Plan Review Details - Permit 06070674
Plan Review Stops For Permit 06070674
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-11 Cont ID  
Sent By amorse Date 2006-10-11 Time 15:27 Rev Time 0.00
Received By amorse Date 2006-10-11 Time 15:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-21 Cont ID  
Sent By amorse Date 2006-09-21 Time 15:12 Rev Time 0.00
Received By amorse Date 2006-09-21 Time 15:12 Sent To PC
Notes
2006-09-21 00:00:00 
  
 DENIED
  
 1) TRUSS PACKAGE IS INCOMPLETE, MISSING
 THE INDIVIDUAL TRUSS SHEETS WITH THE
 SIGNED AND SEALED INDEX SHEET. PLEASE BE
 AWARE THIS CAN BE SUBMITTED TO ON SITE
 INSPECTOR PRIOR TO TRUSS INSTALLATION
  
 2) THE PRESSURES FOR COMPONENT AND
 CLADDING ARE FOR EXPOSURE B AND THE WIND
 DESIGN CRITERIA STATES EXPOSURE C PLEASE
 CORRECT ONE OF THESE ITEMS
  
 3) FLORIDA COVER SHEET FOR THE PROJECTED
 WINDOWS FL#2766-R4 DOES NOT COVER
 ATW-400 AWNING WINDOWS AND THEY ARE NOT
 IMPACT AS STATED ON THE DRAWING PLEASE
 SUBMITTHE CORRET PRODUCT OR IF THIS
 AWNING IS TO BE USED SHUTTER PRODUCT
 APPROVALS WILL BE REQUIRED
  
 4) PER R311.5.4 THERE SHALL BE A LANDING
 AT THE TOP AND BOTTOM OF EACH STAIRWAY.
 THE WIDTH SHALL NOT BE LESS THAN THE
 STAIRWAY BEING SERVED AND SHALL HAVE A
 MINIMUM DIMENSION OF 36" MEASURED IN THE
 DIRECTION OF TRAVEL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-03 Cont ID  
Sent By amorse Date 2006-08-03 Time 15:14 Rev Time 0.00
Received By amorse Date 2006-08-03 Time 12:02 Sent To P
Notes
2006-08-03 00:00:00 
  
 DENIED
  
 1) PROVIDE SURVEY TO VERIFY THE SETBACKS
 AND DETERMINE THE FIRE RESISTANCE RATING
 OF EXTERIOR WALLS
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 4) SUBMIT ENGINEERED TRUSS DRAWINGS FOR
 FLOOR AND ROOF TRUSSES THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD
  
 5) PROVIDE NOTE ON DRAWINGS THAT TERMITE
 TREATMENT IS REQUIRED PER R320.1.1 -
 R320.1.8 FBC
  
 6) PROVIDE ATTIC ACCESS ON DRAWINGS PER
 R807.1 PLEASE NOTE THAT ACCESS IS
 REQUIRED TO BOTH SIDES OF MASTER SUITE
  
 7) SHOW THAT STAIRWAY HAND RAIL WILL
 COMPLY WITH R311.5.6.2 FBC
  
 8) RECONFIGURED WINDERS SHALL COMPLY
 WITH 1009.3 (EXCEPTION #5) FBC
  
 9) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 10) VERIFY ON DRAWINGS THAT WALL AND
 CEILING INSULATION MATCHES THEVALUES
 STATED IN THE ENERGY CALC'S
  
 111) COMPONENT AND CLADDING SCHEDULE
 APPEARS TO BE INCORRECT PLEASE VERIFY AS
 ALL ZONES HAVE THE SAME PRESSURES
  
 12) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ********NOTE*******
 A) PROVIDE PRODUCT APPROVALS FOR ROOF
 COVERING
 B) PRODUCT APPROVAL FOR FRENCH DOORS ARE
 HILIGHTED FOR IMPACT BUT THE NOA IS FOR
 NON-IMPACT
 C) PRODUCT APPROVALS WERE SUBMITTED FOR
 CASEMENT, NONE ARE SPECIFIED ON THE
 DRAWING. WINDOW TYPE #3 IS AWNING AND NO
 PRODUCT APPROVAL WAS SUBMITTED
 D) PRODUCT APPROVAL FOR SINGLE HUNG
 WINDOWS HAVE BEEN REVISED 239-R4 AND A
 NEW NOA IS REQUIRED # 05-1018.01 PLEASE
 NOTE THAT THIS WINDOW REPLACES THE OLD
 701 SERIES
 E) THE SIMPSON TIE INDEX MAY BE
 SUBMITTED FOR WOOD CONNECTORS (IT IS
 ONLY 12 PAGES AND CONTAINS ALL FLORIDA
 APPROVED CONNECTORS AND THEIR FL#S)
 PLEASE SEE THE ATTACHED SHEET WITH
 INSTRUCTION TO RETREIVE INDEX ONLINE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 10:12 Rev Time 0.50
Received By btrobaug Date 2007-04-03 Time 09:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-27 Cont ID  
Sent By btrobaug Date 2007-03-23 Time 16:35 Rev Time 0.50
Received By btrobaug Date 2007-03-23 Time 16:35 Sent To M
Notes
2007-03-27 10:08:58 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE LICENSE NUMBER AT THE SEAL IS INCORRECT FOR THE
 ENGINEER OF RECORD. 471 FS.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-08-02 Cont ID  
Sent By btrobaug Date 2006-08-02 Time 06:47 Rev Time 0.50
Received By btrobaug Date 2006-08-01 Time 17:26 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 10:28 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 10:28 Sent To E
Notes
2007-03-19 10:29:10TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 09:45 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 09:37 Sent To M
Notes
2007-02-14 09:37:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 13:45 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 13:45 Sent To B
Notes
2006-11-30 13:45:45TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 11:20 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 11:20 Sent To B
Notes
2006-10-11 11:21:39TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 09:42 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 09:42 Sent To B
Notes
2006-09-18 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 10:47 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 10:47 Sent To Z
Notes
2006-09-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 10:53 Sent To E
Notes
2006-07-31 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-08-07 Time 10:38 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 18:40 Sent To  
Notes
2006-07-20 00:00:00TO "Z" BOX-PLANS ROUTED TO INCOMING ON
 7/18/06

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 16:32 Rev Time 0.25
Received By tgordon Date 2007-03-29 Time 16:32 Sent To E
Notes
2007-03-29 16:33:04REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-03-26 Cont ID  
Sent By btrobaug Date 2007-03-27 Time 10:09 Rev Time 0.25
Received By tgordon Date 2007-03-26 Time 14:12 Sent To E
Notes
2007-03-26 14:19:32** MECHANICAL REVISION PAGE M-1 **
 *** DENIED ***
 1) SEE MECHANICAL PLAN PAGE M-1 TITLE BLOCK WERE
 ENGINEER SEALED PLANS PRINTED LICENSE # 51482 IS NOT
 JOHN SYLVIA'S LICENSE NUMBER, PLEASE CORRECT.
  
 2) ENGINEERJOHN SYLVIA'S LICENSE EXPIRED 2-28-07,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-16 Cont ID  
Sent By tgordon Date 2007-02-16 Time 16:14 Rev Time 0.30
Received By tgordon Date 2007-02-16 Time 16:14 Sent To  
Notes
2007-02-16 16:37:19* MECHANICAL REVISION *
 *** DENIED ***
 1) MECHANICAL PLANS ON FILE WERE SEALED BY AN ENGINEER
 ( JOHN SYLVIA ) AND ONLY HE CAN MAKE REVISIONS TO THE
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 09:46 Rev Time 0.25
Received By tgordon Date 2006-09-20 Time 09:46 Sent To B
Notes
2006-09-20 00:00:00RETURNED TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-02 Cont ID  
Sent By tgordon Date 2006-08-02 Time 14:39 Rev Time 0.30
Received By tgordon Date 2006-08-02 Time 14:39 Sent To P
Notes
2006-08-02 00:00:00*** DENIED ***
 1) SEE ENERGY CALCULATIONS #6 SHOWS
 CONDITIONED FLOOR AREA AS 2176.8 SQ.
 FT., NEED TO SHOW ADDITION SQ. FT. ONLY,
 NOT WHOLE HOUSE. #11 SHOWS DUCT LOCATION
 IN CONDITIONED AREA, DUCT WORK IS IN THE
 ATTIC AND IN A NON-CONDITIONED SPACE,
 AND DUCT R VALUE IS 4.2, DUCTS IN THE
 ATTIC NEED TO BE R-6. PLEASE CORRECT THE
 ABOVE.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2
  
 3) SHOW SEER OF A/C SYSTEM ON MECHANICAL
 PLANS EQUIPMENT SCHEDULE.
  
 4) MECHANICAL PLANS SHOW FS (FIRE STAT)
 AT AIR HANDLER, PLEASE EXPLAIN WHAT FIRE
 STAT IS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-07 Cont ID  
Sent By jleech Date 2006-08-07 Time 10:34 Rev Time 0.00
Received By jleech Date 2006-08-07 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By lmartine Date 2006-09-19 Time 15:19 Rev Time 0.00
Received By lmartine Date 2006-09-19 Time 15:18 Sent To M
Notes
2006-09-19 00:00:00SEE PLANS FOR ZONING APPROVAL

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-29 Cont ID  
Sent By mmclean Date 2006-07-29 Time 06:57 Rev Time 0.00
Received By mmclean Date 2006-07-29 Time 06:57 Sent To I
Notes
2006-07-29 00:00:00DENIED,
 1. PLEASE SUBMIT A COPY OF THE CURRENT
 SURVEY.
 2. PLEASE PROVIDE THE DIMENSION OF THE
 DRIVEWAY/WALKWAY (WIDTH & LENGTH) OF
 PROPOSED (IF APPLICABLE) & EXISTING
 DRIVEWAY & WALKWAY.
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720