Plan Review Details - Permit 06070583
Plan Review Stops For Permit 06070583
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-07 Cont ID  
Sent By mjacobs Date 2006-08-07 Time 18:52 Rev Time 0.00
Received By mjacobs Date 2006-08-07 Time 18:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By mjacobs Date 2006-07-21 Time 07:18 Rev Time 0.00
Received By mjacobs Date 2006-07-21 Time 05:57 Sent To PC
Notes
2006-07-21 00:00:00 
 1) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2) FL S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 FBC108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 18:05 Sent To B
Notes
2006-08-07 00:00:00**** REDLINED PLANS **
  
 PLEASE SEE PLANS SHOWS 50A PANEL AND
 RISER ATTACHED TO PLANS SHOWS 60A.
 PLEASE ALSO SEE CONDUCTORS ALSO DO NOT
 CORRELATE.
 ** THESE ITEMS WERE REDLINED TO SEE
 RISER AND INSTALL A 60A PANEL.
  
  
 ** PLEASE ALSO SEE PLANS WERE NOTED AS
 THE POOL DECK IS UNDER A SEPARATE PERMIT
 AND NOT INCLUDED IN SCOPE OF CONTRACT.
 THIS IS NOT UNDER HOUSE PERMIT AND
 PLANS, PERMIT APPLICATION AND FEES SHALL
 BE SUBMITTED FOR DECK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 13:10 Sent To P
Notes
2006-07-20 00:00:00********* UNSAT ***********
  
 ** PLEASE KNOW, PLANS SHALL BE SPECIFIC
 TO EACH SITE AND DESIGN.
  
 1) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR ALL EXISTING LOADS AND
 NEW LOADS ADDED.
 PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE.
 220.31B,215.5, FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SEE PLANS INDICATE A NEW
 PANEL, HOWEVER NO INFORMATIONTHE
 BRANCH CIRCUITS, OCP FOR EACH. THIS CAN
 BE DONE BY THE ELECTRICAL CONTRACTOR.
 PLEASE SEE THAT ANY ADDITIONAL
 INFORMATION SUBMITTED FOR PANEL
 SCHEDULES OR LOADS SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS/DESIGN.
 240.4,310.16,215.5 ETC
 FBC 106.1.2 ADMIN SECT
  
 3) NOTE: PLEASE SEE MANY CONDUCTOR SIZES
 ARE BEING SHOWN AS #8'S TO PUMPS, BLOWER
 ETC. PLEASE KNOW THIS SEEMS TO BE A
 MISPRINT AS #8'S WILL NOT FIT INTO THESE
 PUMPS ETC.
 TABLES(9)AND 430 FOR SIZING OF
 CONDUCTORS CONDUITS.
  
 4) NOTE: PLEASE SEE MISSING 'EQUIPMENT
 GROUNDING CONDUCTOR' FROM SERVICE TO THE
 NEW POOL PANEL.
 250.110, 250.122 ETC.
  
 5) NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 AS VALUE FOR THE COMPLETE SCOPE PF WORK
 SEEMS LOW. PLEASE KNOW, A VALUE FOR
 COMPLETE SCOPE FOR POOL/ SPA/HEATER,
 TILE, NEW DECK ETC SHALL BE FIGURED.
 FBC 108.3
  
 6) NOTE: PLEASE CLARIFY WIRING RISER AS
 ONLY ONE DISC SEEMS TO BE SHOWN FOR ALL
 THREE PUMPS??
 PLEASE CLARIFY. 430.101 ETC.
  
 7) NOTE: PLEASE KNOW A NEW RECORDED NOC
 WILL BE REQUIRED UPON PICKING UP OF
 PERMIT. PLEASE SEE FS 713.13(2) AS THE
 NOC HAS EXPIRED.
 WORK WHICH HAS NOT COMMENCED WITHIN 90
 DAYS OF RECORDING NOC, THAT NOC BECOMES
 VOID.
  
  
 ** WHEN REQ'D**
 PLEASE SEE FAC 61G17 AND FS 421.025,
 PLEASE SEE THAT THE SURVEY SHALL CONTAIN
 THE RAISED SEAL AND THE ORIGINAL
 SIGNATURE AND DATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-20 Cont ID  
Sent By mperson Date 2006-07-20 Time 15:50 Rev Time 0.00
Received By mperson Date 2006-07-20 Time 15:50 Sent To B
Notes
2006-07-20 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 17:02 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 17:02 Sent To E
Notes
2006-08-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 13:57 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 13:57 Sent To E
Notes
2006-07-17 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-21 Time   Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 15:27 Sent To  
Notes
2006-07-13 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-20 Cont ID  
Sent By mperson Date 2006-07-20 Time 15:49 Rev Time 0.44
Received By mperson Date 2006-07-20 Time 15:49 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 14:41 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 14:41 Sent To I
Notes
***NONE***