| 2006-09-12 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR GAS PLAN REVIEW: (NOTE: |
| | PREVIOUS COMMENTS WERE NOT ADDRESSED) |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED DRAWINGS ONLY |
| | INDICATES THE MEASUREMENT OF THE |
| | UNDERGROUND PE PIPING. WHAT ARE THE CUT |
| | SECTION MEASUREMENTS OF THE ABOVE GROUND |
| | PIPING? |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: THE RESUBMITTED DRAWINGS ONLY |
| | INDICATE THE UNDER GROUND MATERIAL AND |
| | SIZE. WHAT IS THE SIZE AND MATERIAL OF |
| | THE ABOVE GROUND PIPING? |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | NOTE: THE RESUBMITTED DRAWINGS DO NOT |
| | INDICATE THE GAS TYPE. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: RECORDS INDICATE EXISTING GAS TO A |
| | 40 GAL. NAT. GAS WATER HEATER, PLEASE |
| | REFERENCE THE ATTACHED PERMIT |
| | INFORMATION INDICATING GAS AT SAID |
| | ADDRESS. THE BTU LOAD OF THE EXISTING AS |
| | WELL AS THE NEW PROPOSED GENERATOR BTU,S |
| | NEED TO BE INDICATED ON THE DRAWINGS. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: GAS SYSTEMS ARE SIZED BY THE |
| | LONGEST LENGTH METHOD. AGAIN THE |
| | EXISTING GAS SYSTEM NEEDS TO BE |
| | INDICATED ON THE DRAWING WITH ITS |
| | MEASUREMENTS. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: THE RESUBMITTED DRAWINGS DO NOT |
| | INDICATE THE DELIVERY PRESSURE. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: RESUBMITTED DRAWINGS DO NOT |
| | INDICATE THE DELIVERY PRESSURE, BUT IF |
| | PRESSURE IS 2LB, PLEASE SUBMIT |
| | MANUFACTURER CUT SHEETS OF REGULATORS. |
| | |
| | 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | NOTE: THE RESUBMITTED DRAWINGS DO NOT |
| | HAVE THE PRINTED NAME, SIGNED NAME OF |
| | THE PERSON RESPONSIBLE FOR DRAWING, OR |
| | THE DATE. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |