Plan Review Details - Permit 06070514
Plan Review Stops For Permit 06070514
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-09 Cont ID  
Sent By btrobaug Date 2006-10-25 Time 15:01 Rev Time 0.00
Received By btrobaug Date 2006-10-23 Time 08:03 Sent To  
Notes
2006-11-08 14:22:44 
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}REFERENCE SHEET E-1. THE GENERARTOR GROUNDING
 DETAIL INDICATES THE NEUTRAL AND GROUND NOT BE BONDED
 AT THE GENERATOR. HAVING ESTABLISHED THIS GENERATOR AS
 A SEPARATELY DERIVED SYSTEM IT MUST BONDED PER
 250.30(A)(1). PLEASE MAKE THE NOTE CHANGE.
  
 2}

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By btrobaug Date 2006-07-13 Time 14:58 Rev Time 1.00
Received By btrobaug Date 2006-07-13 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2006-07-18 Time 11:19 Sent To  
Notes
2006-07-18 00:00:00WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By pkrauss Date 2006-07-17 Time 13:57 Rev Time 0.00
Received By pkrauss Date 2006-07-17 Time 13:57 Sent To FIRE
Notes
2006-07-17 00:00:00NO FUEL LINES INDICATED/GENERATOR IS
 SELF-CONTAINED WITH A BELLY TANK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 10:22 Sent To E
Notes
2006-07-13 00:00:00TO "BTROBAUG" DESK--EXPEDITED PLAN--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 11:21 Rev Time 0.00
Received By mwennerg Date 2006-07-12 Time 13:07 Sent To  
Notes
2006-07-12 00:00:00TO "MMCLEAN" DESK--EXPEDITED PERMIT--

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-17 Cont ID  
Sent By pkrauss Date 2006-07-17 Time 13:54 Rev Time 0.00
Received By pkrauss Date 2006-07-17 Time 13:13 Sent To FIRE
Notes
2006-07-17 00:00:00EXTERIOR SELF CONTAINED (SUB-BASE FUEL
 TANK) DIESEL GENERATOR. ENCLOSURE TO
 REDUCE GEN NOISE PER MANUFACTURER'S
 SPECIFICATIONS.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By mmclean Date 2006-07-13 Time 07:41 Rev Time 0.00
Received By mmclean Date 2006-07-13 Time 07:41 Sent To I
Notes
2006-07-13 00:00:00NOTE: THE PROPOSED GENERATOR SHOULD BE
 ENCLOSED WITH LANDSCAPE BUFFER.