| 2007-01-18 16:18:09 | ** UNSAT2ND REVIEW ** |
| | |
| | ** THIS IS THE FIRST SET OF ELECTRICAL PLANS BEING |
| | SUBMITTED FOR REVIEW. THE FIRST SET OF PLANS SUBMITTED |
| | DID NOT CONTAIN ELECTRICAL PLANS NEEDED. |
| | |
| | 1) NOTE: PLEASE SEE MEP SHEETS WHICH CONTAIN A TITLE |
| | BLOCK FOR AN ENGINEERING FIRM WHICH DOES NOT CONTAIN A |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER |
| | THE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, AND |
| | FLORIDA STATUES 471.023. |
| | PLEASE SEE THE USE OF PROTECTED WORDS IS PROHIBITED |
| | UNLESS OBTAINING THE PROPER LICENSING THROUGH THE |
| | STATE. |
| | THIS COMMENT HAS BEEN MADE ON SEVERAL OTHER PROJECTS TO |
| | THIS COMPANY AND PLANS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | ANY FURTHER QUESTIONS ON THIS MATTER SHALL BE MADE TO |
| | THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS. |
| | |
| | 2) NOTE: PLEASE SEE THE "S" SHEETS WHICH CONTAIN A |
| | "RUBBER-STAMP" BY THE ENGINEER FOR THE REQUIRED |
| | ORIGINAL SIGNATURE. PLEASE SEE FLORIDA STATUES 471.025 |
| | AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| | ONE SET OF THESE PLANS ARE ALSO BEING RETAINED BY THIS |
| | OFFICE. |
| | ANY FURTHER QUESTIONS ON THIS SHALL BE MADE TO THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS. |
| | |
| | 3) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM FOR |
| | SERVICE IS INCOMPLETE AT THIS TIME. |
| | PLEASE SEE THE RISER SHOWS AN ADDITIONAL EXISTING MAIN |
| | BREAKER PANEL WHICH A PANEL SCHEDULE WAS NOT SUBMITTED |
| | FOR? PLEASE SEE NO OVER CURRENT PROTECTION IS BEING |
| | SHOWN FOR THIS NEW FEEDER TO THE PANEL "B" WHICH IS |
| | SHOWN ON RISER. |
| | PLEASE COMPLETE. |
| | 310.16, 240.4, 240.24 |
| | FBC 106.1.2, 106.3.5.4 ADMIN SECTION. |
| | |
| | 4) NOTE: PLEASE SEE MISSING THE REQUIRED FOOTER STEEL |
| | AT THE NEW DETACHED BUILDING AS REQUIRED PER 250.32, |
| | 250.50 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 2FT, |
| | 6FT AND 12FT RULE. |
| | |
| | 6) NOTE: PLEASE SEE MISSING THE REQUIRED LOADS FOR |
| | CIRCUITS FOR KITCHENS AND AREAS OF THE LIKE AS REQUIRED |
| | PER 210.52B1, 210.11C1, 220.52 |
| | |
| | 7) NOTE: PLEASE SUBMIT LOAD CALCULATIONS PER 220.83(A) |
| | AND (B). |
| | PLEASE INDICATE A LOAD SUMMARY WHICH CORRELATES WITH |
| | THE PLANS AND PANEL SCHEDULE(S). PLEASE SEE SMALL |
| | APPLIANCE CIRCUITS, WASHER/LAUNDRY ETC SHALL BE SHOWN |
| | AND COORDINATED WITH THE PANEL LOADS AS SHOWN. |
| | |
| | 8) NOTE: PLEASE VERIFY AND CORRELATE THE NEW AHU HEAT |
| | LOAD AND OVER CURRENT PROTECTION WITH THE MECHANICAL |
| | PLANS. PLEASE SEE THE LOADS SHOWN FOR THE A/C LOADS ON |
| | LOAD CALCULATIONS DO NOT CORRELATE WITH THAT OF THE |
| | LOADS SHOWN ON THE PANEL SCHEDULE? |
| | PLEASE SEE 220.83(B) AND 220.60 |
| | |
| | 9) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES |
| | REQUIRED FOR ELECTRICAL PANELS. AS THE PLANS INDICATE A |
| | 1/4INCH SCALE, THE ROOM WHERE THE PANEL IS LOCATED IS |
| | NOT LARGE ENOUGH. |
| | |
| | 10) NOTE: PLEASE CORRELATE RISER, PANEL AND PLANS. |
| | PLEASE SEE THE NEW PANEL B IS BEING SHOWN WITH OUT ANY |
| | MAIN BREAKER OR DISCONNECTING MEANS AS REQUIRED PER |
| | 225.31. PLEASE SEE PLANS HOWEVER SEEM TO SHOW SOME SORT |
| | OF DISCONNECT HOWEVER RISER DOES NOT SHOW ANY |
| | DISCONNECT. |
| | PLEASE CORRELATE THESE. |
| | |
| | 11) NOTE: PLEASE SEE 210.8A6 AND 7 AS MISSING GFI |
| | DESIGNATION ON PLANS FOR AREAS AS STATED IN THESE |
| | SECTIONS. |
| | |
| | 12) NOTE: PLEASE SEE PLANS SHALL STATE THE CODE IN |
| | WHICH THE DESIGN IS UNDER. PLEASE SEE THE PLANS SHALL |
| | STATE FOLLOWING AT A MINIMUM. |
| | 2002 NFPA-70 (NEC). |
| | 2002 NFPA-72 |
| | |
| | 13) NOTE: PLEASE 2002 NEC 210.12AS AFCI PROTECTION IS |
| | REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. |
| | (ALL). |
| | PLEASE SEE MISSING PROTECTION FOR SOME AS NOTED ON |
| | PANEL SCHEDULE. |
| | |
| | 14) NOTE: PLEASE SEE ZONING REVIEW COMMENTS AS THEY |
| | WILL AFFECT THE ELECTRICAL PLANS AND PERHAPS OTHER |
| | TRADES FOR ANY LAYOUT CHANGES ETC. |
| | |
| | 15) NOTE: PLEASE SEE PLANS INDICATE A 220V RECEPTACLE |
| | FOR THE WATER HEATER CONNECTION HOWEVER AS REQUIRED PER |
| | 422.30, 422.31 THIS IS REQUIRED TO BE HARDWIRED. MAY |
| | NOT BE CORD AND PLUG CONNECTED. |
| | |
| | 16) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE |
| | SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE |
| | DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE |
| | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| | SA/SMOKE ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** PLEASEKNOW THAT BASED ON THE PLANS SUBMITTED AND |
| | SOME INFORMATION WHICH WAS NOT SUBMITTED WHICH IS |
| | NEEDED FOR PLAN REVIEW, THERE MAY BE NEW COMMENTS ON |
| | THE NEXT REVIEW WHICH MAY NOT HAVE BEEN MADE ON THIS |
| | REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |