| 2006-07-16 00:00:00 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW AS PER THE |
| | "RED-TAG" CORRECTION NOTICE ATTACHED TO |
| | PERMIT APPLICATION, MUST FIRST OBTAIN A |
| | PERMIT FOR THE INSTALLATION OF THE SPA |
| | AND DECK BEFORE AN ELECTRICAL PERMIT CAN |
| | BE ISSUED. |
| | 105.1 |
| | |
| | 2) NOTE: PLEASE CLARIFY AND CORRELATE |
| | LOADS ON CALCUALTIONS. PLEASE SEE RISER |
| | SUBMITTED INDICATES 38A'S, HOWEVER LOAD |
| | INDICATED ONLY @ 5200VA? . PLEASE SEE |
| | 5200VA DIVIDED BY 240, DOES NOT COME UP |
| | TO 38A'S?? |
| | PLEASE ALSO SEE LOAD SHOWN ON LEFT HAND |
| | SIDE OF CALCS MENTIONS 6KW? |
| | IS THE "ADD HEAT" MEANT TO BE A/C HEAT? |
| | 220.31B |
| | |
| | 3) NOTE: PLEASE KNOW, DISCONNECT IS |
| | REQUIRED WITHIN USER READLIY ACCESSIBLE |
| | LOCATION "WITHIN SIGHT" HOWEVER MORE |
| | THAN 5'. 680.41 |
| | |
| | 4) NOTE: PLEASE BE SURE ALL PLANS |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR |
| | PLANS/DESIGN. FBC 106.1.2 ADMIN SECT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |