Plan Review Details - Permit 06070501
Plan Review Stops For Permit 06070501
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-20 Cont ID  
Sent By rnuquist Date 2007-02-20 Time 19:02 Rev Time 0.00
Received By rnuquist Date 2007-02-20 Time 19:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-13 Cont ID  
Sent By rnuquist Date 2006-12-13 Time 19:26 Rev Time 0.00
Received By rnuquist Date 2006-12-13 Time 19:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By alange Date 2006-10-17 Time 09:00 Rev Time 0.00
Received By alange Date 2006-10-17 Time 08:50 Sent To  
Notes
2006-10-17 09:07:45DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 4."R" VALUES ON ENERGY CALCS DO NOT MATCH PLANS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 08:55 Rev Time 0.00
Received By alange Date 2006-07-31 Time 08:55 Sent To  
Notes
2006-07-31 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 3.MINIMUM FOOTING DEPTH SHALL BE 12"
 SEE R-403.1.4
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS AND STRAPS AND TIEDOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 11.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS R 807.1
  
 12.SQUARE FOOTAGE ON APPLICATION IS
 INCORRECT.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 13.FEES DUE FOR RADON PRIOR TO
 RESUBMITTING.SEE ATTACHED INVOICE.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-04-23 Cont ID  
Sent By dpalmer Date 2007-04-23 Time 15:56 Rev Time 0.00
Received By dpalmer Date 2007-04-23 Time 13:13 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2007-04-07 Time 15:33 Sent To PC
Notes
2007-04-08 08:13:12** UNSAT **
  
 1) NOTE: PLEASE SEE THE SHEETS SUBMITTED HAVE BEEN
 REVISED WITH SHEET DESIGNATIONS AND THE INFORMATION
 WHICH DOES NOT CORRELATE WITH THE RECORD SET OF PLANS.
 PLEASE SEE THAT SEVERAL CHANGES HAVE BEEN MADE WHICH
 ARE NOW IN QUESTION.
 PLEASE CLARIFY THE REVISED SITE PLAN IN E-1 WHICH USED
 TO BE E-2 AND CONTAIN INFORMATION ON THE EXISTING AND
 NEW SMOKE ALARMS?
 PLEASE REVISE AND INCLUDE THE INFORMATION AS PREVIOUSLY
 PERMITTED. PLEASE ALSO SEE THE FOLLOWING COMMENTS WITH
 RESPECT TO PANEL LOCATIONS.
  
 2) NOTE: PLEASE SEE THE REVISED PLANS NOW SEEM TO PLACE
 THE NEW ELECTRICAL SUB PANEL IN A CLOSET OR STORAGE
 ROOM WHICH IS NOT PERMITTED. PLEASE SEE 240.24, 110.26,
 AND 408.7.
  
 3) NOTE: PLEASE SEE THE REVISED SITE PLAN WHICH DOES
 NOT INCLUDE THE METER ON PLANS FOR SERVICE LOCATION?
 PLEASE SHOW.
 230.70,71.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE RISER DIAGRAM HAS NOW BEEN REVISED
 TO SHOW A 320AMP BREAKER IN THE 400A RATED ENCLOSURE?
 PLEASE SEE 240.6 AS 320 IS NOT A BREAKER SIZE. PLEASE
 CLARIFY AND ADJUST PLANS.
 PLEASE ALSO SEE THE RISER AND PLANS SEEM TO HAVE
 REVISED THE SUB PANEL *B* TO A 125AMP PANEL YET THE
 OCP/BREAKER FEEDING THIS PANEL REMAINS 100AMPS? PLEASE
 SEE THE LOAD ON THIS PANEL HAS NOW ALSO INCREASED
 HOWEVER THE LOADS ON THE PANEL REMAIN THE SAME AS THE
 PREVIOUS REVIEWED PLANS?
 PLEASE SEE THE REVISED SHEET NOW NO LONGER CONTAINS ANY
 LOAD CALCULATIONS FOR THE SERVICE AT ALL?
 PLEASE COMPLETE AND SUBMIT COMPLETED REVISED LOAD
 CALCULATIONS PER 220.31B.
 FBC 106.3.5.1.2,106.1.2. NEC 215.5
  
 5) NOTE: PLEASE SEE LOCATIONS ON PLANS WHICH INDICATE
 LIGHTING BEING CONTROLLED FROM MORE THAN ONE LOCATION
 YET THE SWITCHES ARE NOT 3-WAY?
  
 6) NOTE: PLEASE SE THE SMOKE ALARMS ARE CIRCUITED TO
 CIRCUIT 12, YET THE PANEL SCHEDULE SHOWS THIS CIRCUIT
 AS SPARE?
 PLEASE REVISE PANEL SCHEDULE TO INCLUDE ALL DESIGNATED
 LOCATIONS AND AREAS IN WHICH THE CIRCUITS FEED. THE USE
 OF GEN LTS AND GEN RECPTS IS NOT LONGER PERMITTED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE NEC HANDBOOK. 408.4
 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 240.4, 310.16.
 PLEASE PROVIDE THE PANEL DESIGNATION TO THE CIRCUITS
 SHOWN. ARE THEY ALL FROM THE NEW SUB PANEL?
  
 7) NOTE: PLEASE SEE 110.26 AS THE DISC FOR THE CU IS
 SHOWN BEHIND THE UNIT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-08 07:59:14IN REVIEW
2007-04-07 16:00:592007-04-07 16:00:59
 NOTES TO FOLLOW ON 4/8

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-01-11 Cont ID  
Sent By dpalmer Date 2007-01-11 Time 12:31 Rev Time 0.00
Received By dpalmer Date 2007-01-11 Time 11:48 Sent To PC
Notes
2007-01-11 12:32:09REDLINED,
 SOME CODE SECTIONS ON PLANS REFERENCED ARE FROM THE
 1996 NEC, WHEN THEY SHOUD BE FROM THE 2002.
 PLANS OK, FOR CODE COMPLIANCE. STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-12-24 Cont ID  
Sent By dpalmer Date 2006-12-24 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2006-12-24 Time 14:50 Sent To PC
Notes
2006-12-24 15:57:45**UNSAT 4TH REVIEW**
  
 ***PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE 680.71 FOR GFI DESIGNATION IS
 REQUIRED FOR THE JACUZZI CIRCUIT EITHER AT THE RECEPT
 OR THE BRANCH BREAKER FEEDING THIS.
  
 2) NOTE:PLEASE SEE SHEET E-2 AND E-1. PLEASE SEE LOAD
 CALCULATIONS FOR PANEL "B" WHICH ARE COMPLETELY
 DIFFERENT FROM EACH CALCULATION. PLEASE SEE THE PANEL
 "B" LOAD CALCULATION SUBMITTED ON E-1 AND E-2 DO NOT
 COMPLY WITH THE NEC 220.31 EITHER PART. A/C LOADS SHOWN
 AT 16,080 AND DE-RATED AT 40%. THERE IS NO LOCATION IN
 THE CODE WHERE THIS AMOUNT OF UNITSOR UNIT CAN BE
 DE-RATED AT 40%. PLEASE SEE THERE ARE LOADS ON
 NEUTRAL CALCULATIONS FOR EQUIPMENT WHICH IS NOT ON
 PANEL SCHEDULE OR STANDARD CALCULATIONS. PLEASE SEE
 LOADS ON PANEL "B" NOT ON E-2 CALCULATIONS AND VICE
 VERSA.
 PLEASE SEE MISSING THE LOADS PER 220.31, 220.16,
 220.19, 220.31B ETC.
 PLEASE SEE LOAD CALCULATION FOR SERVICE CAN NOT
 VERIFIED AT THIS TIME AS LOADS MAY OR MAY NOT EXCEED
 THE RATING OF THE NEW 300A MCB AS SHOWN.
 *** FYI, WHEN USING AND INSTALLING A FULL SIZED
 NEUTRAL, NEUTRAL LOAD CALCULATIONS ARE NOT REQUIRED BY
 THIS AHJ, HOWEVER ARE PERMITTED TO BE SUBMITTED. PLEASE
 KNOW IF THESE ARE SHOWN ON PLANS, THEN THEY MUST BE
 CODE COMPLIANT AND CORRELATE WITH PANEL SCHEDULES AND
 LOADS
  
 3) NOTE: PLEASE SEE RISER IS NOW COMPLETELY REVISED
 FROM PREVIOUS PLANS. PLEASE SEE MISSING THE FEEDERS
 FROM THE NEW MAIN BREAKER PANEL BOARD TO THE EXISTING
 PANEL "A". PLEASE SEE 310.15B6, 310.16, AND PLEASE SEE
 MISSING EQUIPMENT GROUNDING CONDUCTOR PER 250.24,
 250.110, 250.122.
  
  
 4 NOTE: PLEASE SHOW A LAYOUT OF THE ELECTRICAL SERVICE
 ON PLANS. PLEASE SEE SHEET E-2 INDICATES THE EXISTING
 200A SERVICE, HOWEVER DOES NOT INDICATE IF THIS IS
 WHERE THE NEW PROPOSED SERVICE IS GOING TO BE
 INSTALLED.
 PLEASE SHOW.
 FBC 106.1.2, 230.70, 110.26 , NEED TO VERIFY AND SHOW.
  
 ** NOTE: PLEASE SEE NOTE ON RISER STILL INDICATES ALL
 MAINS AND BREAKERS TO BE 22K?
 THIS IS OK, HOWEVER IF NOTED, THEN 22K RATED BREAKERS
 WILL BE REQUIRED.
  
 5) NOTE: PLEASE SEE FS 481.221 (3) AND 4).
  
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE REMOVED
 FROM SETS AND WILL BE PLACED WITH PREVIOUS RETAINED
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-21 Cont ID  
Sent By dpalmer Date 2006-11-21 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2006-11-21 Time 16:46 Sent To M
Notes
2006-11-21 18:38:29*** UNSAT3RD REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE FROM THE PREVIOUS
 REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE
 ALSO SEE SOME NEW NOTES DUE TO CHANGES IN PLANS AND HOW
 THINGS ARE NOW SHOWN ON THE PLANS SUBMITTED. PLEASE
 ALSO SEE A NEW ELECTRICAL SHEET WHICH WAS NOT ON EITHER
 OF THE FIRST TWO REVIEWS.
 PLEASE SEE TWO NEW NOTES WHICH WERE MISSED BY THIS
 REVIEWER FROM THE PREVIOUS SET OF PLANS. ( MASTER BATH
 GFI RECEPT LOCATION/LOADS FOR A/C'S ON EXIST PANEL
 "A").
  
  
 1) NOTE: PLEASE PROVIDE A LAYOUT FOR THE SMOKE ALARM
 DEVICE IN THE EXISTING DWELLING AREAS EITHER EXISTING
 WHICH MEET THE CURRENT CODE OR NEW TO BE INSTALLED.
 THIS WAS REQUESTED ON PREVIOUS REVIEWS.
 NEED TO SHOW THE SA DEVICES INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
 PLEASE ALSO SEE A DETAIL WAS SUBMITTED WHICH MENTIONED
 NEW AND EXISTING BEING TIED TO CIRCUIT B-12, HOWEVER
 PLEASE SEE SMOKE DETECTOR DETAIL WHICH SHOWS THESE
 BEING CIRCUITED TO THE KITCHEN OR BATH LIGHTING
 CIRCUIT.
 PLEASE KNOW AS PER A RECENT CONFERENCE; PLEASE INDICATE
 THESE DEVICES AS "SA" FOR SMOKE ALARM PER THE
 DEFINITIONS FROM NFPA-72. PLEASE KNOW AS PER AN
 INTERPRETATION FROM NFPA A SD(SMOKE DETECTOR) IS A
 DEVICE WHICH ONLY "DETECTS" AND DOES NOT SOUND AN
 AUDIBLE ALARM, WHERE A SA (SMOKE ALARM) DOES BOTH. THIS
 COMMENT WAS NOT MADE ON THE PREVIOUS REVIEWS AS THIS
 WAS ONLY BROUGHT TO ATTENTION RECENTLY. PLEASE BE SURE
 TO ADJUST CIRCUITING AS DETAIL SHOWS KIT/BATH CIRCUIT
 AND PLANS CALL FOR B-12.
 NFPA-72 11.5.1.1,11.8.3, FBC R313
  
 2) NOTE: PLEASE SEE PLANS NOW CALL FOR 22K AIC RATINGS
 FOR ALL MAIN AND BREAKERS. PLEASE VERIFY THIS STATEMENT
 AS 22K RATED BRANCH BREAKERS WOULD BE ALMOST UNHEARD OF
 FOR A SINGE FAMILY DWELLING AND IT DOES NOT SEEM THIS
 IS THE INTENT OF WHAT THE DESIGN IS SUGGESTING. THE
 EXSPENSE OF ALL BREAKERS BEING 22K WOULD ALSO BE
 SUBSTANITAL. IS THE INTENT TO MAKE THE MAINS 22K RATED
 WITH A SERIES RATING FOR THE BRANCH BREAKERS? IF SO,
 PLEASE INDICATE THIS .
 PLEASE SEE 110.9, 240.12.
 PLEASE SEE PANEL SCHEDULE AND MIS-PRINT FOR PANELS
 WHICH SHOWS "ACI" RATINGS.
  
 3) NOTE: PLEASE SEE A GFI IS BEING SHOWN IN JACUZZI
 AREA WHICH IS PART OF THE BATH ROOM RECEPT CIRCUIT
 HOWEVER ON THE PREVIOUS REVIEW THIS GFI DESIGNATION WAS
 BEING TAKEN FOR THE JACCUZZI TUB, HOWEVER UPON REVIEW
 THE PLANS APPEAR TO BE SHOWING A GFI RECEPT LOCATED
 ABOVE AND IN THE TUB AREA WHICH IS STRICTLY PROHIBITED.
 PLEASE SEE 210.52D. PLEASE SEE 680.71 FOR GFI
 DESIGNATION IS REQUIRED FOR THE JACUZZI CIRCUIT EITHER
 AT THE RECEPT OR THE BRANCH BREAKER FEEDING THIS.
 PLEASE ALSO SEE THE FOLLOWING COMMENT.
  
 4) NOTE: PLEASE SEE THE PLANS APPEAR TO HAVE INTENDED A
 DEDICATED CIRCUIT FOR THE MASTER BATH GFI AND OTHER
 BATH GFI, HOWEVER THE PANEL DESIGNATION DOES NOT
 INCLUDE "BATH" GFI, ONLY SHOWS BEDROOM GFIFOR EACH OF
 THESE.
 PLEASE SEE 210.52D, 210.11.C3
  
 5) NOTE: PLEASE SEE THE DINING ROOM DESIGNATION WAS
 REMOVED FROM THE ELECTRICAL PLANS.
 PLEASE PLACE ON PLANS.
 FBC 106.1.2, ADMIN SECT. 210.52B1
  
 6) NOTE: PLEASE SEE THERE IS NOW A SHEET E-2 WITH LOAD
 CALCULATIONS FOR PANEL "B" WHICH IS COMPLETELY
 DIFFERENT FROM THE PANEL "B" LOAD CALCULATION SUBMITTED
 ON E-1.??
 PLEASE SEE MISSING THE LOADS PER 220.31, 220.16 ETC.
  
 7) NOTE:PLEASE ALSO SEE PANEL "A" SHOWS LOAD
 CALCULATIONS WHICH INDICATE 20KW OF HEAT LOADS YET
 PANEL SCHEDULE ONLY INDICATES A TOTAL OF 15KW OF HEAT.
 (ONE AT 10KW AND THE OTHER AT 5KW).
 PLEASE SEE LOAD CALCULATIONS ALSO SHOW A "SHIFT" OF
 SOME KIND ON THE LOADS TO THE RIGHT OF ALL THE
 APPLIANCES.
 BOTH OF THESE ITEMS WERE SHOWN THE SAME WAY ON PREVIOUS
 PLANS(2ND SET) HOWEVER WAS NOT COMMENTED ON. 220.31.
  
 8) NOTE: PLEASE SEE RISER IS STILL SHOWING "EQUIPMENT
 GROUNDING CONDUCTORS" BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED. PLEASE SEE 250.6,
 AND 250.24B. THE FOLLOWING IS TAKEN FROM THE CODE.
  
 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS.
 (A) ARRANGEMENT TO PREVENT OBJECTIONABLE CURRENT. THE
 GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS,
 SURGE ARRESTERS, AND CONDUCTIVE NON-CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND ARRANGED
 IN A MANNER THAT WILL PREVENT OBJECTIONABLE CURRENT
 OVER THE GROUNDING CONDUCTORS OR GROUNDING PATHS.
  
 THE REST OF 250.6 AND 250.24B TALKS OF THE EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF
 DISCONNECT ONLY.
  
 9) NOTE: PLEASE SHOW A LAYOUT OF THE ELECTRICAL SERVICE
 ON PLANS TO VERIFY GROUPING OF MAINS PER 230.72.
  
  
 10) NOTE: PLEASE SEE THAT ON THE PREVIOUS REVIEW A
 NOTICE WAS GIVEN WITH REFERENCE TO FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS. PLEASE
 KNOW SOME OF THE ABOVE COMMENTS ARE THE SAME FROM THE
 FIRST AND SECOND REVIEW, HOWEVER THE PLANS SEEM TO HAVE
 INTENT AND AN ATTEMPT TO ADDRESS COMMENT(S), EVEN
 THOUGH IT MAY NOT HAVE BEEN ADDRESSED FULLY. THE 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE PERMIT FEE IS NOT
 ASSESSED AT THIS TIME.
 PLEASE SEE SOME OTHER COMMENTS WERE ORIGINATED ON THE
 SECOND REVIEW WHICH WILL NEED TO BE ADDRESSED BY THE
 NEXT REVIEW SO THE NOTICE IS STILL GIVEN AS A NOTICE
 ONLY.
 AS ON PREVIOUS REVIEW ONE SET OF EACH OF THE ELECTRICAL
 PLANS ARE BEING RETAINED BY THIS OFFICE FOR FILE. ONE
 SET OF THE REDLINED PLANS ARE BEING RETURNED. ** IT IS
 RECOMMENDED THAT IF THERE ARE NAY QUESTIONS, COMMENTS
 OR THE NOTES TYPED ABOVE ARE NOT CLEAR IN ANY FASHION,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE TO GO
 OVER COMMENTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 14:13 Sent To M
Notes
2006-10-01 00:00:00***** UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE MANY OF THE COMMENTS FROM
 THE PREVIOUS REVIEW ARE STILL IN NEED OF
 BEING ADDRESSED. PLEASE ALSO SEE NEW
 NOTES FOR CHANGES IN PLANS MADE AND NEW
 NOTES.
 PLEASE SEE MOST COMMENTS ARE THE SAME AS
 PREVIOUS REVIEW AND ALL NOTES BELOW ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH
 NEW NOTES ADDED TO BOTTOM OF LIST.
  
 1) NOTE: NO, PLEASE SEE AN AIC RATING IS
 SHOWN FOR METER CAN NOT NEW MAIN AND
 PANEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: OK, SIZED CORRECTED HOWEVER
 PLEASE SEE OTHER COMMENT FOR FOOTER
 STEEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.66 FOR THE NEW
 MIN SIZE GROUNDING ELECTRODE CONDUCTOR
 AS SERVICE HAS NOW INCREASED TO 300A'S.
 #2 MIN).
  
 3) NOTE: YES, ADDED THESE FROM MAINS TO
 SUB PANELS, HOWEVER PLEASE SEE NOW
 "EQUIPMENT GROUNDING CONDCUTORS" HAVE
 ALSO NOW BEEN ADDED FROM METERCAN TO
 MAINS, WHICH NOW PARALLEL'S THE NEUTRAL.
 PLEASE SEE 250.6, 250.24B AS THIS IS NOT
 PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEEMISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO
 PANELS.
 250.110,250.24B,250.122.
  
 4) NOTE: NO, SAME NOTE, PLEASE SEE PANEL
 SCHEDULE STILL SHOW THE SAME.
 SEE FEEDERS AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY 3/0'S SHOWN FOR
 NEUTRAL'S FOR BOTHPANELS? PLEASE SEE
 THIS IS SHOWN FOR 100A PANELS?
 PLEASE KNOW, 3/0'S WILL NOT FIT INTO
 LUGS ON SMALLER EQUIPMENT.
 106.1.2
  
 5) NOTE: NO, SAME COMMENT AS PANEL
 SCHEDULES STILL SHOW 300A PANELS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND
 PANELS AS PANELS ARE SHOWN AS 300A'S
 EACH.?
 240,215.5,106.1.2
  
 6) NOTE:NO, PLEASE SEE A #6 IS NOTED TO
 NEW SUB PANEL, HOWEVER PLEASE SEE THE
 SIZE SHALL BE AS STATED FOR NEW #2 AND
 SHALL EXTEND TO THEGROUNDING ELECTRODE
 SYSTEM.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE NEW FOOTER STEEL IS
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
 250.50.
  
 7) NOTE:NO, PLEASE PROVIDE LAYOUT FOR
 ALL SD'S EITHER EXISTING OR NEW TO BE
 INSTALLED WHICH CONFORM TO THE CURRENT
 NFPA-72 2002 AS NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SD'S AS
 REQUIRED PER NFPA-72 11.5.1.1, 11.8.3,
 PLEASE ALSO PROVIDE A LAYOUT OF THE
 EXISTING SD'S IF EXISTING WHICH MEET THE
 CURRENT CODE OR NEW SHALL BE INSTALLED.
 R313
  
 8) NOTE: NO, PLEASE SEE CIRCUITING FOR
 DINING, KITCHEN SMALL APPL CIRCUITS TWO
 OR MORE SHALL NOT FEED ANY OTHER AREAS,
 AND RECEPTS. ONLY PERMITTED TO FEED THE
 AREAS OF THE LIKE. PLEASE SEE ELECTRICAL
 DEVICES IN OTHER AREAS ON THE DINING
 APPLIANCE CIRCUIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LTS BEING SHOWN ON A
 SMALL APPL CIRCUIT?
 MECH RM? PLEASE KNOW, NO OTHER LOADS ARE
 PERMITTED ON THE SMALL APPL CIRCUITS.
 210.52B1.
  
 9) NOTE: OK, AS FIXTURE IS NOTED .
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: NO, SAME NOTE>
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULE
 FOR AREAS AND RMS AS NOTED. 408.4.
 IE: BED RM LT, MASTER NEDRM RECEPTS ETC.
  
 15) NOTE: NO, SAME NOTE, PLEASE SEE
 "BATH" GFI/ OR DEDICATED CIRCUIT(S) ARE
 NOT SHOWN ON PANEL SCHEDULE. SEE NOTE
 ABOVE #14.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3.
 MUST ALSO BE 20A AND #12. SHOWS #14 AND
 15A.
  
 16) NOTE: NO, PLEASE SEE NOTE ABOVE WITH
 RESPECT TO NO OTHER ELECTRICAL DEVICES
 ON THIS CIRCUIT, HOWEVER SEE PREVIOUS
 NOTE FOR MIN VA FOR THIS CIRCUIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DINING RM/AREA CIRCUITS PER
 210.52B1,210.11C1, 220.16.
  
 17) NOTE: NO, PLEASE SEE THERE ARE SOME
 ELECTRICAL DEVICES W/OUT CIRCUIT #'S
 ONLY MINOR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 240.4,310.16,215.5 ETC
 FBC 106.1.2, 106.3.5.4
  
 18) NOTE: NO, PLEASE SEE 2002 AND SEE
 ALL CIRCUITING AS SHOWN ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2002 NEC 210.12B
 AND PLEASE LIST ALL THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRED.
 PLEASE KNOW, AFCI IS NOT ONLY FOR
 RECEPTS.
 408.4
  
 19) NOTE: NO, HOWEVER THIS COMMENT SEEM
 TO HAVE BEEN ADDRESSED BUT AS ONLY A
 MISPRINT AS TWO- NFPA-72'S ARE SHOWN.
 MISSING ONLY THE "70". THIS WOULD HAVE
 BEEN REDLINED, HOWEVER PLANS ARE COMING
 BACK FOR OTHER CORRECTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL
 REFERENCE THE FOLLOWING CODES ADOPTED
 AND IN EFFECT FOR THIS PROJECT.
 NFPA-72 2002, NFPA-70 2002. FBC 2004
  
 20) NOTE: NO, PLEASE SEE PREVIOUS NOTE.
 PLEASE ALSO SEE THE PRINTED CA # IS NOT
 CLEAR AND VISABLEON ALL SHEETS, THIS
 WAS HAND-WRITTEN BY THISREVIEWER IN
 ORDER FOR OTHERS TO CLEARLY SEE #.
 PLEASE STILL SEE MISSING PRINTED NAME AS
 REQUIRED.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS FOR THE
 ARCHITECT'S PRINTED NAME AND PRINTED
 LICENSE #.
 PLEASE ALSO SEE PLUMB NOTES AS THE
 SIGNATURE ON PLAUMB RISER ATTACHED TO
 PLANS IS NOT AN ORIGINAL"WET" SIGNATURE.
 PLAN CONTAINS A RAISED SEAL OVER A
 "PHOTO-COPIED" SIGNATURE..
 FS 481.221, FAC 61G1-16.004
  
 21) NOTE: NO, PLEASE SEE NOTE ABOVE FOR
 AFCI PROTECTION AND NOTE FOR EXISTING.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE SD NOTE WHICH IS
 ADDED TO PLANS.
 PLEASE SEE IF THE CIRCUITING IS DONE AS
 NOTED, THEN ARC FAULT PROTECTION WILL BE
 REQUIRED FOR THOSE CIRCUITS ALSO.
 PLEASE KNOW, ALL SD'S ARE REQUIRED TO BE
 WIRED "INLINE".
 PLEASE INDICATE CIRCUITING FROM
 EXISTING.
  
 22) NOTE: OK.
  
 23) NOTE: NO/YES, PLEASE SEE CONDUITS
 WERE CORRECTED O RISER DIAGRAM, HOWEVER
 FEEDER SCHEDULE ON PANEL WAS NOT.
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CONDUIT SIZES AS
 SHOWN AND CONDUCTORS AS SHOWN EXCEED THE
 MAXIMUM PIPE FILL AS SHOWN. PLEASE SEE
 MAX FIGURES IN TABLE CHAPTER 9.
 215.5,106.1.2, ETC
  
 24) NOTE: OK.
  
 25) NOTE: OK, HOWEVER THIS WILL REMAIN
 AS A NOTE FOR NEXT SUBMITTIAL.
  
 ** PREVIOUS REVIEW NOTE **
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE COMPLETE, PLANS ARE
 PICKED UP AND BEFORE RESUBMITTING PLANS.
 PLEASE COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS. ONLY ONE COPY
 OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE ONLY.
  
  
 ***** NEW NOTES*****
  
 26) NOTE: PLEASE VERIFY THE NEW AND
 EXISTING MAINS ARE GROUPED ON
 SITE/OVERVIEW PLAN.
 230.72
  
 27) NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 NOTICE TO FS ABOVE IS ONLY A NOTICE
 GIVEN AT THIS TIME.
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS
 FROM EACHREVIEW HAVE BEEN RETAINED FOR
 FILE DUE TO THE EXTENT OF ELECTRICAL
 COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-22 Cont ID  
Sent By dpalmer Date 2006-07-22 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 20:01 Sent To M
Notes
2006-07-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SEE 250.66 FOR THE NEW
 MIN SIZE GROUNDIGN ELECTRODE CONDUCTOR
 AS SERVICE HAS NOW INCREASED TO 300A'S.
 #2 MIN).
  
 3) NOTE: PLEASE SEEMISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO
 PANELS.
 250.110,250.24B,250.122.
  
 4) NOTE: PLEASE CLARIFY 3/0'S SHOWN FOR
 NEUTRAL'S FOR BOTHPANELS? PLEASE SEE
 THIS IS SHOWN FOR 100A PANELS?
 PLEASE KNOW, 3/0'S WILL NOT FIT INTO
 LUGS ON SMALLER EQUIPMENT.
 106.1.2
  
 5) NOTE: PLEASE CORRELATE RISER AND
 PANELS AS PANELS ARE SHOWN AS 300A'S
 EACH.?
 215.5,106.1.2
  
 6) NOTE: PLEASE SEE NEW FOOTER STEEL IS
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
 250.50.
  
 7) NOTE: PLEASE SEE MISSING SD'S AS
 REQUIRED PER NFPA-72 11.5.1.1, 11.8.3,
 PLEASE ALSO PROVIDE A LAYOUT OF THE
 EXISTING SD'S IF EXISTING WHICH MEET THE
 CURRENT CODE OR NEW SHALL BE INSTALLED.
 R313
  
 8) NOTE: PLEASE SEE LTS BEING SHOWN ON A
 SMALL APPL CIRCUIT?
 MECH RM? PLEASE KNOW, NO OTHER LOADS ARE
 PERMITTED ON THE SMALL APPL CIRCUITS.
 210.52B1.
  
 9) NOTE: PLEASE PROVIDE A FIXTURE
 SCHEDULE FOR CLOSET LTS. PLEASE SEE
 410.8 FOR MIN CLEARENCES.
  
 10) NOTE: PLEASE SEE 424.3B FOR MIN OPC
 FOR AHU HEAT. PLEASE SEE 10+ KW UNIT
 WITH 40A OCP??? AND #8 AWG.
 PLEASE CORRECT.
  
 11) NOTE: PLEASE SEE MISSING A/C
 DISCONNECTS AS REQUIRED PER 440.11 AND
 MIN CLEARENCES PER 110.26.
  
 12) NOTE: PLEASE SEE MISSING GFI
 REQUIRED FOR CU'S. 210.63, 210.8A
  
 13) NOTE: PLEASE SEE MISSING EGRESS LT
 AND CONTROL FROM MASTER BEDRM. 210.70,
 LS 101 7.8
  
 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 FOR AREAS AND RMS AS NOTED. 408.4.
 IE: BED RM LT, MASTER NEDRM RECEPTS ETC.
  
 15) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3.
 MUST ALSO BE 20A AND #12. SHOWS #14 AND
 15A.
  
 16) NOTE: PLEASE SEE MISSING REQUIRED
 DINING RM/AREA CIRCUITS PER
 210.52B1,210.11C1, 220.16.
  
 17) NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 240.4,310.16,215.5 ETC
 FBC 106.1.2, 106.3.5.4
  
 18) NOTE: PLEASE SEE 2002 NEC 210.12B
 AND PLEASE LIST ALL THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRED.
 PLEASE KNOW, AFCI IS NOT ONLY FOR
 RECEPTS.
 408.4
  
 19) NOTE: PLEASE SEE PALSN SHALL
 REFERENCE THE FOLLOWING CODES ADOPTED
 AND IN EFFECT FOR THIS PROJECT.
 NFPA-72 2002, NFPA-70 2002. FBC 2004
  
 20) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS FOR THE
 ARCHITECT'S PRINTED NAME AND PRINTED
 LICENSE #.
 PLEASE ALSO SEE PLUMB NOTES AS THE
 SIGNATURE ON PLAUMB RISER ATTACHED TO
 PLANS IS NOT AN ORIGINAL"WET" SIGNATURE.
 PLAN CONTAINS A RAISED SEAL OVER A
 "PHOTO-COPIED" SIGNATURE..
 FS 481.221, FAC 61G1-16.004
  
 21) NOTE: PLEASE SEE SD NOTE WHICH IS
 ADDED TO PLANS.
 PLEASE SEE IF THE CIRCUITING IS DONE AS
 NOTED, THEN ARC FAULT PROTECTION WILL BE
 REQUIRED FOR THOSE CIRCUITS ALSO.
 PLEASE KNOW, ALL SD'S ARE REQUIRED TO BE
 WIRED "INLINE".
 PLEASE INDICATE CIRCUITING FROM
 EXISTING.
  
 22) NOTE: PLEASE CLARIFY AND VERIFY
 WHERE THE CWP IS FOR THE GROUNDING
 ELECTRODE SYSTEM. PLEASE SEE
 250.50,250.52 ETC.
 PLEASE SHOW.
  
 23) NOTE: PLEASE SEE CONDUIT SIZES AS
 SHOWN AND CONDUCTORS AS SHOWN EXCEED THE
 MAXIMUM PIPE FILL AS SHOWN. PLEASE SEE
 MAX FIGURES IN TABLE CHAPTER 9.
 215.5,106.1.2, ETC
  
 24) NOTE: PLEASE SEE MAIN DISCONNECTS
 ARE MISSING THE SIZE AND OCP FOR EACH.
 240.4,310.16,230.70 ETC.
  
 25) NOTE: *** IMPORTANT**
 ONCE ALL REVIEWS ARE COMPLETE, PLANS ARE
 PICKED UP AND BEFORE RESUBMITTING PLANS.
 PLEASE COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS. ONLY ONE COPY
 OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
2006-07-21 00:00:00REVIEW TO CONTINUE. PLANS WILL GO INTO
 "F" STATUS.
 NOTES TO FOLLOW WHEN REVIEW IS COMPLETE.

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 12:52 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 12:52 Sent To E
Notes
2007-04-19 12:52:29TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 14:21 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 14:21 Sent To M
Notes
2007-04-17 14:22:12TO "M"BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 15:10 Sent To P
Notes
2007-04-13 15:11:15TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-05 Cont ID  
Sent By spalmer Date 2007-04-05 Time 17:40 Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:40 Sent To E
Notes
2007-04-05 17:40:40TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 09:06 Sent To B
Notes
2007-02-09 09:06:37TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 19:02 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 19:02 Sent To E
Notes
2007-01-09 19:02:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 11:17 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 11:12 Sent To E
Notes
2006-12-19 11:17:51TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 09:22 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 09:22 Sent To E
Notes
2006-11-21 09:22:35TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 16:46 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 16:46 Sent To Z
Notes
2006-11-15 16:47:02TO "Z" BOX/RESUB--NEW "Z" AND "P" SHEETS SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 13:42 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 13:42 Sent To E
Notes
2006-09-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 17:28 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 17:28 Sent To Z
Notes
2006-09-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 15:43 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 15:42 Sent To E
Notes
2006-07-20 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 09:03 Rev Time 0.00
Received By alange Date 2006-07-12 Time 14:50 Sent To  
Notes
2006-07-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-18 Cont ID  
Sent By tgordon Date 2007-04-18 Time 10:04 Rev Time 0.30
Received By tgordon Date 2007-04-18 Time 10:04 Sent To  
Notes
2007-04-18 10:05:06REVISION TO MECH. PLANS PAGE AC-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-22 Cont ID  
Sent By tgordon Date 2006-11-22 Time 10:34 Rev Time 0.30
Received By tgordon Date 2006-11-22 Time 10:34 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 08:58 Rev Time 0.30
Received By tgordon Date 2006-10-02 Time 08:58 Sent To P
Notes
2006-10-02 00:00:00*** DENIED ***
 1) AD ARCHITECTURE INC. COMPANY NAME
 APPEARS ON MECHANICAL PLANS THEREFORE
 THE ARCHITECT'S INFORMATION MUST APPEAR
 IN THE TITLE BLOCK, PER FAC 61G1-16.004
  
 2) ALSO THE ARCHITECT WILL NEED TO SIGN
 AND SEAL THE PLANS, OR REMOVE HIS
 COMPANY INFORMATION FROM THEM.
  
 3) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 15:47 Rev Time 0.20
Received By tgordon Date 2006-07-24 Time 15:47 Sent To B
Notes
2006-07-24 00:00:00*** DENIED ***
 1) PROVIDE ALL GRILL SIZES (SUPPLY AND
 RETURN) ON MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-05-02 Cont ID  
Sent By jleech Date 2007-05-02 Time 07:20 Rev Time 0.00
Received By jleech Date 2007-05-02 Time 07:20 Sent To  
Notes
2007-05-02 07:21:37ADDED A LAUNDRY TUB AND LAV TO PLUMBING SYSTEM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-06 Cont ID  
Sent By jleech Date 2006-12-06 Time 11:10 Rev Time 0.00
Received By jleech Date 2006-12-06 Time 11:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 10:59 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 10:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-22 Cont ID  
Sent By jleech Date 2006-07-22 Time 12:24 Rev Time 0.00
Received By jleech Date 2006-07-22 Time 12:24 Sent To M
Notes
2006-07-22 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM; (A) SIGNITURE
 OF ARCHITECT IS A PHOTO COPY. SEE
 FBC-2004 CHAPTER 1 SEC. 106. (B) NO
 HORIZONTAL DRY VENTS PERMITED. (C) SIZE
 ALL PIPE SECTIONS.
 2. SEE ELECTRICAL PLAN REVIEW NOTE #20.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-17 Cont ID  
Sent By mmclean Date 2006-11-17 Time 06:58 Rev Time 0.00
Received By mmclean Date 2006-11-17 Time 06:58 Sent To I
Notes
2006-11-17 06:59:25NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF LANDSCAPE,
 WHICHEVER IS LESS WITHIN THE FIRST 25FT FRONT SETBACK.
  
 NOTE: THE PROPOSED ADDITION MUST HAVE INTERIOR ACCESS
 AND CANNOT BE USED FOR A SEPARATE LIVING SPACE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By mmclean Date 2006-09-26 Time 18:26 Rev Time 0.00
Received By mmclean Date 2006-09-26 Time 18:26 Sent To HIST
Notes
2006-09-26 00:00:00NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 NOTE: THE PROPOSED ADDITION MUST HAVE
 INTERIOR ACCESS AND CANNOT BE USED FOR A
 SEPARATE LIVING SPACE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By mmclean Date 2006-07-19 Time 17:59 Rev Time 0.00
Received By mmclean Date 2006-07-19 Time 17:59 Sent To I
Notes
2006-07-19 00:00:00DENIED,
 1. THE HOA APPROVAL LETTER DOES NOT
 SPECIFIED WHAT THEIR APPROVING, PLEASE
 PROVIDE THE DOCUMENT THAT HAS BEEN
 SIGNED BY THE HOA.
 2. THE PROPOSED ADDITION DOES NOT SHOW
 ON THE FLOOR PLAN AN INTERIOR ACCESS
 FROM THE EXISTING STRUCTURE TO THE NEW
 ADDITION.
 3. THE PROPOSED ADDITION CANNOT BE USED
 FOR A SEPERATE LIVING SPACE AND HAVING
 ANOTHER COOKING FACILITY WITHIN THE
 STRUCTURE.
 4. THE SITE PLAN MUST SHOW THE LOCATION
 OF THE NEW A/C UNIT & RELOCATION OF THE
 EXISTING A/C UNIT.
 5. IF THE PROPOSED ADDITION ENROACH IN
 THE UTILITY EASEMENT, PLEASE SUBMIT ALL
 UTILITY EASEMENT APPROVAL FROM
 BELLSOUTH, FPL, FLORIDA PUBLIC
 UTILITIES, ADELPHIA)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720