Plan Review Details - Permit 06070683
Plan Review Stops For Permit 06070683
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-16 Cont ID  
Sent By lursu Date 2006-08-16 Time 08:08 Rev Time 0.00
Received By lursu Date 2006-08-16 Time 08:08 Sent To  
Notes
2006-08-16 00:00:00OWNER INFO WAS UPDATED

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-04-14 Cont ID  
Sent By jwitmer Date 2008-04-14 Time 14:57 Rev Time 0.55
Received By jwitmer Date 2008-04-14 Time 14:57 Sent To PC
Notes
2008-04-14 14:59:04LETTER EMEMPT LOCATION TO FIRE SPRINKLERS, BUILDING
 STIPULATION NO MERCHANDISE ON EXTERIOR OF BUILDING.
  
 903.3.1.1.1 EXEMPT LOCATIONS.
  
 AUTOMATIC SPRINKLERS SHALL NOT BE REQUIRED IN THE
 FOLLOWING ROOMS OR AREAS WHERE SUCH ROOMS OR AREAS ARE
 PROTECTED WITH AN APPROVED AUTOMATIC FIRE DETECTION
 SYSTEM IN ACCORDANCE WITH SECTION 907.2 THAT WILL
 RESPOND TO VISIBLE OR INVISIBLE PARTICLES OF
 COMBUSTION. SPRINKLERS SHALL NOT BE OMITTED FROM ANY
 ROOM MERELY BECAUSE IT IS DAMP, OF
 FIRE-RESISTANCE-RATED CONSTRUCTION OR CONTAINS
 ELECTRICAL EQUIPMENT.
 (4)IN ROOMS OR AREAS THAT ARE OF NONCOMBUSTIBLE
 CONSTRUCTION WITH WHOLLY NONCOMBUSTIBLE CONTENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-04-10 Cont ID  
Sent By jwitmer Date 2008-04-10 Time 07:59 Rev Time 1.33
Received By jwitmer Date 2008-04-10 Time 07:59 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-02-05 Cont ID  
Sent By jwitmer Date 2008-02-05 Time 13:36 Rev Time 4.44
Received By jwitmer Date 2008-02-05 Time 13:36 Sent To  
Notes
2008-02-05 13:37:01REV: 3 & 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-07-30 Cont ID  
Sent By jwitmer Date 2007-07-30 Time 10:17 Rev Time 2.22
Received By jwitmer Date 2007-07-30 Time 10:17 Sent To PC
Notes
2007-07-30 10:18:136901 OKEECHOBEE BLVD. / 06070683
 BUILDING PROVISOS:
  
 1) ROOFING PERMIT TO BE A SEPARATE PERMIT WITH
 ASSOCIATED FEES AND REVIEW, NOTE THE HIGHLIGHTED
 SUBSYSTEM REQUIRES ENHANCED FASTENING.
 THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD
 THE FASTENERRESISTANCE BE LESS THAN THAT REQUIRED,
 AS DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNEDAND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT ORREGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED. PLEASE PROVIDE THE RAS 117 CALCULATIONS FOR
 ROOFING SUB-PERMIT.
  
 2) RULE 9B-72 REQUIRES TESTING FOR ROOF ACCESS HATCHES,
 CURRENTLY THERE ARE NO ROOF HATCHES THAT HAVE APPLIED
 FOR STATE APPROVAL. BEFORE A CERTIFICATE OF COMPLETION
 WILL BE ISSUED, THE CONTRACTOR SHALL EITHER OBTAIN A
 PRODUCT APPROVAL THROUGH THE STATE WEBSITE THAT WILL
 MEET THE
 WIND PRESSURES OR APPLY AND RECEIVE LOCAL PRODUCT
 APPROVAL WITHIN THIS JURISDICTION. THE CITY OF WEST
 PALM BEACH HAS THE SAME 10 CRITERIA AS THE STATE
 APPROVAL INCLUSIVE OF THIRD PARTY QUALITY ASSURANCE
 PROGRAM, WITH THE THIRD PARTY BEING APPROVED THROUGH
 THE STATE.
  
 3)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-06-29 Cont ID  
Sent By jwitmer Date 2007-06-29 Time 13:53 Rev Time 3.33
Received By jwitmer Date 2007-06-29 Time 13:53 Sent To  
Notes
2007-06-29 13:55:34CONT:PLAN REVIEW
 KATIE GRINDEL (913)236-3437
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO
 THE FBC 2004 WITH 2006 REVISIONS.
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3-8) COMPLIED.
  
 10A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A-E) COMPLIED
 F)ROOFING ASSEMBLIES THERE ARE CURRENTLY SUBMITTED ARE
 FOUR (4) DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED
 TO THE CITY:
 JOHN MANVILLE FL 1037-R1HASTHE BRR
 ARCHITECTURAL REVIEW STAMP
 JOHN MANVILLE FL644-R2HASTHE BRR
 ARCHITECTURAL REVIEW STAMP
 JOHN MANVILLE FL2948-R1NOT REVIEWED
 GAF FL618-R1HASTHE BRR
 ARCHITECTURAL REVIEW STAMP
  
  
 GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED IN
 THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET THE
 MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT THE
 INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE NOT
 HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND ASSOCIATED
 PRESSURES WILL BE USED. PAGES 7-19, PLEASE HIGHLIGHT
 AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF GENERAL
 LIMITATION # 7
 IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING
 PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF
 LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN
 TAKE PLACE.
 G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN
 HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA
 COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED
 (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED
 WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH
 SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES
 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES
 LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND
 ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE
 THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS
 INDICATED NO ENHANCED FASTENING CAN TAKE PLACE.
 H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE
 ADVISORY BOARD TECHNICAL ADVISORY
 I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY
 THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO
 PICK FROM WHICH ARE YOU GOING TO USE?
  
  
 JOHN MANSVILLE REPORT FL644-R2 MIAMI-DADE NOA SHEET 11
 ISSTARRED, THE MAXIMUM DESIGN PRESSURE IS -52.5
 LIMITATION NUMBER (7) REQUIRES AN ENGINEER , ARCHITECT
 OR REGISTERED ROOFING CONSULTANT TO RUN THE RAS 117
 CALCULATION FOR ROOF ZONES 2 & 3.IF THIS PRODUCT IS
 PICKED PLEASE REMOVE ALL OTHER ROOFING APPROVALS FROM
 THE PACKAGE.
  
 THERE ARE TWO OTHER JOHN MANVILLE PRODUCT APPROVALS
 WITH NOTHING HIGHLIGHTED.
  
  
 10B) OUTSWING STEEL DOOR BY REPUBLIC BUILDERS HAS NOT
 BEEN APPROVED BY THE DESIGNER OF RECORD, PLEASE REVIEW
 AND STAMP WITH SHOP DRAWING STAMP.
  
 11) COMPLIED.
  
 12) ROOF HATCHES: IF THERE ARE NO STATE OR MIAMI-DADE
 REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT
 WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN
 OPTION. THE ROOF HATCH SUBMITTAL FROM BABCOCK-DAVIS
 DOES NOT MEET THE REQUIREMENTS FOR A LOCAL PRODUCT
 APPROVAL THERE HAS TO BE AN INDEPENDENT TEST DONE BY A
 LAB LISTED ON THE STATE WEB SITE PLUS THETHIRD PARTY
 QUALITY ASSURANCEENTITY THAT ARE ALSO LISTED ON THE
 STATE WEBSITE
 ADDRESS IS FLORIDABUILDING.ORG.
 NOTE; BILCO HATCH IS CURRENTLY UNDERGOING TESTING AND
 IS SUPPOSE TO HAVE REPORTS BY THE END OF SUMMER.
  
 13) COMPLIED.
  
 14) COVERSHEET MAXIMUM FLOOR AREA ALLOWABLE REFRENENCES
 THE 2003 IBC PLEASE CORRECT.
  
 15) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-04-03 Cont ID  
Sent By jwitmer Date 2007-04-03 Time 08:18 Rev Time 2.22
Received By jwitmer Date 2007-04-03 Time 08:18 Sent To PC
Notes
2007-06-27 18:57:55ADD: 6901 OKEECHOBEE BLVD.
 CONT:PLAN REVIEW
 KATIE GRINDEL (913)236-3437
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: DENIED
  
 NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO
 THE FBC 2004 WITH 2006 REVISIONS.
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3-8) COMPLIED.
  
 10A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A-E) COMPLIED
 F)ROOFING ASSEMBLIES THERE ARE CURRENTLY SUBMITTED ARE
 FOUR (4) DIFFERENT ROOFING PRODUCT APPROVALS SUBMITTED
 TO THE CITY:
 JOHN MANVILLE FL 1037-R1HASTHE BRR
 ARCHITECTURAL REVIEW STAMP
 JOHN MANVILLE FL644-R2HASTHE BRR
 ARCHITECTURAL REVIEW STAMP
 JOHN MANVILLE FL2948-R1NOT REVIEWED
 GAF FL618-R1HASTHE BRR
 ARCHITECTURAL REVIEW STAMP
  
  
 GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED IN
 THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET THE
 MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT THE
 INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE NOT
 HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND ASSOCIATED
 PRESSURES WILL BE USED. PAGES 7-19, PLEASE HIGHLIGHT
 AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF GENERAL
 LIMITATION # 7
 IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING
 PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF
 LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN
 TAKE PLACE.
 G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN
 HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA
 COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED
 (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED
 WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH
 SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES
 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES
 LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND
 ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE
 THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS
 INDICATED NO ENHANCED FASTENING CAN TAKE PLACE.
 H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE
 ADVISORY BOARD TECHNICAL ADVISORY
 I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY
 THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO
 PICK FROM WHICH ARE YOU GOING TO USE?
  
  
 JOHN MANSVILLE REPORT FL644-R2 MIAMI-DADE NOA SHEET 11
 ISSTARRED, THE MAXIMUM DESIGN PRESSURE IS -52.5
 LIMITATION NUMBER (7) REQUIRES AN ENGINEER , ARCHITECT
 OR REGISTERED ROOFING CONSULTANT TO RUN THE RAS 117
 CALCULATION FOR ROOF ZONES 2 & 3.IF THIS PRODUCT IS
 PICKED PLEASE REMOVE ALL OTHER ROOFING APPROVALS FROM
 THE PACKAGE.
  
 THERE ARE TWO OTHER JOHN MANVILLE PRODUCT APPROVALS
 WITH NOTHING HIGHLIGHTED.
  
  
 10B) OUTSWING STEEL DOOR BY REPUBLIC BUILDERS HAS NOT
 BEEN APPROVED BY THE DESIGNER OF RECORD, PLEASE REVIEW
 AND STAMP WITH SHOP DRAWING STAMP.
  
 11) COMPLIED.
  
 12) ROOF HAATCHES: IF THERE ARE NO STATE OR MIAMI-DADE
 REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT
 WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN
 OPTION. THE ROOF HATCH SUBMITTAL FROM BABCOCK-DAVIS
 DOES NOT MEET THE REQUIREMENTS FOR A LOCAL PRODUCT
 APPROVAL THERE HAS TO BE AN INDEPENDENT TEST DONE BY A
 LAB LISTED ON THE STATE WEB SITE PLUS THETHIRD PARTY
 QUALITY ASSURANCEENTITY THAT ARE ALSO LISTED ON THE
 STATE WEBSITE
 ADDRESS IS FLORIDABUILDING.ORG.
 NOTE; BILCO HATCH IS CURRENTLY UNDERGOING TESTING AND
 IS SUPPOSE TO HAVE REPORTS BY THE END OF SUMMER.
  
 13) COVERSHEET BUILDING TYPE IS AGAIN WRONG, THIS IS
 NOT A TYPE 5B BUILDING IS A 4HR FIRE WALL A TYPE IIIB
 MERCANTILE AND OR BUSINESS OCCUPANCY
 HAS UNLIMITED AREA WHEN FULLY SPRINKLED AND 60 FT
 CLEARENCE AROUND THE BUILDING. SEE SECTION 507.2
  
 14) COVERSHEET MAXIMUM FLOOR AREA ALLOWABLE REFRENENCES
 THE 2003 IBC PLEASE CORRECT.
  
 15) COVERSHEET: TOTAL SQ FT BUILDING SIZELISTED IS
 50,790 THIS IS THIS TENANT SPACE, NOT BUILDING SQ FT
 UNLESS THERE ARE 4 HR WALLS ON EACH SIDE OF THE
 BUILDING! PLANS DO NOT INDICATE THIS!
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
2007-04-03 08:20:00"PLAN REVIEW" I
 PERMIT: 06070683
 ADD: 6901 OKEECHOBEE BLVD.
 CONT:PLAN REVIEW
 KATIE GRINDEL (913)236-3437
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO
 THE FBC 2004 WITH 2006 REVISIONS.
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3-8) COMPLIED.
  
 10) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A-E) COMPLIED
 F) GAF BUILT UP ROOF: NO SUBSYSTEM HAS BEEN HIGHLIGHTED
 IN THE REPORT SUBMITTED . UNDER THE FLORIDA COVERSHEET
 THE MIAMI-DADE REPORT IS HIGHLIGHTED (03-0430.11) BUT
 THE INDIVIDUAL SUBSYSTEMS LISTED WITHIN THE REPORT ARE
 NOT HIGHLIGHTED INDICATING WHICH SUBSYSTEM AND
 ASSOCIATED PRESSURES WILL BE USED. PAGES 7-19, PLEASE
 HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES LISTED. IF
 GENERAL LIMITATION # 7
 IS INDICATED AND ZONES 2 & 3 REQUIRE ENHANCED FASTENING
 PLEASE PROVIDE THE CALCULATIONS FOR RAS 117. IF
 LIMITATION # ( IS INDICATED NO ENHANCED FASTENING CAN
 TAKE PLACE.
 G) JOHN MANSVILLEBUILT UP ROOF: NO SUBSYSTEM HAS BEEN
 HIGHLIGHTED IN THE REPORT SUBMITTED . UNDER THE FLORIDA
 COVERSHEET THE MIAMI-DADE REPORT IS HIGHLIGHTED
 (03-0430.11) BUT THE INDIVIDUAL SUBSYSTEMS LISTED
 WITHIN THE REPORT ARE NOT HIGHLIGHTED INDICATING WHICH
 SUBSYSTEM AND ASSOCIATED PRESSURES WILL BE USED. PAGES
 7-19, PLEASE HIGHLIGHT AND SEE MAXIMUM DESIGN PRESSURES
 LISTED. IF GENERAL LIMITATION # 7IS INDICATED AND
 ZONES 2 & 3 REQUIRE ENHANCED FASTENING PLEASE PROVIDE
 THE CALCULATIONS FOR RAS 117. IF LIMITATION # ( IS
 INDICATED NO ENHANCED FASTENING CAN TAKE PLACE.
 H) ROOF HATCHES: SEE PALM BEACH COUNTY BUILDING CODE
 ADVISORY BOARD TECHNICAL ADVISORY
 I) OVERHEAD GARAGE DOOR: NO REPORTS WAS SUBMITTED, ONLY
 THE FLORIDA COVER SHEET, THERE ARE (3) SERIES 591 TO
 PICK FROM WHICH ARE YOU GOING TO USE?
  
 11) COMPLIED.
  
 12) ROOF HAATCHES: IF THERE ARE NO STATE OR MIAMI-DADE
 REPORTS AVAILABLE THEN A LOCAL PRODUCT APPROVAL REPORT
 WITH THIRD PARTY QUALITY ASSURANCE PROGRAM WILL BE AN
 OPTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-12 Cont ID  
Sent By jwitmer Date 2006-12-12 Time 13:47 Rev Time 0.00
Received By jwitmer Date 2006-12-12 Time 13:47 Sent To  
Notes
2006-12-12 14:04:42 
 "PLAN REVIEW" I
 PERMIT: 06070683
 ADD: 6901 OKEECHOBEE BLVD.
 CONT:PLAN REVIEW
 KATIE GRINDEL (913)236-3437
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 NOTE IN FOR PLAN REVIEW ONLY, WILL NEED TO CONFORM TO
 THE FBC 2004 WITH 2006 REVISIONS.
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMPLIED.
  
 4A) THE THREE NUMBERS SUPPLIED ON THE PLAN FOR THE
 CERTIFICATE OF AUTHORIZATION NONE ARE THE COA FOR
 FLORIDA.
 PLEASE PROVIDE THIS NUMBER ON ALL SHEETS REQUIRED,
 AA26001022
  
 4B) THE OTHER ISSUE WITH THE DBA NAME IS BOICE RAIDL
 RAIDL ARCHITECTECTS INC. NOT THE BRR.
  
 5) THIS REQUEST IS FOR THE WHOLE BUILDING, NOT TENANT
 SPACE, UNLESS THE DEMISSING WALLS ARE 4 HR FIRE WALLLS
 BREAKING THIS TENANT SPACE INTO A SEPERATE BUILDING WE
 NEED THE AREA FOR THE COMPLETE BUILDINGPLEASE SHOW THE
 AREA INCREASES ON THE PLANS THE NOTE SUBMITTALS ARE
 THROWN OUT ONCE THE PERMIT IS ISSUED. TABLE 503. 5)
 SHEET C-1 BUILDING CODE SUMMARY, TYPE
 OF CONSTRUCTION, PLANS INDICATE A VB,
 FOR MERCANTILE TABLE 503 INDICATES AN
 ALLOWABLE 9,000 SQ FT. PLEASE PROVIDE
 WHAT INCREASES WERE TAKEN TO ACHIEVE THE
 49,960 SQ FT OF ACTUAL BUILDING?PROVIDE
 CALCULATIONS.NOW THIS IS GOING TO BE FOR
 THE BUILDING NOT TENANT SPACE!!!!!
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) MOST OF THE PRODUCT APPROVALS THAT HAVE FLORIDA
 REPORTS HAVE BEEN PRINTED.
 THERE IS A COMMENT ON EACH REPORT THAT STILL REQUIRES
 FLORIDA APPROVAL COVER SHEETS.PRODUCT APPROVALS
 SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) 2ND REQUEST,THE DESIGN PROFESSIONALS STILL HAVE
 NOT REVIEWED AND APPROVED ANY REPORTS,
 )W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
  
 10) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OVERHEAD DOORS - COMPLIED.
 B) STANLEY ACCESS- COMPLIED.
 C) REPUBLIC BUILDERS PRODUCTS- COMPLIED.
 D) CURRIES EXTERIOR DOORS- COMPLIED
 E)CECO DOORS NEED THE MANUFACTURERS RECOMENDED
 ERECTIION INSTRUCTION, INSPECTOR TO VERIFY THE PSF ON
 SITE.
 F) GAF BUILT UP ROOF NO SUBSYSTEM HAS BEEN HIGHLIGHTED
 AS TO WHICH WILL BE USED, PLEASE NOTE LIMITATIONS.G)
 JOHNS MANVILEE MODIFIED SAME COMMENT AS ABOVE. H) ROOF
 HATCHES RULE 9B-72 THE REVISIONS EFFECTIVE 1-01-06
 REQUIRE PRE-ENGINEERED
 ROOF ACCESS HATCHES TO HAVE APPROVALS. ACOPY OF THIS
 STATEMENT IS ATTACHED.
 I) PRE-ENGINEERED A/C STANDS- NOT CURBS CURBS ARE SHOWN
 DETIAL# 3 S-5.
  
 12) DEALS WITH THE REQUIRIMENT FOR PRODUCT APPROVALS
 SEE 10H AND ATTACHMENT. BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-01 Cont ID  
Sent By jwitmer Date 2006-09-01 Time 13:01 Rev Time 0.77
Received By jwitmer Date 2006-09-01 Time 13:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By jwitmer Date 2006-08-10 Time 09:37 Rev Time 10.00
Received By jwitmer Date 2006-08-10 Time 09:37 Sent To  
Notes
2006-08-10 00:00:00BUILDING PLAN REVIEW
  
 "PLAN REVIEW" I
 PERMIT: 06070683
 ADD: 6901 OKEECHOBEE BLVD.
 CONT:PLAN REVIEW
 KATIE GRINDEL (913)236-3437
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SEE ALL ARCHITECTURAL SHEETS
 SIGNATURES ARE COPIES, PLANS ARE
 REQUIRED TO BE ORIGINAL SIGNATURES.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) CERTIFICATE OF AUTHORIZATION REQUIRED
 FOR ARCHITECTURAL FIRM. 481.219 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 5) SHEET C-1 BUILDING CODE SUMMARY, TYPE
 OF CONSTRUCTION, PLANS INDICATE A VB,
 FOR MERCANTILE TABLE 503 INDICATES AN
 ALLOWABLE 9,000 SQ FT. PLEASE PROVIDE
 WHAT INCREASES WERE TAKEN TO ACHIEVE THE
  
 49,960 SQ FT OF ACTUAL BUILDING?PROVIDE
 CALCULATIONS.NOW THIS IS GOING TO BE FOR
 THE BUILDING NOT TENANT SPACE!!!!!
  
 6) PLANS DO NOT MENTION 2004 EXISTING
 BUILDING CODE AND THE REQUIREMENT 301.5
 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 7) SOILS REPORT IS A COPY NOT AN
 ORIGINAL SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OVERHEAD DOOR WILL REQUIRE FL
 COVERSHEET AND ASSOCIATED REPORT.
 B) STANLEY ACCESS TECHNOLOGIES WILL
 REQUIRE FL COVER SHEET AND ASSOCIATED
 REPORT.
 C) GAF MATERIAL REQUIRES FL COVERSHEET.
  
 11)THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 __X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 12) ROOF HATCH IS THIS NEW? IF SO
 PROVIDE PRODUCT APPROVAL FOR UNIT.
  
 13) PROVIDE INFORMATION ON THE
 ATTACHMENT OF CURBING FOR A/C UNITS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-06-13 Cont ID  
Sent By dpalmer Date 2008-06-13 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2008-06-13 Time 15:33 Sent To PC
Notes
2008-06-13 15:37:39** DENIED**
  
 1) NOTE: ELECTRICAL PERMIT IS ALREADY CLOSED AND
 FINALED OUT. NO FURTHER ELECTRICAL REVISIONS MAY BE
 SUBMITTED, STAMPED OR REVIEWED. MAY APPLY FOR NEW
 ELECTRICAL PERMIT AND SUBMIT REVISIONS UP UNTIL
 BUILDING PERMIT IS CLOSED OUT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-03-17 Cont ID  
Sent By dpalmer Date 2008-03-17 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2008-03-17 Time 18:26 Sent To  
Notes
2008-03-17 18:26:25REVISIONS OK,
 STAMPED ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-01-29 Cont ID  
Sent By dpalmer Date 2008-01-29 Time 09:08 Rev Time 0.00
Received By dpalmer Date 2008-01-29 Time 09:08 Sent To  
Notes
2008-01-29 09:11:32REVISED SHEETS E1,1.1,1.2,2,2.1,4, 4.1,4.2, RE-1,
 REM-1, EM-1
  
 **
 *** FOR INFORMATION FOR THIS REVISION AND ANY OTHER
 REVISION. PLEASE BE SURE THE SCOPE OF WORK FOR
 REVISIONS ACTUALLY CORRELATE WITH PLANS. PLEASE SEE FOR
 EXAMPLE THE SCOPE OF WORK AS SUBMITTED WITH REVISIONS
 CONTAINS SUBSTANTIALLY LESS ITEMS THAN WHAT IS REVISED
 ON PLANS.
 THE ACCURACY OF THIS SCOPE OF WORK CHANGES GREATLY
 AFFECT THE REVIEW TIMES OF SAID PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-07-31 Cont ID  
Sent By dpalmer Date 2007-07-31 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2007-07-30 Time 15:29 Sent To PC
Notes
2007-07-31 09:34:09 
  
 REDLINED,
 CONTROL REQUIRED FOR DOCK LIGHTS, 13-415.1.ABC.1.1

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-07-10 Cont ID  
Sent By dpalmer Date 2007-07-10 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2007-07-09 Time 20:05 Sent To I
Notes
2007-07-10 11:56:192007-07-10 11:56:19
  
 **** UNSAT 6THREVIEW ****
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
  
 1) NOTE: PLEASE SEE THERE ARE SOME ITEMS ON THE ENERGY
 CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS. PLEASE
 KNOW THAT THIS IS THE FIRST REVIEW OF THE INPUT DATA
 REPORT AS IT WAS NOT SUBMITTED ON THE LAST REVIEW. THIS
 WAS NOTED ON PREVIOUS REVIEW.
 PLEASE BE SURE ALL AREAS WHICH ARE DESIGNATED ON PLANS
 ARE THAT OF THE SAME AREAS AS DESIGNATED ON THE ENERGY
 CALCULATIONS. PLEASE SEE SOME OF THESE AREAS ARE
 MISSING AND/OR DO NOT COORDINATE AT THIS TIME. PLEASE
 SEE IT IS NOT POSSIBLE FOR THE METHOD OF CONTROL FOR
 LIGHTING TO BE SHOWN AS *MANUAL ON/OFF* WHEN THE
 LIGHTING ON PLANS AND AS REQUIRED UNDER CHAPTER 13 OF
 THE FBC REQUIRES LIGHTING TO BE AUTOMATED.
 PLEASE SEE SOME SEPARATE SPACES STILL DO NOT INDICATE
 OVER RIDE DEVICES. PLEASE SEE 13-415.1.ABC1.2 AS THESE
 AREAS SHALL CONTAIN EITHER OF THE CONTROLS AS SET-FORTH
 HOWEVER MAY NOT ONLY CONTAIN A SINGLE POLE OR THREE-WAY
 SWITCH. THE DEVICE MUST BE CAPABLE OF OVER RIDING THE
 TIMED SCHEDULING WHEN ON THE TIMED SCHEDULE SYSTEM. IF
 AN AREA IS NOT ON THE SCHEDULED TIMER CONTROLS OR
 ENERGY MANAGEMENT SYSTEM THEM SEPARATE DEVICES SUCH AS
 OS TYPE DEVICES ARE PERMITTED.
 PLEASE SEE AREAS WHICH DO NOT CONTAIN OVER RIDE
 CONTROLS FOR EXAMPLE: PHARMACY, FAMILY TOILET ROOM (NO
 CONTROLS) , LIGHTING OUTSIDE OF TOILETS, ETC PLEASE SEE
 LIGHTS OUTSIDE OF THESE SAME ROOMS AND OTHER AREAS.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 2) NOTE: PLEASE SEE THE COVER SHEET C1 STILL INDICATES
 THE WRONG CODE FOR ELECTRICAL.. ALL OF THE PREVIOUS
 REVIEW STATED THE CODES WHICH NEEDED TO BE ON PLANS.
 PLEASE SEE THE PLANS STILL INDICATE THE 2002
 NEC/NFPA-70. THIS SHOULD BE THE 2005 NEC/ NFPA-70. THIS
 CAN BE REDLINED.
  
 3) NOTE: PLEASE KNOW THAT IT MAY BE POSSIBLE PENDING
 OTHER TRADE REVIEWS TO PROVIDE WHAT IS KNOWN AS A
 *PROVISO* FOR THE LIGHTING CONTROL PART OF THE COMMENT
 ABOVE AND COMMENT NUMBER 2.
 THE *PROVISO* WOULD SET-FORTH CONDITIONS THAT THE
 PERMIT CAN BE ISSUED AND THE LIGHTING CONTROLS ON PLANS
 WOULD NEED TO BE ADDRESSED AND SUBMIT REVISED
 ELECTRICAL PLANS WITHIN 30DAYS OF PERMIT ISSUANCE.
 PLEASE KNOW HOWEVER THAT THE ENERGY CALCULATIONS MAY
 NOT BE DONE AS A *PROVISO* AND MUST BE ADDRESSED AT
 THIS TIME.
 PLEASE BE SURE ANY REVISED ENERGY CALCULATIONS WILL BE
 REQUIRED TO CONTAIN ALL SIGNATURES FROM THE RESPONSIBLE
 PERSONS OF RECORD INCLUDING THAT OF THE OWNER AGENT.
 13-103.1.1.1
 *** IMPORTANT , THE REVIEW FROM THE MECHANICAL REVIEWER
 HAS NOT YET BEEN DONE FOR THE ENERGY CALCULATIONS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-09 20:06:072007-07-09 20:06:07
 PLANS REMOVED FROM INCOMING FOR ELECTRICAL REVIEW.
 PLANS WILL BE RETURNED TO INCOMING WAITING FOR COMM
 BOARD ONCE ELECTRICAL REVIEW IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-06-10 Cont ID  
Sent By dpalmer Date 2007-06-10 Time 14:07 Rev Time 0.00
Received By dpalmer Date 2007-06-10 Time 12:45 Sent To  
Notes
2007-06-10 14:07:49** UNSAT 4TH REVIEW **
  
  
  
 ********** WAL-MART BUILD -OUT******
  
 1) NOTE:PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR
 "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
 EVEN WHEN PLANS ARE 100% CODE COMPLIANT, THE REVIEW
 WILL STILL BE IN FAILED STATUTES AS THE REVIEW OF
 PERMIT APPLICATION(S), LICENSING ETC WILL STILL TAKE
 PLACE.
  
 2) NOTE: PLEASE SUBMIT ONLY DOCUMENTS RELEVANT TO
 PROJECT AND SCOPE OF WORK. PLEASE SEE THE SUBMITTED
 PACKAGE CONTAINS NUMEROUS DOCUMENTS WHICH ARE NOT
 RELEVANT OR NO LONGER RELEVANT TO SCOPE OF WORK OR DOES
 NOT NEED TO BE IN PACKAGE. PLEASE KNOW THAT PRINTING
 OUT OF ON-LINE NOTES DOES NOT NEED TO PLACED IN PACKAGE
 FOR OUR REVIEW AS WE ALREADY HAVE THE NOTES, SEVERAL OF
 THESE WERE SUBMITTED.
 FBC 106.3
  
 3) NOTE: PLEASE SEE EFP SHEETS WHICH ARE NOT SEALED AS
 REQUIRED PER FAC 61G15-23.001.
 PLEASE SEE FS471.025
 ** THIS IS REQUIRE WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 4) NOTE: PLEASE SEE MISSING REQUIRED LICENSE
 INFORMATION ON TITLE BLOCKS FOR EFP SHEETS. PLEASE SEE
 FS 471.023 WHICH REQUIRES A CERTIFICATE OF
 AUTHORIZATION NUMBER AND TO BE PLACED ON TITLE BLOCKS.
 THIS IS FOR SACRAMENTO ENGINEERING.
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 5) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW AS
 THE PLANS WERE NOT CHANGED. PLEASE SEE THE A SHEETS
 STILL INDICATE TWO CODES. THE FA/EFP SHEETS INDICATE
 CODES NOT UNDER THE FBC. (IBC,IFC )
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE THE PREVIOUS REVIEWS WHICH MENTIONED THE
 CODES REQUIRED DEPENDING ON WHEN PERMIT APPLICATION IS
 MADE. PLEASE SEE THE PLANS NOW LIST BOTH CODES FOR 2005
 AND 2002 ARE BEING SHOWN ON PLANS FOR DESIGN ETC??
 PLEASE MAKE THE CORRECTIONS.
 PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS
 #6 WILL BE REQUIRED.
 PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH
 SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED
 UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES
 ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS.
  
 6) NOTE:PLEASE SEE THE NOTES WITH RESPECT TO FBC
 CHAPTER 13 REMAIN IN AFFECT.
 PLEASE SEE THE ENERGY CALCULATIONS ARE NOT PER
 13-415.1.AB.1.1. PLEASE SEE THE PROGRAM OF FLA-COM
 VERSION 3.0 IS THE LATEST EDITION ADOPTED BY THE STATE
 AND CHAPTER 13.
 WHEN THESE ARE DONE, THE ENERGY CALCULATIONS MUST ALSO
 CONTAIN THE INPUT DATA REPORT TO COINCIDE WITH THE
 PLANS FOR REVIEW.
 PLEASE SEE THESE WILL BE REQUIRED TO BE SIGNED, DATED
 AND SEALED AS PREVIOUSLY NOTED. THE FLA-COM SHEETS HAVE
 SPACE FOR THIS.
 PLEASE SEE NOT ALL SEPARATE SPACES WHICH CONTAIN FLOOR
 TO CEILING HEIGHT PARTITIONS CONTAIN CONTROLS AS
 REQUIRED PER 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE SYMBOL LEGEND DOES NOT STATE TIMES OF
 DEVICES.
 PLEASE COORDINATE ALL DOCUMENTS.
 RESPONSE FROM DESIGNER ONLY RESPONDED TO ONE OF THE
 COMMENTS MADE IN THIS NOTE FROM PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED ARE
 STILL NOT SIGNED, DATED AND SEALED BY THE DESIGNER OF
 RECORD NOR ARE THEY UNDER THE CORRECT CODE. THEY ARE
 DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS NOT IN
 EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH
 PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1,
 13-415.2 AND 13-103.1.1.1.
 REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT
 THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006
 REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER
 13.
 PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS,
 WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN
 COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE
 SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON
 OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME
 SCHEDULING ETC.
 PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH
 CHAPTER 13.
  
 PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM
 DETAILS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE DESIGNER(S) OF RECORD.
  
 7) NOTE:PLEASE SEE THIS WAS THE NOTE FROM PREVIOUS
 REVIEW. THIS REMAINS, AS ONLY SOME SHEETS WERE REVISED
 TO CHANGE DOOR SWING. PLEASE SEE SHEETS WHICH WERE NOT
 REVISED STILL INDICATE INWARD SWING ON DOOR.
 ** PREVIOUS REVIEW NOTE **
 THIS IS TAKEN FROM PREVIOUS REVIEW AS NO CHANGES TO
 ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE SEE THE MAIN
 ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND UNOBSTRUCTED
 PATH WHICH IT DOES NOT. THERE IS A WALL CLEARLY SHOWN
 WHICH WOULD IMPEDE THE EGRESS OUT OF THE ROOM IN AN
 EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS, AN
 ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND
 THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT
 ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR
 WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED
 TO CONTAIN PANIC HARDWARE.
 110.26, 90.4
  
 8) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR
 EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1,
 .2, AND .3(4).
 PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES
 AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION
 SHEETS WHICH ARE FROM TWO CODE CYCLES AGO.
 PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE
 2002 NFPA-72
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-20 Cont ID  
Sent By dpalmer Date 2007-02-20 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2007-02-19 Time 10:10 Sent To  
Notes
2007-02-20 15:17:50 
 ********** UNSAT 3RD REVIEW *************
  
 ********** WAL-MART BUILD -OUT******
  
 ** PLEASE SEE PLANS ARE STILL ONLY SUBMITTED FOR "PLAN
 REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 1 NOTE: PLEASE KNOW THAT IT IS MOST HELPFUL FOR A
 REVIEW IF A RESPONSE LETTER OF SOME TYPE IS SUBMITTED
 BY THE DESIGNER OF RECORD. PLEASE SEE THE RESPONSE
 LETTER CONTAINS TWO RESPONSES WHICH ARE BOTH LISTED AS
 ITEM #1 AND DO NOT INDICATE WHAT THEY ARE BEING
 RESPONDED TO??
  
 2) NOTE:PLEASE SEE THE PREVIOUS REVIEWS WHICH
 MENTIONED THE CODES REQUIRED DEPENDING ON WHEN PERMIT
 APPLICATION IS MADE. PLEASE SEE THE PLANS NOW LIST BOTH
 CODES FOR 2005 AND 2002 ARE BEING SHOWN ON PLANS FOR
 DESIGN ETC?? PLEASE MAKE THE CORRECTIONS.
 PLEASE SEE THE 2005 NFPA-70 AND THE 2004 FBC REVISIONS
 #6 WILL BE REQUIRED.
 PLEASE SEE NUMEROUS SECTIONS OF THE FIRE SHEETS WHICH
 SPECIFY THE 1996 NFPA-72 AND OTHER CODES NOT ADOPTED
 UNDER THE STATE. PLEASE SEE ALL OF THE NEW CODES
 ADOPTED IN THE REFERENCE TABLES AND CORRECT PLANS.
  
 3) NOTE:PLEASE SEE THAT THE ENERGY CALCULATIONS
 SUBMITTED ARE STILL NOT SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD NOR ARE THEY UNDER THE CORRECT CODE.
 THEY ARE DONE AND SUBMITTED UNDER THE 2001 IEC WHICH IS
 NOT IN EFFECT IN THE STATE OF FLORIDA. PLEASE SEE BOTH
 PREVIOUS REVIEWS WHICH MENTION TO SEE 13-415.1.AB.1.1,
 13-415.2 AND 13-103.1.1.1.
 REVIEW FOR COMPLIANCE OF CHAPTER 13 CAN NOT BE DONE AT
 THIS TIME. PLEASE ALSO SEE THAT UNDER THE 2006
 REVISIONS TO THE 2004 FBC CONTAINS CHANGES TO CHAPTER
 13.
 PLEASE SEE PREVIOUS NOTE FOR DEVICES ON RESTROOMS,
 WHICH IS NOT CLEAR WHETHER OR NOT THEY CONTAIN
 COVERAGE. PLEASE SPECIFY THE TYPE OF DEVICES. PLEASE
 SEE NOT INFORMATION IS SPECIFIED FOR MAXIMUM TIMES ON
 OVER RIDE OF THESE DEVICES AND OTHER SYSTEMS, TIME
 SCHEDULING ETC.
 PLEASE SUBMIT COMPLETED PLANS FOR COMPLIANCE WITH
 CHAPTER 13.
  
 PLEASE SEE 2004 FBC W/ 2006 REVISIONS CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM
 DETAILS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE DESIGNER(S) OF RECORD.
  
 4) NOTE: THIS IS TAKEN FROM PREVIOUS REVIEW AS NO
 CHANGES TO ROOM LAYOUT OR DOOR HAS BEEN MADE. PLEASE
 SEE THE MAIN ELECTRICAL ROOM SHALL CONTAIN A CLEAR AND
 UNOBSTRUCTED PATH WHICH IT DOES NOT. THERE IS A WALL
 CLEARLY SHOWN WHICH WOULD IMPEDE THE EGRESS OUT OF THE
 ROOM IN AN EMERGENCY. IN THE CASE OF FIRE OR BLINDNESS,
 AN ELECTRICIAN OR OTHER PERSON COULD BECOME TRAPPED AND
 THIS SCENARIO CREATES A LIFE SAFETY ISSUE WHICH IS NOT
 ACCEPTABLE TO THIS AHJ. PLEASE ALSO SEE THAT THE DOOR
 WILL BE REQUIRED TO OPEN OUTWARD AND WILL BE REQUIRED
 TO CONTAIN PANIC HARDWARE.
 110.26, 90.4
  
 5) NOTE: PLEASE SEE THAT THE PANEL LRX WHICH IS STILL
 BEING SHOWN IN A STORAGE ROOM. PLEASE RELOCATE. THIS IS
 A LIFE SAFETY AND PROPERTY SAFETY ISSUE AND WILL NOT BE
 PERMITTED IN THIS ROOM.
 PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY
 TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY
 IGNITABLE MATERIALS ETC.
  
 6) NOTE: PLEASE SEE PLANS STILL FOR A KIRK KEY
 INTERLOCK WHICH DOES NOT PROVIDE A *FAIL SAFE*
 OPERATION. THIS OFFICE HAS REVIEWED DOCUMENTATION
 PROVIDED. THIS OFFICE HAS NOT MENTIONED THAT A LISTED
 TRANSFER SWITCH IS REQUIRED HOWEVER WE ARE REQUIRING
 THE DEVICE IS LISTED FOR USE AND THAT IT PROVIDES
 COMPLETE FAIL SAFE OPERATION.
 DEVICES AS SUBMITTED DO NOT PROVIDE THIS REQUIREMENT.
 PLEASE SEE 110.3, 90.7, 702.6 ETC.
 PLEASE SUBMIT ACTUAL SPEC/MANUFACTURES CUT SHEETS.
  
 7) NOTE: PLEASE SHOW ALL STROBES/HORN DEVICES NEW OR
 EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1,
 .2, AND .3(4).
 PLEASE SEE NOTE ABOVE WITH RESPECT TO NUMEROUS CODES
 AND SECTIONS BEING REFERENCE ON THE FIRE PROTECTION
 SHEETS WHICH ARE FROM TWO CODE CYCLES AGO.
 PLEASE ALSO KNOW THAT WE ARE ALSO CURRENTLY UNDER THE
 2002 NFPA-72
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-19 10:37:322007-02-19 10:37:32
 REVIEW TO CONTINUE ON 2/20 NOTES TO FOLLOW , PLANS WILL
 BE PLACED INTO A "F" STATUS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 19:12 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 17:45 Sent To  
Notes
2006-12-07 19:12:27********** UNSAT 2ND REVIEW *************
  
 ********** WAL-MART NEW /REMODEL******
  
 ** PLEASE SEE PLANS WERE ONLY SUBMITTED FOR "PLAN
 REVIEW" AND HAVE NOT BEEN SUBMITTED FOR PERMIT. PLEASE
 KNOW THAT AT THIS TIME AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTS NEW CODES AND THESE WILL CHANGE
 AND AFFECT DESIGNS SUBMITTED ON PLANS. PLEASE KNOW THAT
 AS THE PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION BEFORE THE END OF TODAY'S DATE, ALL PLANS
 WILL BE REQUIRED TO BE REDESIGNED UNDER THE NEW
 CODE(S).
  
 ** PLEASE SEE SOME COMMENTS BELOW WHICH STILL NEED TO
 BE ADDRESSED. PLEASE SEE SOME OF THESE ARE NOTED WITH A
 "NO" OR "OK". THOSE OF WHICH MAY CONTAIN AN "OK/NO"
 MEANS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED.
  
 ** PLEASE SEE THERE ARE ALSO SOME NEW NOTES.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE:NO/OK. PLEASE SEE MISSING INFORMATION IS
 STILL REQUIRED FOR THE ARCHITECTURAL FIRM. PLEASE SEE
 THE NUMBER WHICH WAS ADDED TO THE TITLE BLOCKS IS THAT
 OF THE STATE OF FLORIDA'S CORPORATION NUMBER WHICH IS
 NOT THE CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 THE NUMBER NEEDED FOR DOING BUSINESS AS AN
 ARCHITECTURAL FIRM IS ISSIED FROM THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 THIS IS REQUIRED FOR ALL "A" SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
 THE MEP SHEETS SEEM TO HAVE BEEN ADJUSTED TO INCLUDE
 ONLY THE PE'S AS INDIVIDUALS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED INFORMATION ON TITLE
 BLOCKS FOR ARCHITECTURAL AND ENGINEERING FIRMS. PLEASE
 SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUES 481.219 FOR THE ARCHITECTURAL FIRM AND PLEASE
 SEE FAC61G15-23.002 AND FS 471.023 FOR THE ENGINEERING
 FIRM.
 PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER'S
 FOR INDIVIDUAL DESIGNERS OF RECORD.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR BOTH FIRMS REQUIRED
 ON TITLE BLOCKS ALSO.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 4) NOTE:NO, PLEASE SEE THE CODES WERE ADDED AS
 REQUESTED, HOWEVER SINCE A PERMIT HAS NOT BEEN APPLIED
 FOR THE FOLLOWING CODES WILL BE THE NEW RELEVANT CODES
 IN EFFECT TO THE NEW DESIGN. PLEASE SEE THE 2005
 NFPA-70 AND THE 2004 FBC REVISIONS #6 WILL BE
 REQUIRED.
 THE OTHER CODES AS NOTED BELOW WILL REMAIN.
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE SEE PLANS MENTIONS THE 2004
 FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER
 27 OF THE 2004 FBC ADOPTED THE 2002
 NFPA-70 (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 NFPA-72 2002, NFPA-101 2003.
  
 5) NOTE:NO, PLEASE SEE AS THE CODE HAS CHANGED THERE
 ARE NOW NEW REQUIREMENTS IN THE SAME SECTIONS AS NOTED
 BELOW. PLEASE SEE HOWEVER THAT THE COMPLETED
 INFORMATION FROM THE PREVIOUS REVIEW WAS NOT ADDRESSED
 AS NEEDED ON PLANS. PLEASE SEE ENERGY CALCULATIONS
 SUBMITTED ARE NOT COMPLETE AS NEEDED. THESE ARE ALSO
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER
 OF RECORD. PLEASE SEE NO LIGHTING POWER DENSITIES WERE
 SUBMITTED. PLEASE SEE BATH ROOMS WHICH ARE NOT A SINGLE
 STALL, WILL REQUIRE A DIFFERENT TYPE OF OCCUPANCY
 SENSOR TYPE DEVICE. THESE SHALL BE THE TYPE WHICH WILL
 ACTIVATE UNDER OTHER CONDITIONS OTHER THAN MOTION.
 PLEASE SEE AS NO TIMES ON OVER RIDES COULD NOT BE
 LOCATED THERE ARE ITEMS WHICH CAN NOT BE REVIEWED FOR
 COMPLIANCE AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2004 FBC CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST CASE FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY MANG SYSTEM
 DETAILS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2.ABC.1 FOR TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY CALCULATIONS ARE SIGNED,
 DATED AND SEALED BY THE DESIGNER(S) OF RECORD.
  
 6) NOTE: OK.
  
 7) NOTE:NO, PLEASE SEE THE MAIN ELECTRICAL ROOM SHALL
 CONTAIN A CLEAR AND UNOBSTRUCTED PATH WHICH IT DOES
 NOT. THERE IS A WALL CLEARLY SHOWN WHICH WOULD IMPEDE
 THE EGRESS OUT OF THE ROOM IN AN EMERGENCY. IN THE CASE
 OF FIRE OR BLINDNESS, AN ELECTRICIAN OR OTHER PERSON
 COULD BECOME TRAPPED AND THIS SCENARIO CREATES A LIFE
 SAFETY ISSUE WHICH IS NOT ACCEPTABLE TO THIS AHJ.
 PLEASE ALSO SEE THAT THE DOOR WILL BE REQUIRED TO OPEN
 OUTWARD AND WILL BE REQUIRED TO CONTAIN PANIC
 HARDWARE.
 110.26, 90.4
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS SHALL BE
 REQUIRED FOR MAIN ELECTRICAL ROOM. PLEASE ALSO SEE
 PANIC HARDWARE AND DOORS CHANGES WILL BE REQUIRED FOR
 NEW EQUIPMENT.
  
 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS
 STORAGE WILL NOT BE PERMITTED, HOWEVER THIS OFFICE
 INCLUDING THE FIRE MARSHAL?S OFFICE HAS BEEN IN TOO
 NUMEROUS STORAGE ROOMS WHICH MATERIALS ARE PLACED
 IN-FRONT OF EQUIPMENT ETC. THIS IS ALSO A LIFE SAFETY
 HAZARD AND WILL REQUIRE THIS PANEL TO BE RELOCATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL WHICH IS BEING SHOWN IN STORAGE ROOM
 SHALL BE A DEDICATED ELECTRICAL/EQUIPMENT ROOM OR
 PLEASE RELOCATE PANEL.
 PLEASE SEE 110.26, 408.7, AND 240.24 AS STORAGE OF ANY
 TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF EASILY
 IGNITABLE MATERIALS.
  
 9) NOTE: NO, PLEASE SEE AS OF THE MANUFACTURES
 SPECS/CUT SHEETS SUBMITTED THE EQUIPMENT BEING PROPOSED
 IS NOT ACCEPTABLE TO THIS AHJ AS BEING USED OR
 PROVIDING ANY FAIL SAFE OPERATION OR PROVIDES
 INADVERTENT OPERATION. PLEASE SEE UL LISTING 1081 ETC.
 PLEASE SEE OTHER LISTINGS WHICH WILL REQUIRE THIS
 EQUIPMENT BEING SERVICE ENTRANCE RATED, AND MUST MEET
 SECTIONS GIVEN.
 PLEASE SEE 110.3, 90.7, 702.6 ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ACTUALSPEC/MANUFACTURES CUT SHEETSFOR
 THE MAIN SW BD AND PROPOSED"KIRK KEY INTERLOCK".
 PLEASE KNOW, THIS OFFICE HAS SEEN SOME SYSTEMS WHICH DO
 NOT MEET THE CODE WITH RESPECT TO TRANSFER EQUIPMENT
 AND LISTED FOR THE INTENDED USE.
 702.6, 110.3
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SHOW ANY STROBES/HORN DEVICES NEW OR
 EXISTING MEETING THE 2004 FBC CHAPTER 11. 11-4.28.1,
 .2, AND .3(4).
 THIS WAS NOT IN PREVIOUS REVIEW AS IT HAS NOW BECOME A
 REQUIRED REVIEW FOR THE ELECTRICAL PLAN REVIEW STAFF.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 09:12 Rev Time 0.00
Received By dpalmer Date 2006-07-30 Time 18:57 Sent To  
Notes
2006-08-03 00:00:00********** UNSAT *************
  
 **********WAL-MART NEW /REMODEL******
  
 ** PLEASE SEE PLANS WERE ONLY SUBMITTED
 FOR "PLAN REVIEW" AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
  
 1) NOTE: PLEASE SEE ALL ARCHITECTURAL
 SHEETS CONTAIN A RAISED SEAL OVER A
 "PHOTO-COPIED" SIGNATURE OF THE
 ARCHITECT OF RECORD. PLEASE KNOW UNDER
 FS 481.221 AND FAC 61G1-16.004 THE
 SIGNATURE SHALL BE ORIGINAL. SEALED
 PHOTO-COPIED PLANS ARE NOT ACCEPTABLE.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE ALSO SEE "S-1, S-2, AND
 S-3, AS THESE ALSO CONTAIN A RAISED SEAL
 OVER A PHOTO-COPIED SIGNATURE>
 PLEASE SEE FS 472.025, FAC 61G17
 REQUIRED FOR BOTH SETS AND WHETHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS FOR
 ARCHITECTURAL AND ENGINEERING FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUES 481.219
 FOR THE ARCHITECTURAL FIRM AND PLEASE
 SEE FAC61G15-23.002 AND FS 471.023 FOR
 ENGINEERING FIRM.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE NUMBER'S FOR INDIVIDUAL
 DESIGNERS OF RECORD.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR BOTH
 FIRMS REQUIRED ON TITLE BLOCKS ALSO.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES AT A MINIMUM.
 PLEASE SEE PLANS MENTIONS THE 2004
 FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER
 27 OF THE 2004 FBC ADOPTED THE 2002
 NFPA-70 (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 NFPA-72 2002, NFPA-101 2003.
  
 5) NOTE: PLEASE SEE 2004 FBC CHAPTER 13.
 PLEASE SEE 13-413.1ABC.1, PROVIDE WORST
 CASE FOR FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE PROVIDE LIGHTING CONTROL/ ENERGY
 MANG SYSTEM DETAILS.
 PLEASE SEE 13-415.1.AB.1 ,
 13-415.2.ABC.1 FOR TABLES 415.2.C.1 AND 415.2.B.1.
 PLEASE ALSO BE SURE ALL ENERGY
 CALCULATIONS ARE SIGNED, DATED AND
 SEALED BY THE DESIGNER(S) OF RECORD.
  
 6) NOTE: PLEASE SEE PANELS IN
 DELI/BAKERY ARE WHICH DO NOT SEEM TO
 MEET 110.26 FOR MIN CLEARANCES.
  
 7) NOTE: PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS
 SHALL BE REQUIRED FOR MAIN
 ELECTRICAL ROOM. PLEASE ALSO SEE PANIC
 HARDWARE AND DOORS CHANGES WILL BE
 REQUIRED FOR NEW EQUIPMENT.
  
 8) NOTE: PLEASE SEE PANEL WHICH IS BEING
 SHOWN IN STORAGE ROOM SHALL BE A
 DEDICATED ELECTRICAL/EQUIPMENT ROOM OR
 PLEASE RELOCATE PANEL.
 PLEASE SEE 110.26,408.7, AND 240.24 AS
 STORAGE OF ANY TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF
 EASILY IGNITABLE
 MATERIALS.
  
 9) NOTE: PLEASE SUBMIT ACTUAL
 SPEC/MANUFACTURES CUT SHEETSFOR THE
 MAIN SW BD AND PROPOSED"KIRK KEY
 INTERLOCK". PLEASE KNOW, THIS OFFICE HAS
 SEEN SOME SYSTEMS WHICH DO NOT MEET THE
 CODE WITH RESPECT TO TRANSFER EQUIPMENT
 AND LISTED FOR THE INTENDED USE.
 702.6, 110.3
  
 10) NOTE: PLEASE CLARIFY OF ALL
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE ALREADY SHOWN AT 125%.
 215.3,230.42 ETC
 PLEASE PROVIDE DETAIL ON LOAD
 CALCULATIONS.
 220.
  
 11) NOTE: PLEASE CLARIFY RECEPTS IN
 BATH(S) AS GFI PROTECTED OR NOT.
 PLEASE SEE PANEL SCHEDULE DOES NOT SEEM
 TO INDICATE THE REQUIRED GFI PROTECTION.
 210.8B1
  
 ** PLEASE BE SURE TO SEE ANY POSISBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS/DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2006-08-02 00:00:00PLANS WILL BE GOING INTO A "F" STATUS,
 NOTES TO FOLLOW.
2006-07-30 00:00:00IN ELECTRIC FOR REVIEW,

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-02-08 Cont ID  
Sent By rchokshi Date 2007-02-08 Time 11:24 Rev Time 0.00
Received By rchokshi Date 2007-02-08 Time 11:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-01-18 Cont ID  
Sent By rchokshi Date 2007-01-18 Time 10:48 Rev Time 0.00
Received By rchokshi Date 2007-01-18 Time 10:32 Sent To B
Notes
2007-01-18 10:48:48FAILED FOR FOLLOWING REASONS:
  
 I. ENG REVIEW DWGS ARE NOT SEALED BY P E
 2.PLEASE SHOW POLLUTION PREVENTION SILT FENCE AROUND
 THE CONSTRUCTION SITE ON THE DRAWINGS.
 3.IT APPEARES THAT YOU ARE GOING TO USE THE EXISTING
 DRAINAGE SYSTEM FOR STORM WATER. IS THAT TRUE? AREYOU
 ADDING ANY DRAINAGE STORM WATER PIPE, OR EXFILTRATION
 TRENCH, OR POND?ALL STORM WATER GO IN THE POND?
 PLEASE EXPLAIN ANY CHANGES IN STORM WATER DRAINAGE
 SYSTEM. DO YOU HAVE ANY STORM WATER OUTLET GOING IN
 CITY SYSTEM OR SFWMD CANAL?
 PLEASE PROVIDE EACH ITEM SEPARATELY TO EXPEDITE THE
 PERMITTING PROCESS. THANKS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By rchokshi Date 2006-09-01 Time 13:53 Rev Time 0.00
Received By rchokshi Date 2006-09-01 Time 13:24 Sent To  
Notes
2006-09-01 00:00:00FAILED:
  
 1. NEED POLLUTION PREVENTION
 PLANS,BEFORE,DURING,& AFTER. DUMPSTER
 ENCLOSURE DETAILS PER CITY OF WPB MUST
 BE INCLUDED IN THE DRAWINGS
 2. PRE & POST CONST. PERVIOUS,IMPERVIOUS
 AREA, STORM WATER CAL.,CRITERIA FOR
 RUNOFF CAL.,CONTROL STUCTURES DETAILS IF
 ANY, EXFILTRATION TRENCHES, PIPES ETC.,
 CAL.,WET-DRY RETENTION POND AREAES ETC.
 IF ANY, WE LIKE TO KNOW HOW YOU ARE
 GOING TO TAKE CARE OF STORM WATER. SFWMD
 PERMIT, GEOTECHNICAL REPORT ETC,
 3. UTILITY REVIEW MUST BE APPROVED FROM
 45TH STREET (MANNY G.) BEFORE WE
 APPROVE.
 4. CITY OF WPB DETAIS STANDARDS MUST BE
 INCLUDED IN THE DRAWINGS FOR SIDEWALK,
 PARKINGS,HANDICAP PARKINGS PER ADA
 STANDARDS MUST BE INCLUDED IN THE
 DRAWINGS,
 5. SITE ELEVATIONS, CENTER OF ROAD
 ELEVATIONS,SIDEWALK AND FIRST FLOOR
 ELEVATIONS MUST BE PER FLORIDA CODES &
 FIRST FLOOR ELE MUST BE HIGH ENOUGH SO
 NOT BE FLOODED.
  
 PLEASE RESPOND EACH ITEM SEPARATELY
 UNDER ENGINEERING REVIEW.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-04-04 Cont ID  
Sent By mawillia Date 2008-04-04 Time 15:49 Rev Time 0.00
Received By mawillia Date 2008-04-04 Time 15:21 Sent To  
Notes
2008-04-04 15:27:53*****02/27/08 REVISION, APPROVED*****
  
  
 REVISED PLAN SHEETS A7,E1, AND E1.1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-02-07 Cont ID  
Sent By mawillia Date 2008-02-07 Time 14:05 Rev Time 0.00
Received By mawillia Date 2008-02-07 Time 12:56 Sent To  
Notes
2008-02-07 14:05:47****08/24/07 REVISION, APPROVED*****
  
  
 REVISED PLAN SHEETS A7. A7A, FP2, FP2.3, E1, AND E1.1
 WERE STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-07-18 Cont ID  
Sent By mawillia Date 2007-07-18 Time 17:48 Rev Time 0.00
Received By mawillia Date 2007-07-18 Time 17:29 Sent To  
Notes
2007-07-18 17:33:47*****APPROVED*****
  
 NO OTHER FIRE PLAN REVIEW REQUIRED UNLESS THERE HAVE
 BEEN CHANGES TO THE FLOOR PLAN, LIFE SAFETY, LIGHTING,
 OR FIRE PROTECTION SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-07-03 Cont ID  
Sent By mwennerg Date 2007-07-03 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2007-07-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-03-22 Cont ID  
Sent By mawillia Date 2007-03-22 Time 15:59 Rev Time 0.00
Received By mawillia Date 2007-03-22 Time 14:08 Sent To  
Notes
2007-03-22 15:47:07******UNSAT******
  
 *PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW:
  
  
  
 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
 ADD THIS COMMENT TO SHEET EFP2
  
 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
 MAKE THE NECESSARY CORRECTIONS ON SHEET EFP2, UNDER
 AHJ/COMPLIANCE NOTE #8 AND ALSO IN THE SEQUENCE OF
 OPERATIONS DETAIL,TO REFLECT THIS OPERATION.
  
 *NEW CMMENT:
  
  
 1.IN REGARDS TO NFPA 72, NATIONAL FIRE ALARM CODE,
 THE 2002 EDITION (NOT 1996) SHOULD BE REFERENCED.MAKE
 THE NECESSARY CORRECTIONS ON SHEET EFP2.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-25 Cont ID  
Sent By mawillia Date 2007-01-25 Time 12:09 Rev Time 0.00
Received By mawillia Date 2007-01-25 Time 12:09 Sent To  
Notes
2007-01-25 12:47:38******UNSAT******
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW (10/10/2006) WHICH HAVE NOT
 BEEN MARKED APPROVED.IN ADDITION SEE NEW COMMENT.
  
  
  
 01.)NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.(APPROVED)
  
 02.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241. (APPROVED)
  
 03)ON THE APPROPIATE EXTERIOR ELEVATION SHEET,
 SHOW/DISPALAY THE SUITE UNIT NUMBER OF THIS 6901
 OKEECHOBEE BOULEVARD SHOPPING PLAZA.AS PER WEST PALM
 BEACH CODE, CHARACTERS ( NUMBERS AND/OR LETTERS) SHALL
 BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 (APPROVED)
  
 04.)SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER SYSTEM (APPROVED)AND FIRE ALARM
 SYSTEM.(SEE NEW COMMENT)
  
 05.)FIRE SPRINKLER SHALL BE MAINTAINED OPERATIONAL
 UNTIL SUCH SUCH TIMETHAT THE SYSTEM IS DEMOLISHED.
 PRIOR TO THE SPRINKLER SYSTEM BEING TAKEN OUT OF
 SERVICE, NOTIFICATION AND APPROVAL SHALL BE ATTAINED
 FROM THE FIRE PREVENTION BUREAU.(APPROVED)
  
 06.)DEMOLITION OPERATIONS INVOLVING THE USE OF
 CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITH
 NFPA 51B.(APPROVED)
  
 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. (SEE
 NEW COMMENT)
  
 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. (SEE
 NEW COMMENT)
  
 09.)LOCK-BOX ENTRY KEY SYSTEM WILL BE REQUIRED.SHOW
 THE LOCATION OF THIS DEVICE ON THE APPROPIAITE PLAN
 SHEET(S).(APPROVED)
  
 10.)INTERIOR FINISH FOR WALLS AND CEILINGS SHALL BE
 CLASS "A" OR CLASS "B".
  
 11.)ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 12.)PANIC HARDWARE TO BE INSTALLED ON EXIT DOORS WITH
 AN OCCUPANT LOAD OF ONE HUNDRED PERSONS OR MORE.IN
 RELATION TO POWERED DOORS, REFERENCE NFPA 101, 7.2.1.9
  
 13.)SHOW ON THE APPROPIATE FIRE PROTECTION PLAN
 SHEET(S) THE LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.(APPROVED)
  
 NEW
  
 14.CLASS A MERCANTILE OCCUPANCIES (GREATER THAN
 30,000 SQ. FT.) SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM.PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By mawillia Date 2006-10-10 Time 16:54 Rev Time 0.00
Received By mawillia Date 2006-10-10 Time 15:02 Sent To  
Notes
2006-10-10 15:14:52******DENIED******
  
  
  
 01.)NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 02.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03)ON THE APPROPIATE EXTERIOR ELEVATION SHEET,
 SHOW/DISPALAY THE SUITE UNIT NUMBER OF THIS 6901
 OKEECHOBEE BOULEVARD SHOPPING PLAZA.AS PER WEST PALM
 BEACH CODE, CHARACTERS ( NUMBERS AND/OR LETTERS) SHALL
 BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
  
 04.)SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM
 MODIFICATION.
  
 05.)FIRE SPRINKLER SHALL BE MAINTAINED OPERATIONAL
 UNTIL SUCH SUCH TIMETHAT THE SYSTEM IS DEMOLISHED.
 PRIOR TO THE SPRINKLER SYSTEM BEING TAKEN OUT OF
 SERVICE, NOTIFICATION AND APPROVAL SHALL BE ATTAINED
 FROM THE FIRE PREVENTION BUREAU.
  
 06.)DEMOLITION OPERATIONS INVOLVING THE USE OF
 CUTTING AND WELDING SHALL BE DONE IN ACCORDANCE WITH
 NFPA 51B.
  
 07.)FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE AND
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
  
 08.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 09.)LOCK-BOX ENTRY KEY SYSTEM WILL BE REQUIRED.SHOW
 THE LOCATION OF THIS DEVICE ON THE APPROPIAITE PLAN
 SHEET(S).
  
 10.)INTERIOR FINISH FOR WALLS AND CEILINGS SHALL BE
 CLASS "A" OR CLASS "B".
  
 11.)ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 12.)PANIC HARDWARE TO BE INSTALLED ON EXIT DOORS WITH
 AN OCCUPANT LOAD OF ONE HUNDRED PERSONS OR MORE.
  
 13.)SHOW ON THE APPROPIATE FIRE PROTECTION PLAN
 SHEET(S) THE LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHERS AT DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-06-05 Cont ID  
Sent By adarroug Date 2008-06-05 Time 13:52 Rev Time 0.00
Received By adarroug Date 2008-06-05 Time 13:52 Sent To M
Notes
2008-06-05 13:52:30TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 09:28 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 09:28 Sent To  
Notes
2008-05-27 15:55:28TO "COMM" BD#5
2008-05-21 09:28:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 10:30 Sent To B
Notes
2008-04-11 10:30:50TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 16:25 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 16:25 Sent To FIRE
Notes
2008-04-08 16:25:40TO"F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 16:08 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 16:08 Sent To  
Notes
2008-03-06 16:08:29TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 15:11 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 15:11 Sent To P
Notes
2008-03-06 15:12:07TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-08 Cont ID  
Sent By adarroug Date 2008-01-08 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-01-08 Time 16:14 Sent To  
Notes
2008-01-08 16:17:06TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-30 Cont ID  
Sent By dpalmer Date 2007-07-30 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2007-07-30 Time 15:29 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-09 Cont ID  
Sent By adarroug Date 2007-07-09 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-07-09 Time 16:16 Sent To  
Notes
2007-07-18 15:49:20TO "COMM" BD#30/PLANS ON RACK--LARGE ROLLED PLANS AND
 PAPERWORK
2007-07-09 16:17:25WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 14:15 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 14:15 Sent To  
Notes
2007-06-05 13:53:14TO "COMM" BD#51--PLANS ON RACK--LARGE FOLDED
2007-05-16 14:16:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-07 Cont ID  
Sent By adarroug Date 2007-02-07 Time 11:13 Rev Time 0.00
Received By adarroug Date 2007-02-07 Time 11:13 Sent To  
Notes
2007-02-19 07:44:10TO COMM BOARD SPACE #59
2007-02-07 11:13:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 08:23 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 08:23 Sent To  
Notes
2006-11-29 15:13:21TO COMM BOARD #39
2006-11-21 08:24:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By mawillia Date 2006-10-10 Time 15:02 Rev Time 0.00
Received By mawillia Date 2006-07-14 Time 11:21 Sent To  
Notes
2006-08-11 00:00:008/11/06-MOVED TO "COMM" BD#60
2006-07-28 00:00:00TO COMM BOARD # 43
2006-07-14 00:00:00WAITING FOR "COMM" BD-CHANGING FROM
 WINN-DIXIE TO WALMART, MAY NEED ZONING
 FOR CHANGE OF USE

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-06-25 Cont ID  
Sent By rregueir Date 2008-06-25 Time 13:55 Rev Time 0.00
Received By rregueir Date 2008-06-25 Time 13:31 Sent To PC
Notes
2008-06-25 13:56:01REVISED M2, R2, R3 AND ENERGY CALCS

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-03-20 Cont ID  
Sent By hmoser Date 2008-03-20 Time 17:42 Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 17:38 Sent To  
Notes
2008-03-20 17:44:41PLAN DENIED
 PAGE R-2 NOT STAMPED BY ARCHITECT
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-01-23 Cont ID  
Sent By rregueir Date 2008-01-23 Time 16:13 Rev Time 0.00
Received By rregueir Date 2008-01-23 Time 16:12 Sent To  
Notes
2008-01-23 16:13:14REVISED PG M1, R1, R2, R3

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-01-23 Cont ID  
Sent By rregueir Date 2008-01-23 Time 16:10 Rev Time 0.00
Received By rregueir Date 2008-01-23 Time 11:29 Sent To  
Notes
2008-01-23 14:32:26REVISION 3 PG M2: DENIED
  
 NOTE: A FOUR PAGE SCOPE-OF-WORK REPORT WAS PROVIDED TO
 SHOW NATURE AND LOCATION OF CHANGES. THIS REPORT DOES
 NOT INDICATE ANY MECHANICAL PLANS AS PART OF THIS
 REVISION. HOWEVER, PAGES M1, M2, R1, R2 AND R3 ARE ALL
 INCLUDED IN THIS REVISION.
  
 1. PG M2: ROOFTOP UNIT SCHEDULE HAS BEEN REVISED TO
 REFLECT THE NEW OWNER-SUPPLIED EQUIPMENT. IN
 CONJUNCTION WITH THAT CHANGE, NOTE #9 HAS BEEN UPDATED
 TO REFLECT THE EFFICIENCY RATINGS OF THE NEWLY
 SPECIFIED EQUIPMENT. THE EFFICIENCIES LISTED IN THIS
 NOTE DO NOT CORRESPOND WITH THE CURRENT PERMIT ENERGY
 CALCULATIONS. IN MOST CASES, THE EFFICIENCIES HAVE GONE
 DOWN. PROVIDE REVISED ENERGY CALCULATIONS WHICH
 INCORPORATE THE NEW EQUIPMENT EFFICIENCIES.
  
 2. PG M2: THE 5 TON UNIT SHOWS AN EFFICIENCY RATING OF
 12.6 SEER. THE MINIMUM EFFICIENCY REQUIRED FOR A UNIT
 THIS SIZE IS 13.0 SEER IN ACCORDANCE WITH FBC TABLE
 13-407.1.ABC.3.2A. THIS IS A PRESCRIPTIVE MINIMUM
 REGARDLESS OF WHAT PASSES ON THE CALCULATIONS IN
 ACCORDANCE WITH FBC 13-400.1. PG M2 WILL NOT PASS
 REVIEW UNTIL THE NEW INFORMATION IS COORDINATED WITH
 REVISED ENERGY CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-07-17 Cont ID  
Sent By rregueir Date 2007-07-17 Time 18:34 Rev Time 0.00
Received By rregueir Date 2007-07-17 Time 17:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-09 Cont ID  
Sent By rregueir Date 2007-06-09 Time 15:26 Rev Time 0.00
Received By rregueir Date 2007-06-09 Time 15:47 Sent To  
Notes
2007-06-09 15:26:49PLAN CHECK ONLY. THIS PLAN WAS REVIEWED UNDER THE 2004
 FBC BEFORE THE EFFECTIVE DATE OF THE 2006 REVISIONS
 (DECEMBER 8,2006). UPON RESUBMITTAL FOR PERMIT, THE
 PLANS WILL NEED TO BE REVIEWED TO VERIFY COMPLIANCE
 WITH THE LATEST EDITION OF THE FBC IN EFFECT AT THE
 TIME OF ACTUAL PERMIT APPLICATION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-03-17 Cont ID  
Sent By rregueir Date 2007-03-17 Time 11:06 Rev Time 0.00
Received By rregueir Date 2007-03-17 Time 11:06 Sent To  
Notes
2007-03-17 11:15:24*******3RD PLAN CHECK ONLY*******
  
 THESE COMMENTS ARE NUMBERED TO CORRESPOND WITH PREVIOUS
 CPMMENTS AND RESPONSES DATED12/13/06 FOR THE PURPOSE OF
 CONTINUITY.
  
 1. PLEASE HAVE THE ENGINEER OF RECORD AFFIX HIS OR HER
 OFFICIAL SEAL ALONG WITH SIGNATURE AND DATE PER FBC
 106.1
  
 2. OK
  
 3. OK
  
 4. PLEASE INCORPORATE OUTSIDE AIR CALCULATIONS (LABELED
 'VENTILLATION SUMMARY') ON TO PLANS AND/OR HAVE THE
 ENGINEER OF RECORD AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID ACCOMPANYING DATA PER FBC
 106.1
  
 5. OK
  
 NOTE: SEPARATE PERMITS/APPLICATIONS WILL BE REQUIRED
 FOR WALK-IN COOLERS/FREEZERS, HITCHEN HOODS, HOOD
 SUPPRESSION SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS OR
 IF YOU FIND THEM TO BE UNCLEAR IN ANY WAY, PLEASE FEEL
 FREE TO CONTACT ME VIA PHONE OR EMAIL. MY CONTACT
 INFORMATION IS LISTED BELOW.
  
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By pkrauss Date 2006-12-13 Time 15:15 Rev Time 0.00
Received By pkrauss Date 2006-12-13 Time 15:15 Sent To  
Notes
2006-12-13 15:31:02********2ND PLAN CHECK ONLY*******
  
  
 1.PLEASE PROVIDE ENERGY CALCULATIONS IN ACCORDANCE
 WITH 2004 FBC CHAPTER 13 SECTION 13-101.1.3.
  
 2.PLEASE PROVIDE ANCHORING DETAILS FOR THE CURBS TO
 THE ROOF DECK.PLEASE NOTE CURBS SHALL BE A MINIMUM OF
 8"ABOVE THE ROOF SURFACE PER 2004 FBC 1509.7.
  
 3.EQUIPMENT STANDS LOCATED ON THE ROOF IN WHICH THE
 ROOFING MATERIAL IS REQUIRED UNDER THE STAND, THE
 CLEARANCE REQUIRED BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL SHALL BE IN ACCORDANCE WITH
 2004 FBC TABLE 1509.7.PLEASE NOTE, PRODUCT APPROVALS
 REQUIRED FOR EQUIPMENT STANDS LOCATED ON THE ROOF.
  
 4.PLAN SHEET M2 OUTSIDE AIR IS INDICATED ON THE
 ROOFTOP UNIT SCHEDULE.PLEASE INDICATE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 5.PLAN SHEET M2 ROOFTOP UNIT SCHEDULE DOES NOT
 INDICATE DUCT SMOKE DETECTOR ON UNITS 1,2, 9, 11 & 12.
 PER 2004 FMC 606.2.1 SMOKE DETECTORS SHALL BE INSTALLED
 INSUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER
 THAN 2,000 CFM.WHERE MULTIPLE AIR HANDLING SYSTEMS
 WHERE THE AGGREGATE AIR IS GREATER THAN 2,000 CFM, DUCT
 SMOKE DETECTORS WILL BE REQUIRED IN ALL UNITS
 REGARDLESS OF THE THE CAPACITY, 2004 FMC 606.2.2.
  
 PLEASE NOTE, ADDITIONAL PERMITS & PLANS REQUIRED FOR
 THE HOOD, GREASE DUCT & FIRE SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By pkrauss Date 2006-10-06 Time 10:27 Rev Time 0.00
Received By pkrauss Date 2006-10-06 Time 10:27 Sent To  
Notes
2006-10-06 00:00:00PROVISO:PLAN CHECK ONLY
  
 1.PLAN SHEET M1, THE ROOFTOP EQUIPMENT
 PIPING RUNOUT INDICATES 3/4" FOR ALL
 UNITS.PLEASE NOTE, CONDENSATE SHALL BE
 INSTALLED PER MANUFACTURER'S
 SPECIFICATIONS, FULL LINE SIZE FOR
 PROPER DRAINAGE.
  
 2.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION & WALK-IN
 COOLERS.PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-06-04 Cont ID  
Sent By kstevens Date 2008-06-04 Time 18:07 Rev Time 0.00
Received By kstevens Date 2008-06-04 Time 18:07 Sent To  
Notes
2008-06-04 18:11:36DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P3 VENT FOR FIXTURE MG07 NOT APPROVED. VENT
 SHALL NOT OFFSET HORIZONTALLY UNTILL 6" ABOVE THE FLOOD
 RIM LEVEL OF THE FLOOR SINK. SECTION 905.4.
  
 2. SHT P3 VENT FOR FLOOR SINK SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. SECTION 905.3.
 (FLOOR SINK BY COL. LINE 6/E-D.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-06-04 Cont ID  
Sent By kstevens Date 2008-06-04 Time 18:06 Rev Time 0.00
Received By kstevens Date 2008-06-04 Time 18:05 Sent To  
Notes
2008-06-04 18:07:02REVISION OK--SHTS P1 & P2

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-03-29 Cont ID  
Sent By kstevens Date 2008-03-29 Time 13:36 Rev Time 0.00
Received By kstevens Date 2008-03-29 Time 13:36 Sent To  
Notes
2008-03-29 14:00:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P1 INDICATES THAT EWC-1 IS DELETED. SHT C1
 PLUMBING FIXTURE COUNT INDICATES THAT 2 DRINKING
 FOUNTAINS ARE REQUIRED. DELETING 1 DRINKING FOUNTAIN
 ONLY LEAVES 1 DRINKING FOUNTAIN. THIS DOES NOT COMPLY
 WITH TABLE 403.1. PLEASE CLARIFY.
 ****RESPONSE NOTED, BUT PER SECTIONS 606.2(1) AND
 1002.1. EACH FIXTURE SHALL HAVE IT OWN SHUT OFF VALVE
 AND ITS OWN TRAP. THE HI/LOW DRINKING FOUNTAIN HAS ONLY
 ONE WATER SUPPLY AND ONE TRAP AND AS SUCH IS ONLY ONE
 FIXTURE.
  
 2. SHT P2 INDICATES THE WATER SUPPLY FOR THE DRINKING
 FOUNTAIN EWC-1 HAS BEEN DELETED. THIS IS REQUIRED PER
 TABLE 403.1. PLEASE CLARIFY.
 ****RESPONSE NOTED, BUT PER SECTIONS 606.2(1) AND
 1002.1. EACH FIXTURE SHALL HAVE IT OWN SHUT OFF VALVE
 AND ITS OWN TRAP. THE HI/LOW DRINKING FOUNTAIN HAS ONLY
 ONE WATER SUPPLY AND ONE TRAP AND AS SUCH IS ONLY ONE
 FIXTURE.
  
 3. SHT P3 THE WATER RISER DIAGRAM AND THE SANITARY
 RISER DIAGRAM SHOWS THE SANITARY AND WATER HAVE BEEN
 DELETED FOR EWC-1 (DRINKING FOUNTAIN). THIS IS REQUIRED
 PER TABLE 403.1. PLEASE CLARIFY.
 ****RESPONSE NOTED, BUT PER SECTIONS 606.2(1) AND
 1002.1. EACH FIXTURE SHALL HAVE IT OWN SHUT OFF VALVE
 AND ITS OWN TRAP. THE HI/LOW DRINKING FOUNTAIN HAS ONLY
 ONE WATER SUPPLY AND ONE TRAP AND AS SUCH IS ONLY ONE
 FIXTURE.
  
 4. OK
 5. OK
  
 **********NEW COMMENT**********
  
 1B. NEW SHT P3 SUBMITTED SHALL INCLUDE THE DATE THE
 SIGNATURE AND SEAL IS AFFIXED AS
 REQUIRED61G15-23.002(1) & FS 471.025.
  
 2B. IF REVISING SHTS P-1 & P-2, THREE COPIES OF EACH
 SHEET TO BE REVISED SHALL BE SUBMITTED. SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-02-04 Cont ID  
Sent By kstevens Date 2008-02-04 Time 15:39 Rev Time 0.00
Received By kstevens Date 2008-02-04 Time 15:39 Sent To  
Notes
2008-02-04 15:53:18DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P1 INDICATES THAT EWC-1 IS DELETED. SHT C1
 PLUMBING FIXTURE COUNT INDICATES THAT 2 DRINKING
 FOUNTAINS ARE REQUIRED. DELETING 1 DRINKING FOUNTAIN
 ONLY LEAVES 1 DRINKING FOUNTAIN. THIS DOES NOT COMPLY
 WITH TABLE 403.1. PLEASE CLARIFY.
  
 2. SHT P2 INDICATES THE WATER SUPPLY FOR THE DRINKING
 FOUNTAIN EWC-1 HAS BEEN DELETED. THIS IS REQUIRED PER
 TABLE 403.1. PLEASE CLARIFY.
  
 3. SHT P3 THE WATER RISER DIAGRAM AND THE SANITARY
 RISER DIAGRAM SHOWS THE SANITARY AND WATER HAVE BEEN
 DELETED FOR EWC-1 (DRINKING FOUNTAIN). THIS IS REQUIRED
 PER TABLE 403.1. PLEASE CLARIFY.
  
 4. SHT P3 SANITARY RISER DIAGRAM SHOWS A DRY HORIZONTAL
 VENT FOR THE FLOOR SINK WITH A VENT AT FIXTURE R32:
 REACH IN FROZEN. SECTION 905.3. PLEASE SHOW
 COMPLIANCE.
  
 5. SHT P3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 CHANGES SHOWN ON SHT P1 AT THE GREASE INTERCEPTORS.
 SECTION 106.1.1 AND SECTION 901.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-04 Cont ID  
Sent By kstevens Date 2008-02-04 Time 15:39 Rev Time 0.00
Received By kstevens Date 2008-02-04 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-02 Cont ID  
Sent By kstevens Date 2007-03-02 Time 10:14 Rev Time 0.00
Received By kstevens Date 2007-03-01 Time 10:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-13 Cont ID  
Sent By kstevens Date 2007-01-13 Time 06:33 Rev Time 0.00
Received By kstevens Date 2007-01-13 Time 06:33 Sent To  
Notes
2007-01-13 07:23:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS DESIGNED BY THE REGISTERED ARCHITECT. THE
 ORIGINAL SIGNATURE IS
 REQUIRED ON THE SEAL, AND THE BUSINESS
 LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. 61G1-16.004(1)(5)
 AND FS 481.219 481.2055.
 ****RESPONSE NOTED, BUT THE CERTIFICATE OF
 AUTHORIZATION IS NOT INDICATED IN THE TITLE BLOCK OF
 THE ARCHITECT. (SEE ATTACHED SHEET FROM THE DBPR
 WEBSITE INDICATE PROPER BUSINESS NUMBER).
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. A5.3 FAMILY TOILET ROOM, (129),
 WOMENS TOILET ROOM, (130), MEN'S TOILET
 FOOM, (127). SHALL BE ACCESSIBLE. SUBMIT
 THE FOLLOWING:
 FOR W/C'S...
 A. OK
 B. OK
 C. OK
 D. OK
 FOR STALLS....
 A. 11-4.17.3 EXCEPTION 2 THE ACCESSIBLE
 W/C SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR. (SEE MENS TOILET
 ROOM).
 ****NOT ADDRESSED
 FOR URINALS...
 A. OK
 B. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED
 FOR LAVS....
 A. OK
 B. OK
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
 D. OK
  
 8. OK
 9. OK
  
 10. ALL PME & REFRIG. SHEETS. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, AND
 LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. 61G15-23.002(2) & FS 471.025.
 ****RESPONSE NOTED, BUT THE LICENSE NUMBER IS NOT
 INDICATED IN THE TITLE BLOCK.
  
 11. SHT P1 GREASE INTERCEPTORS SHALL BE
 SIZED BY THE UTILITY DEPT. ENVIRONMENTAL COMPLIANCE
 MGR. PLEASE CONTACT LYNN
 MASSON, (561) 822-2271, FAX (561)
 822-2279, OR E-MAIL [email protected] FOR
 A DETERMINATION ON INTERCEPTOR SIZE.
 WASTE ORDINANCE #3434.
 ****RESPONSE NOTED, WAITING FOR A DETERMINATION FROM
 MR. WILLIAMS. NO MORE ACTION REQUIRED BY THE
 CONTRACTOR.
  
 12. OK
 13. OK
 14. OK
  
 15. SHT P-3 WATER HAMMER ARRESTORS ARE
 REQUIRED AT ALL QUICK CLOSING VALVES,
 SUCH AS DISH WASHERS, ICE MAKERS, ETC.
 PLEASE SHOW ONE AT THE ICE MAKER. ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES, IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN AT
 THE LAVS IN MENS AND WOMENS TOILET ROOM.
 SECTION 604.9 AND PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS
 REQUIRED AT FIXTURE MG07 ICE MAKER.
  
 16. OK
 17. OK
 18. OK
 19. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-19 Cont ID  
Sent By kstevens Date 2006-08-19 Time 16:02 Rev Time 0.00
Received By kstevens Date 2006-08-19 Time 16:02 Sent To  
Notes
2006-08-19 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS DESIGNED BY THE REGISTERED ARCHITECT. THE
 ORIGINAL SIGNATURE IS
 REQUIRED ON THE SEAL, AND THE BUSINESS
 LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. 61G1-16.004(1)(5)
 AND FS 481.219 481.2055.
  
 2. SHT D1 DEMO REQUIREMENTS #'S 2 & 3
 DEAD ENDS ARE NOT ALLOWED. SECTION
 704.5.
  
 3. SHT D1 GREASE INTERCEPTORS SHALL BE
 PUMPED OUT AND WASHED DOWN PRIOR TO
 REMOVING.
  
 4. SHTS A1, A5.2 & A9 BREAK ROOM SINK
 SHALL BE ACCESSIBLE. PLEASE SUBMIT A
 DETAIL SHOWING THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED. NO CABINET DOORS
 ALLOWED IN CLEAR FLOOR SPACE).
 D. 11-4.24.7 FAUCETS
  
 5. SHT A5.3 DRINKING FOUNTAIN TO BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.5 CLEARANCES AND CLEAR FLOOR
 SPACE. (FORWARD APPROACH REQUIRED).
  
 6. SHT A5.2 DETAIL 1 INDICATES A SINK
 WITH AN EYEWASH STATION. MORE
 INFORMATION REQUIRED. PLEASE SUBMIT A
 DETAIL AND MANUFACTURE SPECIFICATION & INSTALLATION
 SHEETS.
  
 7. A5.3 FAMILY TOILET ROOM, (129),
 WOMENS TOILET ROOM, (130), MEN'S TOILET
 FOOM, (127). SHALL BE ACCESSIBLE. SUBMIT
 THE FOLLOWING:
 FOR W/C'S...
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 FOR STALLS....
 A. 11-4.17.3 EXCEPTION 2 THE ACCESSIBLE
 W/C SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR. (SEE MENS TOILET
 ROOM).
 FOR URINALS...
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.4 FLUSH CONTROLS
 FOR LAVS....
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 8. SHT A5.3 DETAIL 6 TOILET ELEVATION
 FOR THE ACCESSIBLE STALL DOES NOT SHOW
 THE LAV. SECTION 106.1.1.
  
 9. SHT A5.3 FAMILY TOILET, W/C TO BE 18"
 OFF THE WALL TO CENTERLINE OF THE
 FIXTURE. SEE FIG. 28.
  
 10. ALL PME & REFRIG. SHEETS. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, AND
 LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. 61G15-23.002(2) & FS 471.025
  
 11. SHT P1 GREASE INTERCEPTORS SHALL BE
 SIZED BY THE UTILITY DEPT. ENVIRONMENTAL COMPLIANCE
 MGR. PLEASE CONTACT LYNN
 MASSON, (561) 822-2271, FAX (561)
 822-2279, OR E-MAIL [email protected] FOR
 A DETERMINATION ON INTERCEPTOR SIZE.
 WASTE ORDINANCE #3434.
  
 12. SHT P1 CLEANOUTS REQUIRED PER
 SECTIONS 708.3.1, 708.3.3, & 708.3.5
 REQUIRED ON THE SANT., GREASE, AND
 CONDENSATE SYSTEMS.
  
 13. SHT P1 INDICATES REMOVAL OF ALL
 FLOOR DRAINS. IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM
 DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5.
  
 14. SHT P1 MINIMUM FACILITIES REQUIRES
 TWO DRINKING FOUNTAINS. ONLY A HI/LOW
 DRINKING FOUNTAIN IS SHOWN. IF A FIXTURE
 HAS ONLY ONE DRAIN LINE AND ONE SUPPLY
 LINE IT IS CONSIDERED ONE FIXTURE.
 PLEASE INDICATE THE LOCATION OF EWC-1 AS
 SHOWN ON SHT P4 PLUMBING FIXTURE
 SCHEDULE. TABLE 403.1.
  
 15. SHT P-3 WATER HAMMER ARRESTORS ARE
 REQUIRED AT ALL QUICK CLOSING VALVES,
 SUCH AS DISH WASHERS, ICE MAKERS, ETC.
 PLEASE SHOW ONE AT THE ICE MAKER. ALL
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES, IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN AT
 THE LAVS IN MENS AND WOMENS TOILET ROOM.
 SECTION 604.9 AND PDI-WH 201.
  
 16. SHT P3 2 WAY CLEANOUTS ARE REQUIRED
 AT THE INLET AND EXIT OF EACH GREASE
 INTERCEPTOR.
  
 17. SHT P3 THE SANT. RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN BETWEEN
 FIXTURE AND 1ST FIXTURE.
 SHOW ALL PIPE SIZES ON THE RISER
 DIAGRAM. SECTION 106.1.1 AND TABLES
 710.1(1) & 710.1(2).
  
 18. SHT P4 COFFEE BAR PLUMBING EQUIPMENT CONNECTION
 SCHEDULE CO8. SUBMIT MANUF SPECIFICATION SHEETS FOR THE
 WATER
 FILTER. FILTER SHALL COMPLY WITH NSF 42.
  
 19. SUBMIT A CONDENSATE RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES.
 SECTION 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status N Date 2008-01-11 Cont ID  
Sent By kdfreema Date 2008-01-11 Time 08:37 Rev Time 0.00
Received By kdfreema Date 2008-01-11 Time 08:37 Sent To  
Notes
2008-01-11 08:41:00***NOT REQUIRED***
  
 PROPOSED REVISIONS DO NOT IMPACT ZONING MATTERS.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-04 Cont ID  
Sent By kdfreema Date 2006-12-04 Time 09:47 Rev Time 0.00
Received By kdfreema Date 2006-12-04 Time 09:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By kdfreema Date 2006-08-04 Time 11:00 Rev Time 0.00
Received By kdfreema Date 2006-08-04 Time 11:00 Sent To  
Notes
2006-08-04 00:00:00PLANS SUBMITTED FOR PERMIT DO NOT MATCH
 PLANS APPROVED THROUGH MINOR PD
 AMENDMENT PROCESS.
  
 THE ADDITION OF CONCRETE CURBING AND
 LANDSCAPABLE AREA IN FRONT OF BALE AND
 PALLET ENCLOSURE IS REQUIRED AND SHALL
 BE PROVIDED. LANDSCAPE PLANS (SIGNED AND
 SEALED) CONSISTENT WITH THE APPROVED
 MINOR PD AMENDMENT SHALL BE PROVIDED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER AT
 561-822-1435 WITH QUESTIONS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved