| Plan Review Stops For Permit 06070674 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-10-11 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-10-11 |
Time |
15:27 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-09-21 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-09-21 |
Time |
15:12 |
Sent To |
PC |
|
| Notes |
| 2006-09-21 00:00:00 | | | | | | | DENIED | | | | | | 1) TRUSS PACKAGE IS INCOMPLETE, MISSING | | | THE INDIVIDUAL TRUSS SHEETS WITH THE | | | SIGNED AND SEALED INDEX SHEET. PLEASE BE | | | AWARE THIS CAN BE SUBMITTED TO ON SITE | | | INSPECTOR PRIOR TO TRUSS INSTALLATION | | | | | | 2) THE PRESSURES FOR COMPONENT AND | | | CLADDING ARE FOR EXPOSURE B AND THE WIND | | | DESIGN CRITERIA STATES EXPOSURE C PLEASE | | | CORRECT ONE OF THESE ITEMS | | | | | | 3) FLORIDA COVER SHEET FOR THE PROJECTED | | | WINDOWS FL#2766-R4 DOES NOT COVER | | | ATW-400 AWNING WINDOWS AND THEY ARE NOT | | | IMPACT AS STATED ON THE DRAWING PLEASE | | | SUBMITTHE CORRET PRODUCT OR IF THIS | | | AWNING IS TO BE USED SHUTTER PRODUCT | | | APPROVALS WILL BE REQUIRED | | | | | | 4) PER R311.5.4 THERE SHALL BE A LANDING | | | AT THE TOP AND BOTTOM OF EACH STAIRWAY. | | | THE WIDTH SHALL NOT BE LESS THAN THE | | | STAIRWAY BEING SERVED AND SHALL HAVE A | | | MINIMUM DIMENSION OF 36" MEASURED IN THE | | | DIRECTION OF TRAVEL | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-03 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-08-03 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-08-03 |
Time |
12:02 |
Sent To |
P |
|
| Notes |
| 2006-08-03 00:00:00 | | | | | | | DENIED | | | | | | 1) PROVIDE SURVEY TO VERIFY THE SETBACKS | | | AND DETERMINE THE FIRE RESISTANCE RATING | | | OF EXTERIOR WALLS | | | | | | 2) THE STATE OF FLORIDA REQUIRES | | | COLLECTION OF A RADON SURCHARGE ON ALL | | | NEW CONSTRUCTION COMPUTED ON UNDER ROOF | | | FLOOR SPACE PER 10D-91 FAC. THESE FEES | | | WILL BE ADDED TO THE PERMIT APPLICATION | | | FEES | | | | | | 3) THOSE PRODUCTS WHICH ARE REGULATED BY | | | DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | | | | 4) SUBMIT ENGINEERED TRUSS DRAWINGS FOR | | | FLOOR AND ROOF TRUSSES THAT COMPLY WITH | | | R802.10.1 FBC WITH PERMIT APPLICATION OR | | | BEFORE INSTALLATION THAT HAVE BEEN | | | REVIEWED AND APPROVED BY THE DESIGNER OF | | | RECORD | | | | | | 5) PROVIDE NOTE ON DRAWINGS THAT TERMITE | | | TREATMENT IS REQUIRED PER R320.1.1 - | | | R320.1.8 FBC | | | | | | 6) PROVIDE ATTIC ACCESS ON DRAWINGS PER | | | R807.1 PLEASE NOTE THAT ACCESS IS | | | REQUIRED TO BOTH SIDES OF MASTER SUITE | | | | | | 7) SHOW THAT STAIRWAY HAND RAIL WILL | | | COMPLY WITH R311.5.6.2 FBC | | | | | | 8) RECONFIGURED WINDERS SHALL COMPLY | | | WITH 1009.3 (EXCEPTION #5) FBC | | | | | | 9) SUBMIT ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND | | | DATED BY PREPARER AND OWNER/AGENT PRIOR | | | TO SUBMITTAL | | | | | | 10) VERIFY ON DRAWINGS THAT WALL AND | | | CEILING INSULATION MATCHES THEVALUES | | | STATED IN THE ENERGY CALC'S | | | | | | 111) COMPONENT AND CLADDING SCHEDULE | | | APPEARS TO BE INCORRECT PLEASE VERIFY AS | | | ALL ZONES HAVE THE SAME PRESSURES | | | | | | 12) THE PERMIT APPLICATION SHALL INCLUDE | | | TWO COPIES OF EACH PRODUCT APPROVAL THAT | | | IS RELEVANT PER 9B-72. THESE SHOULD | | | INCLUDE THE FLORIDA STATE APPROVAL COVER | | | PAGES, AND THE PRODUCT NOA THAT LISTS | | | THE SYSTEM COMPONENTS/ FASTENER LIST | | | PAGES, THE PAGES WITH THE CHOSEN | | | ASSEMBLY/ SYSTEM TO BE USED AND THE | | | GENERAL LIMITATIONS PAGE. ALL CAN BE | | | FOUND ON WWW.FLORIDABUILDING.ORG | | | | | | ********NOTE******* | | | A) PROVIDE PRODUCT APPROVALS FOR ROOF | | | COVERING | | | B) PRODUCT APPROVAL FOR FRENCH DOORS ARE | | | HILIGHTED FOR IMPACT BUT THE NOA IS FOR | | | NON-IMPACT | | | C) PRODUCT APPROVALS WERE SUBMITTED FOR | | | CASEMENT, NONE ARE SPECIFIED ON THE | | | DRAWING. WINDOW TYPE #3 IS AWNING AND NO | | | PRODUCT APPROVAL WAS SUBMITTED | | | D) PRODUCT APPROVAL FOR SINGLE HUNG | | | WINDOWS HAVE BEEN REVISED 239-R4 AND A | | | NEW NOA IS REQUIRED # 05-1018.01 PLEASE | | | NOTE THAT THIS WINDOW REPLACES THE OLD | | | 701 SERIES | | | E) THE SIMPSON TIE INDEX MAY BE | | | SUBMITTED FOR WOOD CONNECTORS (IT IS | | | ONLY 12 PAGES AND CONTAINS ALL FLORIDA | | | APPROVED CONNECTORS AND THEIR FL#S) | | | PLEASE SEE THE ATTACHED SHEET WITH | | | INSTRUCTION TO RETREIVE INDEX ONLINE | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-03 |
Time |
10:12 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-04-03 |
Time |
09:54 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-23 |
Time |
16:35 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-03-23 |
Time |
16:35 |
Sent To |
M |
|
| Notes |
| 2007-03-27 10:08:58 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | THE LICENSE NUMBER AT THE SEAL IS INCORRECT FOR THE | | | ENGINEER OF RECORD. 471 FS. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-02 |
Time |
06:47 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-01 |
Time |
17:26 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-03-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-19 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-19 |
Time |
10:28 |
Sent To |
E |
|
| Notes |
| 2007-03-19 10:29:10 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-14 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-14 |
Time |
09:37 |
Sent To |
M |
|
| Notes |
| 2007-02-14 09:37:54 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-30 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-30 |
Time |
13:45 |
Sent To |
B |
|
| Notes |
| 2006-11-30 13:45:45 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-11 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-11 |
Time |
11:20 |
Sent To |
B |
|
| Notes |
| 2006-10-11 11:21:39 | TO "AMORSE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-18 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-18 |
Time |
09:42 |
Sent To |
B |
|
| Notes |
| 2006-09-18 00:00:00 | TO "AMORSE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-11 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-11 |
Time |
10:47 |
Sent To |
Z |
|
| Notes |
| 2006-09-11 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-31 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-31 |
Time |
10:53 |
Sent To |
E |
|
| Notes |
| 2006-07-31 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-07 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-20 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | TO "Z" BOX-PLANS ROUTED TO INCOMING ON | | | 7/18/06 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-29 |
Time |
16:32 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-03-29 |
Time |
16:32 |
Sent To |
E |
|
| Notes |
| 2007-03-29 16:33:04 | REVISION TO MECH. PLANS PAGE M-1. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-27 |
Time |
10:09 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-03-26 |
Time |
14:12 |
Sent To |
E |
|
| Notes |
| 2007-03-26 14:19:32 | ** MECHANICAL REVISION PAGE M-1 ** | | | *** DENIED *** | | | 1) SEE MECHANICAL PLAN PAGE M-1 TITLE BLOCK WERE | | | ENGINEER SEALED PLANS PRINTED LICENSE # 51482 IS NOT | | | JOHN SYLVIA'S LICENSE NUMBER, PLEASE CORRECT. | | | | | | 2) ENGINEERJOHN SYLVIA'S LICENSE EXPIRED 2-28-07, | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-02-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-16 |
Time |
16:14 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-02-16 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2007-02-16 16:37:19 | * MECHANICAL REVISION * | | | *** DENIED *** | | | 1) MECHANICAL PLANS ON FILE WERE SEALED BY AN ENGINEER | | | ( JOHN SYLVIA ) AND ONLY HE CAN MAKE REVISIONS TO THE | | | PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-20 |
Time |
09:46 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-09-20 |
Time |
09:46 |
Sent To |
B |
|
| Notes |
| 2006-09-20 00:00:00 | RETURNED TO LUIS M. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-02 |
Time |
14:39 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-08-02 |
Time |
14:39 |
Sent To |
P |
|
| Notes |
| 2006-08-02 00:00:00 | *** DENIED *** | | | 1) SEE ENERGY CALCULATIONS #6 SHOWS | | | CONDITIONED FLOOR AREA AS 2176.8 SQ. | | | FT., NEED TO SHOW ADDITION SQ. FT. ONLY, | | | NOT WHOLE HOUSE. #11 SHOWS DUCT LOCATION | | | IN CONDITIONED AREA, DUCT WORK IS IN THE | | | ATTIC AND IN A NON-CONDITIONED SPACE, | | | AND DUCT R VALUE IS 4.2, DUCTS IN THE | | | ATTIC NEED TO BE R-6. PLEASE CORRECT THE | | | ABOVE. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2 | | | | | | 3) SHOW SEER OF A/C SYSTEM ON MECHANICAL | | | PLANS EQUIPMENT SCHEDULE. | | | | | | 4) MECHANICAL PLANS SHOW FS (FIRE STAT) | | | AT AIR HANDLER, PLEASE EXPLAIN WHAT FIRE | | | STAT IS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-08-07 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-08-07 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-09-19 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-09-19 |
Time |
15:18 |
Sent To |
M |
|
| Notes |
| 2006-09-19 00:00:00 | SEE PLANS FOR ZONING APPROVAL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-29 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-29 |
Time |
06:57 |
Sent To |
I |
|
| Notes |
| 2006-07-29 00:00:00 | DENIED, | | | 1. PLEASE SUBMIT A COPY OF THE CURRENT | | | SURVEY. | | | 2. PLEASE PROVIDE THE DIMENSION OF THE | | | DRIVEWAY/WALKWAY (WIDTH & LENGTH) OF | | | PROPOSED (IF APPLICABLE) & EXISTING | | | DRIVEWAY & WALKWAY. | | | | | | NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF | | | LANDSCAPE, WHICHEVER IS LESS WITHIN THE | | | FIRST 25FT FRONT SETBACK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|