, | | | SUCH AS DISH WASHERS, ICE MAKERS, ETC. | | | PLEASE SHOW ONE AT THE ICE MAKER. ALL | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR THE FIXTURES, IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN AT | | | THE LAVS IN MENS AND WOMENS TOILET ROOM. | | | SECTION 604.9 AND PDI-WH 201. | | | | | | 16. SHT P3 2 WAY CLEANOUTS ARE REQUIRED | | | AT THE INLET AND EXIT OF EACH GREASE | | | INTERCEPTOR. | | | | | | 17. SHT P3 THE SANT. RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN BETWEEN | | | FIXTURE AND 1ST FIXTURE. | | | SHOW ALL PIPE SIZES ON THE RISER | | | DIAGRAM. SECTION 106.1.1 AND TABLES | | | 710.1(1) & 710.1(2). | | | | | | 18. SHT P4 COFFEE BAR PLUMBING EQUIPMENT CONNECTION | | | SCHEDULE CO8. SUBMIT MANUF SPECIFICATION SHEETS FOR THE | | | WATER | | | FILTER. FILTER SHALL COMPLY WITH NSF 42. | | | | | | 19. SUBMIT A CONDENSATE RISER DIAGRAM | | | ISOMETRIC SHOWING ALL PIPE SIZES. | | | SECTION 106.3.5.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-01-11 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-01-11 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2008-01-11 08:41:00 | ***NOT REQUIRED*** | | | | | | PROPOSED REVISIONS DO NOT IMPACT ZONING MATTERS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-12-04 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-12-04 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-12-04 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-08-04 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-08-04 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-08-04 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2006-08-04 00:00:00 | PLANS SUBMITTED FOR PERMIT DO NOT MATCH | | | PLANS APPROVED THROUGH MINOR PD | | | AMENDMENT PROCESS. | | | | | | THE ADDITION OF CONCRETE CURBING AND | | | LANDSCAPABLE AREA IN FRONT OF BALE AND | | | PALLET ENCLOSURE IS REQUIRED AND SHALL | | | BE PROVIDED. LANDSCAPE PLANS (SIGNED AND | | | SEALED) CONSISTENT WITH THE APPROVED | | | MINOR PD AMENDMENT SHALL BE PROVIDED. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER AT | | | 561-822-1435 WITH QUESTIONS. |
|
|