Plan Review Details - Permit 06070580
Plan Review Stops For Permit 06070580
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-01-25 Cont ID  
Sent By mperson Date 2007-01-25 Time 09:40 Rev Time 0.00
Received By mperson Date 2007-01-25 Time 09:40 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2006-12-07 Cont ID  
Sent By mperson Date 2006-12-07 Time 09:47 Rev Time 0.00
Received By mperson Date 2006-12-07 Time 09:47 Sent To PC
Notes
2006-12-07 09:49:25REFERENCE GEN/RES PERMIT #06070435 FOR GAS PLAN REVIEW
 COMMENTS.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-11-06 Cont ID  
Sent By mperson Date 2006-11-06 Time 14:31 Rev Time 0.00
Received By mperson Date 2006-11-06 Time 14:31 Sent To PC
Notes
2006-11-06 14:33:28NOTE: REFERENCE GEN/RES PERMIT #06070435

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By mperson Date 2006-09-12 Time 10:53 Rev Time 0.33
Received By mperson Date 2006-09-12 Time 10:53 Sent To  
Notes
2006-09-12 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW: (NOTE:
 PREVIOUS COMMENTS WERE NOT ADDRESSED)
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWINGS ONLY
 INDICATES THE MEASUREMENT OF THE
 UNDERGROUND PE PIPING. WHAT ARE THE CUT
 SECTION MEASUREMENTS OF THE ABOVE GROUND
 PIPING?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWINGS ONLY
 INDICATE THE UNDER GROUND MATERIAL AND
 SIZE. WHAT IS THE SIZE AND MATERIAL OF
 THE ABOVE GROUND PIPING?
  
 3. TYPE OF GAS, (LP OR NATURAL)
 NOTE: THE RESUBMITTED DRAWINGS DO NOT
 INDICATE THE GAS TYPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: RECORDS INDICATE EXISTING GAS TO A
 40 GAL. NAT. GAS WATER HEATER, PLEASE
 REFERENCE THE ATTACHED PERMIT
 INFORMATION INDICATING GAS AT SAID
 ADDRESS. THE BTU LOAD OF THE EXISTING AS
 WELL AS THE NEW PROPOSED GENERATOR BTU,S
 NEED TO BE INDICATED ON THE DRAWINGS.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: GAS SYSTEMS ARE SIZED BY THE
 LONGEST LENGTH METHOD. AGAIN THE
 EXISTING GAS SYSTEM NEEDS TO BE
 INDICATED ON THE DRAWING WITH ITS
 MEASUREMENTS.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE RESUBMITTED DRAWINGS DO NOT
 INDICATE THE DELIVERY PRESSURE.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: RESUBMITTED DRAWINGS DO NOT
 INDICATE THE DELIVERY PRESSURE, BUT IF
 PRESSURE IS 2LB, PLEASE SUBMIT
 MANUFACTURER CUT SHEETS OF REGULATORS.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 NOTE: THE RESUBMITTED DRAWINGS DO NOT
 HAVE THE PRINTED NAME, SIGNED NAME OF
 THE PERSON RESPONSIBLE FOR DRAWING, OR
 THE DATE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By mperson Date 2006-07-26 Time 14:26 Rev Time 0.55
Received By mperson Date 2006-07-26 Time 14:26 Sent To  
Notes
2006-07-26 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. THE FOLLOWING INFORMATION
 NEEDS TO BE ON THE ISOMETRIC DRAWING.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 THIS INCLUDES BOTH ABOVE AND BELOW
 GROUND.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). THIS INCLUDES THE EXISTING
 BTU LOAD AS WELL AS THE NEW.
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). THIS
 INCLUDES EXISTING AS WELL AS NEW.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE:
 IF GAS SYSTEM IS 2LB, PLEASE SUBMIT
 MANUFACTURE CUT SHEETS ON THE
 REGULATORS.)
 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE ATTACHED PERMIT
 INFORMATION INDICATING ADDRESS HAS
 EXISTING GAS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 10:48 Sent To G
Notes
2006-10-27 10:48:35TO "DPALMER" DESK/RESUB--W/PERMIT#06070435

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-26 Cont ID  
Sent By mperson Date 2006-07-26 Time 14:44 Rev Time 0.00
Received By mperson Date 2006-07-12 Time 09:20 Sent To  
Notes
2006-07-12 00:00:00TO "Z" BOX W/PERMIT#06070435