Plan Review Details - Permit 06070568
Plan Review Stops For Permit 06070568
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-01 Cont ID  
Sent By jgomez Date 2006-09-01 Time 11:01 Rev Time 0.50
Received By jgomez Date 2006-09-01 Time 10:16 Sent To PC
Notes
2006-09-01 00:00:00PLANS UNDER 'Y'

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-24 Cont ID  
Sent By jgomez Date 2006-08-24 Time 08:29 Rev Time 0.50
Received By jgomez Date 2006-08-24 Time 08:29 Sent To  
Notes
2006-08-24 00:00:00BUILDING REVIEW 3RD CHECKLIST:
  
 1- HARDISOFFIT PRODUCT APPROVAL REQUIRES
 INSTALLATION TO BE OVER MINIMUM 2"X4"
 WOOD JOISTS (OR TRUSSES) SPACED AT A
 MAXIMUM OF 16"O.C.SEE SHEET 3 OF 3
 PRODUCT APPROVAL SUBMITTED. ENGINEERED
 DRAWINGS SHOW TRUSSES SPACED AT 24"O.C.
 NEED TO PROVIDE MINIMUM SPACING AS
 REQUIRED ON PRODUCT APPROVAL. REVISE
 ENGINEERED DRAWINGS AS REQUIRED.
 ***NOTE: THIS IS THE FIRST TIME THIS
 PRODUCT APPROVAL WAS SUBMITTED FOR
 REVIEW. THAT'S WHY THIS COMMENT WAS NOT
 RAISED BEFORE.
  
 2- FLORIDA PRODUCT APPROVAL #1423:
 A) NEED TO PROVIDE 2004 CODE VERSION.
 ONE SUBMITTED IS FOR 2001.
  
 B) NEED TO PROVIDE DRAWING SHOWING THE
 SPECS OF SPECIFIED CONNECTOR. NO
 INFORMATION WAS SUBMITTED.
  
 3- FLORIDA PRODUCT APPROVAL #474 IS
 MISSING THE DRAWINGS SHOWING THE SPECS
 OF SPECIFIED CONNECTORS. NO INFORMATION
 WAS SUBMITTED.
  
 4- THERE IS A PRODUCT APPROVAL SUBMITTED
 FOR WOOD CONNECTORS U, LU, LUP, HU & WM.
 WHERE ARE THESE CONNECTORS SPECIFIED ON
 ENGINEERED DRAWINGS?.
  
 5- AS REQUESTED ON PREVIOUS CHECKLISTS,
 ENGINEER OF RECORD NEED TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS AS REQUIRED BY SECTION 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- PLEASE DON'T STAPLE PRODUCT APPROVALS
 TO ENGINEERING DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-14 Cont ID  
Sent By jgomez Date 2006-08-14 Time 09:18 Rev Time 0.40
Received By jgomez Date 2006-08-14 Time 09:17 Sent To  
Notes
2006-08-14 00:00:00BUILDING REVIEW 2ND CHECKLIST;
  
 1- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72
 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON ENGINEER'S DRAWINGS.
  
 B) HARDIPANEL SIDING.
  
 2- ENGINEER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By jgomez Date 2006-07-12 Time 17:21 Rev Time 0.00
Received By jgomez Date 2006-07-12 Time 09:17 Sent To  
Notes
2006-07-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- STRUCTURAL DRAWINGS:
 A) PROVIDE COMPLETE ENGINEERING
 PACKAGE ADDRESSING ALL STRUCTURAL WORK
 TO BE PERFORMED ON THE SPECIFIC
 BUILDING.
 B) REVISEADDRESS OF BUILDING.
 C) ALL ENGINEERING INFORMATION TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
 D) SECOND PAGE IS MISSING THE TITLE
 BLOCK AND ADDRESS OF JOB.
 E) CONNECTOR SIMPSON H2.5A SPECIFIED ON
 DETAIL #1 IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED.
 F) DETAIL #1: SPECIFY CONNECTORS FOR
 NEW (2)2X12 BEAM.
 G) SPECIFY HOW ARE NEW 2X4 SCABS
 ATTACHED TO BOTTOM OF TRUSS CHORDS?
 H) SPECIFY SIZE OF STEEL ANGLES AND
 NUMBER OF BOLTS.
 I) SPECIFY NEW SOFFITS.
 J) DETAIL #5: SPECIFY ALL CONNECTORS.
 K) DETAIL #4: SPECIFY SPACING FOR HEX
 HEAD BOLTS ALONG THE BEAM.
  
 2- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ALL STRUCTURAL CONNECTORS
 SPECIFIED ON DETAILS.
 B) DESIGNER OF RECORD TO REVIEW AND
 APPROVE ALL PRODUCT APPROVALS PRIOR TO
 SUBMITTAL.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-28 Cont ID  
Sent By adarroug Date 2006-08-28 Time 16:46 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 16:46 Sent To B
Notes
2006-08-28 00:00:00TO "JGOMEZ" DES/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 13:30 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 13:29 Sent To B
Notes
2006-08-21 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-14 Cont ID  
Sent By jgomez Date 2006-08-14 Time 09:16 Rev Time 0.00
Received By jgomez Date 2006-08-11 Time 08:55 Sent To  
Notes
2006-08-11 00:00:00TO "JGOMEZ" DESK/RESUB