| Notes |
| 2006-07-16 00:00:00 | ******** UNSAT ********** | | | | | | 1) NOTE: PLEASE INDICATE LOADS INTENDED | | | FOR NEW FEED AND LOADS ON EXISTING | | | PANEL. | | | 220.31., 215.5 | | | | | | 2) NOTE: PLEASE SEE 225.31-225.39 FOR | | | MEANS OF DISONNECT REQUIRED AT THE | | | DETACHED BLDG/SHED. | | | PLEASE KNOW, MIN CLEARENECES SHALL BE | | | MAINTAINED PER 110.26 | | | | | | 3)NOTE: PLEASE PROVIDE GROUNDING | | | ELECTRODE SYSTEM AT THE DETACHED BLDG | | | PER 250.32 | | | | | | ** PLEASE KNOW, DEPTH MUST BE PER 300.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|