Plan Review Details - Permit 06070505
Plan Review Stops For Permit 06070505
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 15:49 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 15:42 Sent To PC
Notes
2006-07-16 00:00:00******** UNSAT **********
  
 1) NOTE: PLEASE INDICATE LOADS INTENDED
 FOR NEW FEED AND LOADS ON EXISTING
 PANEL.
 220.31., 215.5
  
 2) NOTE: PLEASE SEE 225.31-225.39 FOR
 MEANS OF DISONNECT REQUIRED AT THE
 DETACHED BLDG/SHED.
 PLEASE KNOW, MIN CLEARENECES SHALL BE
 MAINTAINED PER 110.26
  
 3)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED BLDG
 PER 250.32
  
 ** PLEASE KNOW, DEPTH MUST BE PER 300.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  