Plan Review Details - Permit 06070594
Plan Review Stops For Permit 06070594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-06 Cont ID  
Sent By amorse Date 2007-04-06 Time 06:56 Rev Time 0.00
Received By amorse Date 2007-04-06 Time 06:56 Sent To PC
Notes
2007-04-06 07:55:32 
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE
 FIRST REVIEW
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 10) PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1
 PROVIDE DRAINAGE AWAY FROM BUILDING AND ADJACENT
 PROPERTY.
 *****************************************************
  
 1)SECTION B/A2 SHEATHING SHALL BE FASTENED PER THE
 FBC AND PLYWOOD NAILING DETAIL ON S2
  
 2)THE FOLLOWING PRODUCT APPROVAL COMMENTS REQUIRE
 REVISION
  
 A)MARVIN DOORS REQUIRE THE CORRECT FLORIDA COVER
 SHEETS (FL#6536)
 B)MARVIN FIXED WINDOWS REQUIRE BOTH CORRECT FLORIDA
 COVER SHEET (FL#7151) AND REVISED MIAMI-DADE NOA
 (05-0815.08)
 C)THE FIRESTONE MODIFIED ROOFING PRODUCT APPROVAL IS
 INCOMPLETE THE MIAMI-DADE NOA IS MISSING INFORMATION
 DUE TO THE REPRINTED SIZE THAT CUTS OFF THE BOTTOM OF
 THE PAGE. ALSO THE FIRST 5 PAGES WITH THE MATERIAL LIST
 AS WELL AS THE SYSTEM USED AND THE LIMITATIONS PAGE ARE
 ALL REQUIRED AS PART OF THE PRODUCT APPROVAL THAT WAS
 SUBMITTED.
  
 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004. PHOTO COPIED, STAMPED OR
 REPRODUCED
 SIGNATURES ARE NOT ACCEPTABLE PER
 471.025 F.S.
  
 4)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC.COVENANT ENGINEERING IS A
 BUSINESS AND AS SUCH REQUIRES A CERTIFICATE OF
 AUTHORIZATION NUMBER, PLEASE PROVIDE IN TITLE BLOCK.
  
 5)ENERGY CALC'S DO NOT MATCH THE INSULATION TYPES ON
 THE ARCHITECTURAL DRAWINGS PLEASE VERIFY AND MAKE
 CORRECTIONS TO EITHER THE ENERGY CALC'S OR THE
 DRAWINGS.
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 09:18 Rev Time 0.00
Received By alange Date 2006-07-31 Time 09:18 Sent To  
Notes
2006-07-31 00:00:00 
 DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 3.ROOF SHEATHIN ON A-2 SHALL COMPLY
 WITH 2304.9.1 #31
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.FOOTING DEPTH SHALL COMPLY WITH
 R403.1.2 12" DEEP
  
 6.FOOTING WITH SHALL BE PER SOIL
 ENGINEERING REPORT RECOMMENDATIONS.
  
 7.MODIFIED BITUMEN PRODUCT APPROVALS
 SUBMITTED WITH QUALITY ASSURANCE SHALL
 HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 8.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 9.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-18 Cont ID  
Sent By dpalmer Date 2007-01-18 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2007-01-17 Time 07:47 Sent To M
Notes
2007-01-18 16:18:09** UNSAT2ND REVIEW **
  
 ** THIS IS THE FIRST SET OF ELECTRICAL PLANS BEING
 SUBMITTED FOR REVIEW. THE FIRST SET OF PLANS SUBMITTED
 DID NOT CONTAIN ELECTRICAL PLANS NEEDED.
  
 1) NOTE: PLEASE SEE MEP SHEETS WHICH CONTAIN A TITLE
 BLOCK FOR AN ENGINEERING FIRM WHICH DOES NOT CONTAIN A
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER
 THE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, AND
 FLORIDA STATUES 471.023.
 PLEASE SEE THE USE OF PROTECTED WORDS IS PROHIBITED
 UNLESS OBTAINING THE PROPER LICENSING THROUGH THE
 STATE.
 THIS COMMENT HAS BEEN MADE ON SEVERAL OTHER PROJECTS TO
 THIS COMPANY AND PLANS ARE BEING RETAINED BY THIS
 OFFICE.
 ANY FURTHER QUESTIONS ON THIS MATTER SHALL BE MADE TO
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 2) NOTE: PLEASE SEE THE "S" SHEETS WHICH CONTAIN A
 "RUBBER-STAMP" BY THE ENGINEER FOR THE REQUIRED
 ORIGINAL SIGNATURE. PLEASE SEE FLORIDA STATUES 471.025
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 ONE SET OF THESE PLANS ARE ALSO BEING RETAINED BY THIS
 OFFICE.
 ANY FURTHER QUESTIONS ON THIS SHALL BE MADE TO THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM FOR
 SERVICE IS INCOMPLETE AT THIS TIME.
 PLEASE SEE THE RISER SHOWS AN ADDITIONAL EXISTING MAIN
 BREAKER PANEL WHICH A PANEL SCHEDULE WAS NOT SUBMITTED
 FOR? PLEASE SEE NO OVER CURRENT PROTECTION IS BEING
 SHOWN FOR THIS NEW FEEDER TO THE PANEL "B" WHICH IS
 SHOWN ON RISER.
 PLEASE COMPLETE.
 310.16, 240.4, 240.24
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE MISSING THE REQUIRED FOOTER STEEL
 AT THE NEW DETACHED BUILDING AS REQUIRED PER 250.32,
 250.50
  
 5) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 2FT,
 6FT AND 12FT RULE.
  
 6) NOTE: PLEASE SEE MISSING THE REQUIRED LOADS FOR
 CIRCUITS FOR KITCHENS AND AREAS OF THE LIKE AS REQUIRED
 PER 210.52B1, 210.11C1, 220.52
  
 7) NOTE: PLEASE SUBMIT LOAD CALCULATIONS PER 220.83(A)
 AND (B).
 PLEASE INDICATE A LOAD SUMMARY WHICH CORRELATES WITH
 THE PLANS AND PANEL SCHEDULE(S). PLEASE SEE SMALL
 APPLIANCE CIRCUITS, WASHER/LAUNDRY ETC SHALL BE SHOWN
 AND COORDINATED WITH THE PANEL LOADS AS SHOWN.
  
 8) NOTE: PLEASE VERIFY AND CORRELATE THE NEW AHU HEAT
 LOAD AND OVER CURRENT PROTECTION WITH THE MECHANICAL
 PLANS. PLEASE SEE THE LOADS SHOWN FOR THE A/C LOADS ON
 LOAD CALCULATIONS DO NOT CORRELATE WITH THAT OF THE
 LOADS SHOWN ON THE PANEL SCHEDULE?
 PLEASE SEE 220.83(B) AND 220.60
  
 9) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES
 REQUIRED FOR ELECTRICAL PANELS. AS THE PLANS INDICATE A
 1/4INCH SCALE, THE ROOM WHERE THE PANEL IS LOCATED IS
 NOT LARGE ENOUGH.
  
 10) NOTE: PLEASE CORRELATE RISER, PANEL AND PLANS.
 PLEASE SEE THE NEW PANEL B IS BEING SHOWN WITH OUT ANY
 MAIN BREAKER OR DISCONNECTING MEANS AS REQUIRED PER
 225.31. PLEASE SEE PLANS HOWEVER SEEM TO SHOW SOME SORT
 OF DISCONNECT HOWEVER RISER DOES NOT SHOW ANY
 DISCONNECT.
 PLEASE CORRELATE THESE.
  
 11) NOTE: PLEASE SEE 210.8A6 AND 7 AS MISSING GFI
 DESIGNATION ON PLANS FOR AREAS AS STATED IN THESE
 SECTIONS.
  
 12) NOTE: PLEASE SEE PLANS SHALL STATE THE CODE IN
 WHICH THE DESIGN IS UNDER. PLEASE SEE THE PLANS SHALL
 STATE FOLLOWING AT A MINIMUM.
 2002 NFPA-70 (NEC).
 2002 NFPA-72
  
 13) NOTE: PLEASE 2002 NEC 210.12AS AFCI PROTECTION IS
 REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS.
 (ALL).
 PLEASE SEE MISSING PROTECTION FOR SOME AS NOTED ON
 PANEL SCHEDULE.
  
 14) NOTE: PLEASE SEE ZONING REVIEW COMMENTS AS THEY
 WILL AFFECT THE ELECTRICAL PLANS AND PERHAPS OTHER
 TRADES FOR ANY LAYOUT CHANGES ETC.
  
 15) NOTE: PLEASE SEE PLANS INDICATE A 220V RECEPTACLE
 FOR THE WATER HEATER CONNECTION HOWEVER AS REQUIRED PER
 422.30, 422.31 THIS IS REQUIRED TO BE HARDWIRED. MAY
 NOT BE CORD AND PLUG CONNECTED.
  
 16) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASEKNOW THAT BASED ON THE PLANS SUBMITTED AND
 SOME INFORMATION WHICH WAS NOT SUBMITTED WHICH IS
 NEEDED FOR PLAN REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH MAY NOT HAVE BEEN MADE ON THIS
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-22 Cont ID  
Sent By dpalmer Date 2006-07-22 Time 11:23 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 20:02 Sent To M
Notes
2006-07-22 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE SUBMIT COMPLETED
 ELECTRICLA PLANS FOR REVIEW.
 PLEASE SEE 2002 NFPA-70 (NEC) AND PLEASE
 SEE 2002 NFPA-72 .
 PLEASE SUBMIT RISER, PANEL SCHEDULES,
 MIN CIRCUITS, CONDUCTOR SIZES,
 GROUNDING, OVER CURRENT PROTECTION,
 SD'S, LIGHTING AND CONTROLS, DEDICATED
 CIRCUITS REQUIRED, A/C'S , DISCONNECTS,
 RECEPTS SPACING, EGRESS LIGHTING AND
 CONTROLS, LOAD CALCULATIONS ETC ETC.
 PLEASE KNOW, DUR TO NO ELECTRICAL PLANS
 SUBMITTED AT THIS TIME FOR REVIEW,
 COMMENTS MAY FOLLOWING ONCE PLANS ARE
 SUBMITTED.
 PLEASE SEE 2002 NEC , ALL CHAPTERS,
 ALONG WITH FBC 2004, AND NFPA-72.
  
 106.1.2, 106.1.3, 106.3.5.4 FBC ADMIN
 SECT AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-16 Cont ID  
Sent By adarroug Date 2007-01-16 Time 17:15 Rev Time 0.00
Received By adarroug Date 2007-01-16 Time 17:15 Sent To E
Notes
2007-01-16 17:16:31TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 15:17 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 15:17 Sent To Z
Notes
2006-12-28 15:17:57TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 18:23 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 18:23 Sent To E
Notes
2006-07-20 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 09:59 Rev Time 0.00
Received By alange Date 2006-07-13 Time 10:31 Sent To  
Notes
2006-07-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-19 Cont ID  
Sent By tgordon Date 2007-01-19 Time 09:25 Rev Time 0.45
Received By tgordon Date 2007-01-19 Time 09:25 Sent To P
Notes
2007-01-19 09:30:07*** DENIED ***
 1) COULD NOT FIND THE A/C SYSTEM LISTED ON PLANS IN THE
 ARI DIRECTORY, PLEASE CORRECT MODEL NUMBERS OR SUBMIT
 MANUFACTURER'S SPECIFICATION'S FOR A/C SYSTEM.
  
 2) ENERGY CALCULATIONS ARE SHOWING A HEAT RECOVERY UNIT
 FOR A CONSERVATION CREDIT, PLEASE SHOW THE HEAT
 RECOVERY UNIT ON THE MECHANICAL PLANS ANDPLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S FOR HEAT
 RECOVERY UNIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 16:34 Rev Time 0.25
Received By tgordon Date 2006-07-24 Time 16:34 Sent To B
Notes
2006-07-24 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06070596 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 2) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 3) NEW ENERGY CALCULATIONS WILL NEED TO
 BE SIGNED BY OWNER/AGENT ALSO, PER 2004
 FBC 13-600.3.ABC.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-01 Cont ID  
Sent By jleech Date 2007-02-01 Time 09:04 Rev Time 0.00
Received By jleech Date 2007-02-01 Time 09:04 Sent To B
Notes
2007-02-01 09:23:27DENIED;
  
 1. SEE NOTES ONE AND TWO ON ELECTRICAL PLAN REVIEW
 COMMENT SHEET.
 2. SECONDARY DRAIN PROTECTION NOT SHOWN ON PLANS AS
 REQUIRED BY SECTION 1107 OF THE PLUMBING CODE.
 3. WATER RISER DIAGRAM; WATER HAMMER ARRESTORS ARE NOT
 SHOWN WERE REQUIRED. SEE SECTION 604.9 ICEMAKERS.
 4. PER. TABLE 403.1 AUTOMATIC CLOTHES WASHING
 CONNECTION S ARE REQUIRED OR A CENTRAL WASHER IS
 REQUIRED SHOW HOW THIS WILL BE DONE.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-22 Cont ID  
Sent By jleech Date 2006-07-22 Time 13:02 Rev Time 0.00
Received By jleech Date 2006-07-22 Time 13:02 Sent To M
Notes
2006-07-22 00:00:00DENIED;
 1.SIZE ROOF SCUPPERS AND RAIN LEADERS
 PER FBC-2004 PLUMBING CHAPTER 11. ALSO
 SHOW SECONDARY DRAIN PROTECTION
 SEC.1107.
 2.RAIN WATER LEADERS SHALL DISCHARGE A
 MINUUM OF 12" FROM BUILDING.
 3.SANITARY RISER DIAGRAM IS REQUIRED PER
 FBC-2004 CHAPTER 1 SEC.106.3.5.4(9).
 4. PLANS MUST PASS ZONONG BEFORE
 PLUMBING CAN BE APPROVED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-11 Cont ID  
Sent By mmclean Date 2007-01-11 Time 14:49 Rev Time 0.00
Received By mmclean Date 2007-01-11 Time 14:49 Sent To I
Notes
2007-01-11 15:04:47DENIED,
 1.THE PROPOSED LOCATION OF THE A/C UNIT WILL NOT MEET
 THE REQUIRED SETBACK. WILL NEED TO MOVE THE LOCATION
 AND THE REQUIREMENT WILL BE THAT THE PROPOSED A/C SHALL
 NOT BE CLOSER THAN 10.2FT FROM REAR AND 1FT FROM SIDE
 PROPERTY LINE. (BASE ON THE PROPOSED LOCATION).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By mmclean Date 2006-07-20 Time 10:45 Rev Time 0.00
Received By mmclean Date 2006-07-20 Time 08:29 Sent To I
Notes
2006-07-20 00:00:00DENIED,
 1. THE PROPOSED STRUCTURE DOES NOT MEET
 THE REQUIREMENTS OF A CABANA. SEC 94-611
 (DEFINITION) CABANA MEAN AN ACCESSORY
 BUILDING OR PORTION OF THE MAIN BUILDING
 USED AS A BATHHOUSE OR A DRESSING AREA
 NOT CONTAINING A KITCHEN IN CONNECTION
 WITH A SWIMMING POOL OR A TENNIS COURT.
 2. MUST HAVE INTERIOR ACCESSORY WITHIN
 THE 2 STORY STRUCTURE.
 3. THE PROPOSED SQUARE FOOTAGE OF THE
 PROPOSED CABANA IS OVER THE 1000SQ FT.
 COVERED PATIO IS INCLUDED IN THE SQUARE
 FOOTAGE SEC 94-304(1)
 4. NEED TO PROVIDE ELECTRICAL PLANS,
 PLUMBING & MECHANICAL PLANS.
 5. PLEASE SHOW THE LOCATION OF A/C UNIT
 ON THE SITEPLAN.
 6. PLEASE PROVIDE THE DISTANCE OF THE
 PROPOSED STRUCTURE FROM THE MAIN HOUSE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720