| Plan Review Stops For Permit 06070499 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-10-16 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-10-16 |
Time |
07:25 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-10-03 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-10-03 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | DENIED BY BUILDING | | | | | | 1) THRESHOLD BUILDINGS REQUIRE THREE | | | SETS OF SIGNED AND SEALED PLANS. CITY | | | AMENDMENTS TO FBC 106.1 AND 109.3.6. | | | SOME OF THE PAGES ARE MISSING FROM | | | PLANS. THREE COMPLETE SETS ARE REQUIRED. | | | SEE PLUMBING REVIEW COMMENTS. | | | | | | 2) PREVIOUS COMMENTS HAVE BEEN ADDRESSED | | | BY ENGINEER'S LETTER. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-09-18 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-09-18 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2006-09-18 00:00:00 | DENIED BY BUILDING | | | | | | 1) THRESHOLD BUILDINGS REQUIRE THREE | | | SETS OF SIGNED AND SEALED PLANS. CITY | | | AMENDMENTS TO FBC 106.1 AND 109.3.6. | | | | | | 2) PREVIOUS COMMENTS HAVE BEEN ADDRESSED | | | BY ENGINEER'S LETTER. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-08-10 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-08-10 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2006-08-10 00:00:00 | DENIED | | | | | | 1)13-412.1.ABC.2.6 SWIMMING POOL AND | | | SPA TEMPERATURE CONTROLS. | | | | | | 13-412.1.ABC.2.6.1 TIME SWITCHES. | | | TIME SWITCHES SHALL BE INSTALLED ON | | | SWIMMING POOL HEATERS AND PUMPS. | | | | | | 2) POOL COVERS | | | 13-412.1.ABC.2.6.2 POOL COVERS . | | | HEATED POOLS SHALL BE EQUIPPED WITH A | | | VAPOR RETARDANT POOL COVER ON OR AT THE | | | WATER SURFACE. POOLS HEATED TO MORE THAN | | | 90?F (32?C) SHALL HAVE A POOL COVER WITH | | | A MINIMUM INSULATION VALUE OF R -12. | | | | | | 3) 13-412.1.ABC.2.6.3 POOL HEATERS. | | | POOL HEATERS SHALL BE EQUIPPED WITH A | | | READILY ACCESSIBLE ON-OFF SWITCH TO | | | ALLOW SHUTTING OFF THE HEATER WITHOUT | | | ADJUSTING THE THERMOSTAT SETTING. POOL | | | HEATERS FIRED BY NATURAL GAS SHALL NOT | | | HAVE CONTINUOUSLY BURNING PILOT LIGHTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-12 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-12 |
Time |
14:25 |
Sent To |
P |
|
| Notes |
| 2006-10-12 14:47:39 | STAMPED ON PREVIOUS REVIEW, SAME SHEETS WITH NEW PLUMB | | | ADDED ON 8 1/2 X 11. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-01 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-01 |
Time |
09:57 |
Sent To |
P |
|
| Notes |
| 2006-10-01 00:00:00 | OK, ELECTRICAL PAGES STAMPED. | | | | | | ** SHEETS FOR BUILDING IS NOT PART OF | | | THIS PERMIT AND THOSE SHEETS ARE FOR | | | REFERENCE ONLY AND ANY REVSIONS WHICH | | | ARE NEEDED, NEED TO BE SUBMITTED UNDER | | | THE MAIN BUIDLING PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-17 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-17 |
Time |
13:24 |
Sent To |
P |
|
| Notes |
| 2006-09-17 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE THAT THE ELECTRICAL | | | PLANS OK, HOWEVER BEING THAT THIS IS A | | | THRESHOLD PROJECT, A MINIMUM OF THREE | | | SETS ARE REQUIRED FOR REVIEW AND | | | STAMPING. | | | | | | 106.1, 109.3.6 | | | | | | THERE IS NO NEED TO SUPPLY THE | | | ELECTRICLA PLANS REFERENCE UNDER THE | | | BASE BUILDING PERMIT/PLANS. | | | ONLY THE PLANS FROM THE POOL ENGINEER. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-28 |
Time |
07:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-27 |
Time |
21:08 |
Sent To |
P |
|
| Notes |
| 2006-07-28 00:00:00 | ******** USNAT ******** | | | | | | 1) NOTE: PLEASE ADJUST VALUE FOR SCOPE | | | OF WORK. PLEASE KNOW VALUE SHALL INCLUDE | | | ALL LABOR AND MATERIALS, EVEN IF ANY | | | MATERIALS ARE OWNER SUPPLIED. | | | FBC 108.3 | | | PLEASE KNOW THAT THIS OFFICE MAY ASSESS | | | A VALUE BASED ON THE GUIDES ADOPTED | | | UNDER THE FBC. | | | VALUE IS CURRENTLY VERY LOW. | | | | | | 2) NOTE: PLEASE PROVIDE AN ELECTRICLA | | | WIRING DIAGRAM SHOWING ALL BRANCH | | | CIRCUITS TO EQUIPMENT ALONG WITH OCP, | | | AND CONDUCTOR SIZES. | | | PLEASE SUBMIT A PANEL SCHEDULE FOR | | | EQUIPMENT INDICATING ALL EQUIPMENT. | | | PLEASE NOTE WHERE PANEL LOCATION IS. | | | PLEASE SEE MINIMUM WORKIGN CLEARENCES | | | SHALL BE MET FOR DISCONNECTING MEANS | | | ETC, THE ROOM SEEMS TO CONTAIN EQUIPMENT | | | IN MANY AREAS AND AS NO ELECTRICAL IS | | | SHOWN, MINCLEARENCES ETC CAN NOT BE | | | VERIFIED. | | | PLEASE COMPLETE . | | | 240.4,310.16,110.26, 408.4 ETC | | | FBC 106.1.2 ADMIN SECT. | | | | | | 3) NOTE: PLEASE BE SURE THE RAISED SEAL | | | ON PLANS ARE CLEAR AND VISABLE WITH ALL | | | INFORMATION ON ENGINEER'S SAID SEAL. | | | FS 471.025 FAC 61G15-23.002, .001 | | | THIS IS REQUIRED FOR ALL SHEETS AND FOR | | | ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-10-13 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-10-13 |
Time |
11:14 |
Sent To |
B |
|
| Notes |
| 2006-10-13 11:17:26 | CONTRACTOR INFORMATION | | | NOTE: GAS PERMIT REQUIRED. | | | ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINALINSPECTION. | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-08-01 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-01 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-08-01 |
Time |
10:35 |
Sent To |
B |
|
| Notes |
| 2006-08-01 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-11 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-11 |
Time |
09:03 |
Sent To |
E |
|
| Notes |
| 2006-10-11 09:04:15 | TO "DPALMER" DESK/RESUB--NEW SHEETS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-28 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-28 |
Time |
10:05 |
Sent To |
E |
|
| Notes |
| 2006-09-28 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-09 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-09 |
Time |
18:02 |
Sent To |
E |
|
| Notes |
| 2006-09-09 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-27 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-27 |
Time |
17:38 |
Sent To |
E |
|
| Notes |
| 2006-07-27 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-08-10 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-07-12 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-10-13 |
Time |
11:00 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-10-13 |
Time |
10:59 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-10-02 |
Time |
08:53 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-10-02 |
Time |
08:52 |
Sent To |
B |
|
| Notes |
| 2006-10-02 00:00:00 | DENIED 3RD TIME | | | | | | THE FOLLOWING INFORMATION IS STILL | | | REQUIRED FOR PLUMBING PLAN REVIEW: | | | | | | 1. PER FBC-2004 PLUMBING, SECTION | | | 802.2.1 AIR GAP:THE AIR GAP BETWEEN | | | THE INDIRECT WASTE AND THE FLOOD RIM OF | | | THE WATSTE RECEPTOR SHALL BE A MINIMUM | | | OF TWICE THE EFFECTIVE OPENING OF THE | | | INDIRECT WASTE PIPE. | | | NOTE: PLEASE CORRECT SHEET SP-1.07 POOL | | | WASTE LINE DETAIL FROM A THREE INCH AIR | | | GAP TO A SIX INCH AIR GAP FOR THE | | | RESUBMITTAL. | | | 2. THE RESUBMITTED PRINTS ON SHEETS | | | SP-1.07 AND SP-2.03 NEED TO HAVE A NEW | | | REVISION DATE FOR THE NEW RESUBMITTED | | | DETAILS INDICATING THE NEW REVISED POOL | | | AND SPA WASTE LINE DETAILS. | | | 3. THE RESUBMITTED PRINTS NEED TO BE | | | CORRELATED SO THAT THE NEW POOL AND SPA | | | WASTE LINE DETAILS ARE IN ALL THREE | | | RESUBMITTED SETS OF PRINTS. | | | NOTE: A) REVISED SHEET SP-1.07 IS | | | MISSING ON ONE OF THE THREE RESUBMITTED | | | SETS. | | | B) REVISED SHEET SP-2.03 IS | | | MISSING ON TWO OF THE THREE RESUBMITTED | | | SETS. | | | 4. PLEASE DELETE THE POOL AND SPA WASTE | | | DETAILS THAT HAVE BEEN CROSSED OUT IN | | | RED INK AND ARE NOT CODE COMPLIANT ON | | | SHEETS SP-2.03 AND SP-2.04 AND ONLY | | | RESUBMIT THE NEW POOL AND SPA WASTE | | | DETAILS. | | | 5. SEE ATTACHED NOTICE FLORIDA STATUTE | | | 553.80(2)(B) REGUARDING FOUR (4) TIMES | | | THE FEE. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-09-18 |
Time |
09:03 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2006-09-18 |
Time |
09:03 |
Sent To |
B |
|
| Notes |
| 2006-09-18 00:00:00 | ******DENIED 2ND TIME****** | | | REFERENCE: FBC-2004 SEC. 424.1 PUBLIC | | | SWIMMING POOLS. | | | FBC-2004 CHAPTER 1 | | | FBC-2004 PLUMBING | | | | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW: | | | | | | 1. THE POOL WASTE LINE AIR GAP DETAIL | | | INDICATED ON SHEETS SP-1.07 AND SP-2.04 | | | ARE UNACCEPTABLE. A MINIMUM AIR GAP OF | | | 6" IS REQUIRED FOR A 3" WASTE PIPE PER | | | FBC-2004 PLUMBING SECTION 802.2.1. | | | PLEASE NOTE THE DEFINITION OF AIR GAP. | | | AIR GAP (DRAINAGE SYSTEM)- THE | | | UNOBSTRUCTED VERTICAL DISTANCE THROUGH | | | THE FREE ATMOSPHERE BETWEEN THE OUTLET | | | OF THE WASTE PIPE AND THE FLOOD LEVEL | | | RIM OF THE RECEPTACLE INTO WHICH THE | | | WASTE PIPE IS DISCHARGING. | | | NOTE: PLEASE SEE THE CORRECTED DRAWING | | | IN RED ON SHEET SP-1.07 FOR REFERENCE | | | FOR RESUBMITTAL. | | | 2. NOTE: THIS IS A THRESHOLD PROJECT, A | | | MINIMUM OF THREE COPIES REQUIRED FOR | | | REVIEW AND STAMPING PER FBC-2004 CHAPTER | | | 1 SECTION 106.1 AND SECTION 109.3.6. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-08-01 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-01 |
Time |
09:29 |
Rev Time |
2.00 |
| Received By |
mperson |
Date |
2006-08-01 |
Time |
09:29 |
Sent To |
G |
|
| Notes |
| 2006-08-01 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004, SECTION 424.1. | | | SWIMMING POOLS: | | | | | | THE FOLLOWING CORRECTIONS AND INFORMA- | | | TION IS REQUIRED FOR PLUMBING PLAN | | | REVIEW: | | | | | | 1) PLEASE CORRELATE SHEET SP-1.04, SWIM- | | | MING POOL PIPING PLAN AND SHEET SP-1.06, | | | SWIMMING POOL SCHEDULE OF EQUIPMENT IN | | | RELATION TO ITEM #4 EQUALIZER FITTING | | | AND ITEM #5 GUTTER DRAINS. THESE ITEMS | | | ARE NUMBERED INCORRECTLY ON SHEET | | | SP-1.04. ALSO ON SHEET SP-1.06 PIPING | | | SUPPORT DETAIL THE GUTTER DRAIAN IS | | | INCORRECTLY INDICATED AS AN EQUALIZER | | | FITTING. PLEASE CORRECT ANDSEE | | | CORRECTED DRAWING IN RED INK FOR | | | REFERENCE FOR RESUBMITTAL. | | | 2) PLEASE NOTE THAT ON SHEETS SP-1.07, | | | SP-2.03 AND SP-2.04 THE POOL AND SPA | | | WASTE LINE AIR GAP DETAILS INDICATE THE | | | POOL EQUIPMENT BEING DRAINED INTO THE | | | STORM SEWER SYSTEM, THIS IS INCORRECT, | | | THEY SHALL DRAIN INTO TRAPPED HUB DRAINS | | | INTO THE SANITARY SYSTEM. PLEASE CORRECT | | | AND SEE CORRECTED DRAWING IN RED INK FOR | | | REFERENCE FOR RESUBMITTAL. | | | 3) ON SHEETS SP-1.07 AND SP-2.01 GAS | | | POOL HEATERS ARE INDICATED PLEASE | | | PROVIDE MANUFACTURER CUT SHEETS WITH THE | | | FOLLOWING INFORMATION. | | | (A) FBC-2004 SEC. 424.1.6.5.14 SWIMMING | | | POOL WATER HEATERS SHALL BEAR THE LABEL | | | OF A RECOGNIZED TESTING AGENCY. | | | (MANUFACTURE SHEETS REQUIRED, PLEASE | | | SUBMIT) | | | (B) WATER RETENTION, PROVIDE A POSITIVE | | | MEANS OF RETAINING WATER IN THE HEATER | | | WHEN PUMP IS SHUT OFF.(MANUFACTURE | | | SHEETS REQUIRED, PLEASE SUBMIT) | | | 4) PLEASE SEE ELECTRICAL COMMENT #3 | | | REGUARDING ENGINEER'S SEAL. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2006-10-18 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2006-10-18 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2006-10-18 12:00:55 | LANDSCAPE AND ROOF TERRACE INCLUDED IN MAIN PERMIT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-07-25 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2006-07-25 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2006-07-25 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2006-07-25 00:00:00 | POOL REVIEW; LANDSCAPE REQS TO BE | | | REVIEWED WITH LANDSCAPE SUBMITTAL. | | | MJF |
|
|