| 2006-07-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- FLAT ROOF SYSTEM: A) DADE COUNTY NOA |
| | 03-0430.13 PACKAGE SUBMITTED SHOWS |
| | SELECTED APPROVED ASSEMBLY ON PAGE 27 |
| | FOR CONCRETE DECK, NON INSULATED |
| | ASSEMBLY. BUT, THERE IS ADDITIONAL |
| | INFORMATION SUBMITTED FOR INSULATION. |
| | NEED TO BE SPECIFIC ON WHICH ASSEMBLY IS |
| | GOING TO BE INSTALLED. INSULATED OR |
| | NON-INSULATED IN ORDER TO CHECK |
| | COMPLIANCE WITH GENERAL LIMITATION #7 OR |
| | #9 ON LAST PAGE OF NOA. SEE ATTACHED |
| | COPY OF CITY POLICY FOR RE-ROOFS PERMITS |
| | FOR REQUIRED INFORMATION TO BE |
| | SUBMITTED. |
| | B) PROVIDE COPY OF COVER PAGE OF |
| | FLORIDA PRODUCT APPROVAL FL-617 WHICH IS |
| | THE ONE THAT MATCHES THIS NOA. |
| | C) IF SELECTING AN INSULATED ASSEMBLY, |
| | THEN CLEARLY MARK WHICH INSULATION |
| | ASSEMBLY IS GOING TO BE INSTALLED. |
| | |
| | 2- DADE COUNTY NOA 01-1226.03 FOR ELK |
| | PRESTIQUE SHINGLES IS EXPIRED. PROVIDE |
| | CURRENT NOA. |
| | |
| | 3- NOTICE OF COMMENCEMENT IS EXPIRED |
| | AFTER 90 DAYS IF WORK IS NOT STARTED. |
| | SEE FLORIDA STATUTES SEC. 713.13(2). |
| | NEED RE-RECORDED N.O.C. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |