| 2006-08-22 00:00:00 | BUILDING REVIEW 3RD CHECKLIST: |
| | |
| | TRUSS PACKAGE: |
| | 1- ENGINEER TO PROVIDE ALL HIS |
| | INFORMATION IN ALL DWGS AS REQ'D BY |
| | CHAPTER 471 FL. ST. & SEC. 61G15-23.002 |
| | OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | ***NO DONE. |
| | |
| | 2- ALL ENGINEER DRAWINGS AND LETTERS |
| | NEED TO BE SIGNED AND SEALED AS REQUIRED |
| | BY CHAPTER 471 FL. ST. AND 61G15-23.002, |
| | INCLUDING ALL GENERAL NOTES AND GENERAL |
| | DETAILS. |
| | |
| | ***NO DONE. |
| | |
| | 3- A) GENERAL DETAILS NEED TO BE |
| | UPDATED. FBC 2004 CALLS FOR ASCE 7-02, |
| | NOT ASCE 7-98. ENGINEER TO UPDATE ALL |
| | DRAWINGS. |
| | |
| | ***NO DONE. |
| | |
| | B) PROVIDE ONLY THE DETAILS THAT |
| | APPLY TO THIS JOB. PLEASE, DON'T PROVIDE |
| | UNNECESSARY INFORMATION TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | ***OK. |
| | |
| | 4- DESIGN LOADS SHOWN IN TRUSS LAYOUT, |
| | ENGINEERED TRUSS AND GENERAL DRAWINGS |
| | NEED TO MATCH. REVISE AS REQUIRED. |
| | |
| | |
| | ***NO DONE. |
| | |
| | 5- SPECIFY ROOF SHEATHING NAILING. SEE |
| | TABLE 2304.9.1 FBC 2004. |
| | |
| | ***OK. |
| | |
| | 6- SPECIFY TRUSS TO WALL CONNECTORS AND |
| | PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AS REQUIRED BY RULE 9B-72. GO |
| | TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| | PRODUCT APPROVALS. |
| | |
| | *** DRAWING 11A BY THE ENGINEER JOHN |
| | HOLT AND TRUSS LAYOUT DON'T MATCH. TRUSS |
| | LAYOUT CALLS FOR RAKED BEAM, WHILE |
| | DRAWING 11A CALLS FOR GABLE END TRUSS. |
| | THERE IS NOT GABLE END TRUSS. ENGINEER |
| | DRAWING 11A AND TRUSS DRAWINGS TO MATCH. |
| | ***NOTE: MAKE SURE DRAWING 11A IS |
| | LEGIBLE. |
| | |
| | 7- ROOF PITH OF 2.5:12 REQUIRES 2 LAYERS |
| | OF UNDERLAYMENT. SEC. 1507.2.2 FBC 2004. |
| | |
| | ***OK. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |