Plan Review Details - Permit 06070671
Plan Review Stops For Permit 06070671
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-25 Cont ID  
Sent By alange Date 2006-08-24 Time 16:28 Rev Time 0.00
Received By alange Date 2006-08-24 Time 16:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 08:21 Rev Time 0.00
Received By alange Date 2006-07-25 Time 08:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 20:23 Sent To  
Notes
2006-08-16 00:00:00REDLINED PLANS.
 BOX, FEEDERS ETC ABOVE CEILING SHALL BE
 LABLED AND IDENTIFIED FOR FEEDERS/BOX ,
 CIRCUIT AND PANEL LOCATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 18:25 Sent To  
Notes
2006-07-18 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 A CLEAR AND VISABLE SEAL WITH ALL
 INFORMATION AS REQUIRED ON SAID SEAL.
 PLEASE SEE FAC 61G15-23.001,.002 AND FS
 471.025
 ** PLEASE KNOW, THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE PLAN NOTES MENTIONS
 THE COMPLETE REMOVAL OF PANEL "J",
 WIRING , CONDUIT ETC AND TERMINATE
 FEEDERS INTO A J-BOX IN CEILING AREA
 WITH TAPS, LABELING ETC, HOWEVER PLEASE
 SEE NEW RECEPTS SHOWN INDICATE THE
 CIRCUITING TO THIS PANEL WHICH IS BEING
 REMOVED??
 HOW IS THIS POSSIBLE OR IS THERE ANOTHER
 PANEL "J"??
 PLEASE CORRELATE AND REVISE AS NEEDED.
  
 3) NOTE: PLEASE SEE THAT THE FOLLOWING
 CODES AT A MIN SHALL BE INDICATED ON
 PLANS.
 2004 FBC, NFPA-70 2002
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By mawillia Date 2006-08-24 Time 14:12 Rev Time 0.00
Received By mawillia Date 2006-08-24 Time 14:12 Sent To  
Notes
2006-08-24 00:00:00**APPROVED**
  
  
  
  
  
 1.)STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.)ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL, DUST AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING ALTERATION.
  
 4.)PROVIDE SEPARATE PERMIT AND SHOP
 DRAWINGS/PLANS FOR SPRINKLER REMODEL.
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By mwennerg Date 2006-07-19 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2006-07-19 Time 13:46 Sent To  
Notes
2006-07-19 00:00:00***DENIED***
  
 PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING CLARITY AND VISIBILITY
 REQUIREMENTS FOR ENGINEER'S SEAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 14:42 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 14:42 Sent To  
Notes
2006-08-16 00:00:00TO "BOB"#11
2006-08-10 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 08:23 Rev Time 0.00
Received By alange Date 2006-07-13 Time 16:02 Sent To  
Notes
2006-07-18 00:00:00TO "BOB"#18
2006-07-13 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 13:49 Rev Time 0.15
Received By tgordon Date 2006-08-17 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By tgordon Date 2006-07-18 Time 14:14 Rev Time 0.25
Received By tgordon Date 2006-07-18 Time 14:13 Sent To  
Notes
2006-07-18 00:00:00*** DENIED ***
 1) ENGINEER'S SEAL IMPRESSION IS NOT
 VISIBLE NOR LEGIBLE, PLEASE HAVE
 ENGINEER RE-SEAL PLANS (CHECK ALL PAGES
 FOR SEAL).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  