Plan Review Details - Permit 06070544
Plan Review Stops For Permit 06070544
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By alange Date 2006-07-24 Time 09:01 Rev Time 0.00
Received By alange Date 2006-07-24 Time 09:01 Sent To  
Notes
2006-07-24 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COMPLETE SETS OF PLANS
 FOR REVIEW.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, ROOFING, LINTELS, STRAPS AND
 TIE-DOWNS AND GLASS BLOCK.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 11.SEE GENERAL NOTE #1.SHOULD READ,
 WEST PALM BEACH NOT PALM BEACH COUNTY.
  
 12.CORRECT AREA CALCS TO INCLUDE THE
 CORRECT SQUARE FOOTAGE FOR COVERED
 PATIO.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 07:35 Sent To M
Notes
2006-07-20 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE KNOW PLANS ARE REQUIRED
 TO CONTAIN THE CURRENT CODE RELEVANT AND
 IN EFFECT FOR THE JOB. PLEASE SEE THAT
 PLANS REFLECT THE FOLLOWING AT A MIN
 2004 FBC, 2002 NFPA-70, NFPA-72 2002
 PLEASE SEE OTHER CODES FOR OTHER TRADES
 WHICH MAY BE NEEDED.
 106.1.2
 ** PLEASE ALSO SEE PLANS MENTIONS WORK
 PER "PALM BEACH COUNTY", HOWEVER PLEASE
 SEE THAT THE SCOPE OF WORK IS IN THE
 CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE MANY RECEPTS MISSING
 PER 210.52
 PLEASE SEE MANY OF THESE AREAS AARE
 REDLINED ON PLANS SUBMITTED.
 PLEASE SHOW ALL EXISTING RECEPTS WHICH
 MEET CODE AND SHOW AS "E" NEXT TO THE
 RECEPTS. PLEASE KNOW, DUE TO THE AMOUNT
 OF RENOVATION AND ADDITION, RECEPTS MAY
 NEED TO BE BROUGHT UP TO CODE.
  
 3) NOTE: PLEASE SEE NOTE MENTIONS ARC
 FAULT FOR EXISTING BEDRMS WILL BE
 BROUGHT UP TO CODE WITH ARROWS, HOWEVER
 PLEASE SEE THESE ARROWS AND THIS NOTE IS
 IN THE GARAGE??
 PLEASE SEE OTHER COMMENTS AS ALL ARC
 FAULT CIRCUITS WILL BE REQUIRED ON A
 PANEL SCHEDULE.
 210.12B
  
 4) NOTE: PLEASE SEE THAT ALL SLEEPINGS
 RMS AND ADAPTABLE SLEEPING RMS SHALL
 CONTAIN SD'S INSIDE AND OUTSIDE. PLEASE
 PROVIDE A LAYOUT FOR ALL NEW OR EXISTING
 MEETING CURRENT CODES. PLEASE ALSO KNOW
 , ALL SHALL BE WIRED INLINE ETC AS
 REQUIRED PER NFPA-72 11.5.1.1, 11.8.3
 R313
  
 5) NOTE: PLEASE SUBMIT AND PROVIDE A
 COMPLETE PANEL SCHEDULE SHOWING ALL
 CIRCUITS AND MIN REQUIRED DEDICATED
 CIRCUITS. PLEASE INDICATE ALL OCP AND
 MIN CONDUCTORS SIZES.
 408.4, 240.4,310.16 ETC.
  
 6) NOTE: PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUIT(S) PER 210.52D,
 210.11C3, MUST BE 20A AND #12.
  
 7) NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE AN "O" ABOVE MAIN, IS THIS
 ACTUALLY THE METER? IS THIS A METER/MAIN
 COMBO?
 PLEASE BE SURE TO SHOW LOCATION OF ALL
 SERVICE EQUIPMENT ON PLANS.
 PLEASE SEE 240.24, 230.70, 110.26 ETC
 FOR LOCATIONS NOT PERMITTED AND
 LOCATIONS REQUIRED.
  
 8) NOTE: PLEASE THE LOAD CALCS INDICATE
 ONLY ONE GDO CIRCUIT, HOWEVER TWO DOORS
 ARE SHOWN. PLEASE VERIFY AND INDICATE OF
 EXISTING.
 106.1.2
  
 9) NOTE: PLEASE SEE PLANS DO NOT
 INDICATE THE EXISTING OR NEW A/C SYSTEM.
 PLEASE SHOW THE LOCATION OF THE AHU AND
 CU'S ALONG W/ DISCONNECTS AS REQUIRED
 PER 440.11.
 PLEASE ALSO SEE 210.70 IF IN ATTIC AND
 PLEASE SEE 210.63 FOR GFI REQUIRED
 OUTSIDE.
  
 10) NOTE: PLEASE SEE MISSING GFI ALONG
 WALL SPACE ON KITCHEN COUNTER SPACE.
 210.52C1
  
 11) NOTE: PLEASE SEE MIN VA REQUIRED FOR
 WASHER AND LAUNDRY PER 220.169, 210.11C2
  
 12) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR THE ARCHOTECTURAL
 FIRM AS REQUIRED UNDER THE FAC
 61G1-16.004 AND FS 481.219
 MISSING CERTIFICATE OF AUTHORIZATION #.
  
 13) NOTE: PLEASE SEE THAT TWO SETS OF
 ALL PLANS ARE SUBMITTED FOR REVIEW AND
 STAMPING. ONE SET REMAINS ONFILE AND
 ONE SET GOES BACK TO JOBSITE FOR
 INSPECTIONS.
  
 14) NOTE: PLEASE SEE 210.52B1 FOR MIN
 CIRCUIT(S) FOR DINING, BREAKFAST AREAS
 ETC OF THE LIKE. PLEASE SEE THESE SHALL
 BE 20A AND #12 ALONG WITH MIN VA PER
 210.11C1,220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 11:26 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 11:26 Sent To E
Notes
2006-07-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-24 Cont ID  
Sent By alange Date 2006-07-24 Time 09:09 Rev Time 0.00
Received By alange Date 2006-07-12 Time 14:08 Sent To  
Notes
2006-07-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-07-20 Cont ID  
Sent By tgordon Date 2006-07-20 Time 14:05 Rev Time 0.20
Received By tgordon Date 2006-07-20 Time 14:05 Sent To P
Notes
2006-07-20 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By mperson Date 2006-07-21 Time 10:16 Rev Time 1.30
Received By mperson Date 2006-07-21 Time 10:16 Sent To B
Notes
2006-07-21 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL. (NOTE: THE SANITARY
 ISOMETRIC RISER DIAGRAM INDICATED ON
 SHEET A3 DOES NOT REFLECT THE FLOOR
 PLAN)
 2. PER FBC-2004, CHAPTER 1, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.(NOTE: NOT ALL PIPES
 ARE SIZED ON THE PLUMBING RISER)
 3. PER FBC-2004 PLUMBING, SECTION 420.
 WATER CLOSETS HAVE INTREGRAL TRAPS,
 THEREFORE THE TRAPS INDICATED ON THE
 PLMG. RISER DIAGRAM ON SHEET A3 SHALL BE
 ELIMINATED ON THE RESUBMITTAL.
 4. PER FBC-2004, SECTION 708, PLEASE
 INDICATE THE FOLLOWING ON SHEET A3,
 PLMG. RISER DIAGRAM FOR THE RESUBMITTAL.
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (B) ELIMINATE "OPTION W/C AND SHOWER
 DRAIN BE USED AS CLEANOUTS" ON SHEET A3
 PLMG. RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 13:05 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 13:05 Sent To I
Notes
2006-07-16 00:00:00DENIED,
 1. MUST PROVIDE TWO SETS OF PLANS WITH
 PERMIT APPLICATION.
 2. ONLY ONE SET WAS SUBMITTED.
  
 NOTE: (ZONING STAMP VOIDED)
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720