Plan Review Details - Permit 06070486
Plan Review Stops For Permit 06070486
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By lursu Date 2006-07-11 Time 10:42 Rev Time 0.00
Received By amorse Date 2006-07-11 Time 11:22 Sent To  
Notes
2006-07-11 00:00:00NEED AN EXTENSION FOR UNIT # 202
 CREATE TEMPORARY PCN = TEMP7443431528202
 FOR THE UNIT 202 UNDER 1617 N FLAGLER
 DR.PERMIT MUST BE ATTACHED TO IT BEFORE
 PRINTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By amorse Date 2006-09-06 Time 11:23 Rev Time 0.00
Received By amorse Date 2006-09-06 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-17 Cont ID  
Sent By amorse Date 2006-08-17 Time 07:08 Rev Time 0.00
Received By amorse Date 2006-08-17 Time 07:08 Sent To  
Notes
2006-08-17 00:00:00 
  
 DENIED
  
 1) PLEASE MAKE NEW COPIES OF THE UPDATED
 DRAWINGS WITH ALL CHANGES AND RESIGN. NO
 INK,PENCIL OR WHITEOUT CAN BE PRESENT ON
 DRAWINGS OTHER THAN SIGNATURE OF
 RESPONSIBLE PARTY. OTHERWISE BUILDING IS
 OK
  
 2) PLEASE SHOW DEED TO PERMIT CLERK WHEN
 RESUBMITTING NEW DRAWINGS TO HAVE OWNERS
 NAME ENTERED INTO SYSTEM BEFORE PERMIT
 CAN BE PRINTED AS IT IS STILL UNDER TDC
 FLAGLER. PLEASE BE SURE ENTIRE DEED WITH
 NOTORIZED SECTION IS COPIED OR IT WILL
 NOT BE ACCEPTED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By amorse Date 2006-07-21 Time 09:56 Rev Time 0.00
Received By amorse Date 2006-07-21 Time 09:56 Sent To PC
Notes
2006-07-21 00:00:00 
  
 DENIED
  
 1) PROVIDE CORRECT ADDRESS (UNIT NUMBER)
 PROPERTY APPRAISER HAS MISTER DUNN IN
 UNIT 302. IF HE IS INDEED OWNER OF 202
 PROVIDE PROOF OF OWNERSHIP SUCH AS DEED
  
 2) IF INFORMATION IS INCORRECT THEN A
 NEW NOC WILL BE REQUIRED WITH THE
 CORRECT INFORMATION. ALSO BE AWARE THAT
 THE TAX FOLIO/PCN NUMBER IS INCORRECT ON
 THE APPLICATION AND THE NOC
  
 3) THE PERSONS RESPONSIBLE FOR THE
 DRAWINGS SHALL SIGN AND DATE THEM. ALSO
 LEGIBLY PRINT THEIR NAME, ADDRESS AND
 PHONE NUMBER ON THE PLANS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 08:12 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 08:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-15 Cont ID  
Sent By dpalmer Date 2006-08-15 Time 13:12 Rev Time 0.00
Received By dpalmer Date 2006-08-15 Time 13:09 Sent To  
Notes
2006-08-15 00:00:00** UNSAT **
  
 1) NOTE: PLEASE PROVIDE TWO COPIES WHICH
 DO NOT CONTAIN HAND WRITTEN ITEMS IN
 PEN. PLEASE KNOW PLANS IN PEN OR PENCIL
 MAY BE CHANGED AT ANY TIME.
 106.1.
  
 ELEC IS OK.
  
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 18:58 Sent To  
Notes
2006-07-18 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE INDICATE CIRCUITING ON
 PLANS FOR NEW RECEPTS, SD, LTS ETC
 PLEASE SEE INDICATE CONTROL FOR ALL
 ITEMS(LTS).
 PLEASE SEE MISSING LIGHTING AND CONTROL
 FOR BEDRM.
 PLEASE CORRELATE WITH A PANEL SCHEDULE
 TO BE SUBMITTED.408.4, 210.12B, 210.70
  
 2) NOTE: PLEASE SEE SD'S ARE NOTED AS
 BEING EXISTING, HOWEVER EXISTING PLANS
 DO NOT INDICATE SD'S AND IT IS THE
 KNOWLEDGE OF THIS OFFICE SINCE THESE
 RMS/AREAS WERE NOT BUILT OUT UNDER BASE
 BLDG, THAT SD'S DID NOT MEETING REQUIRED
 SPACES AS SPACE WAS OPEN.
 PLEASE SEE NFPA-72 11.5.1.1, AND PLEASE
 SEE NEC 210.12B AS ALL ARE REQUIRED TO
 BE ARC FAULT PROTECTED, WIRED INLINE
 ETC.
  
 3) NOTE: PLEASE CLEARLY SPECIFY ALL
 EXISTING AND ALL NEW.
 106.1.2
  
 4) NOTE: PLEASE KNOW, AS FOR EELCTRICAL
 SCOPE OF WORK, THE PLANS DO NOT NEEDS TO
 BE SIGNED,AND SEALED BY AN ARCHITECT OR
 ENGINEER, HOWEVER PLANS ARE REQUIRED TO
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS AND
 SAID DESIGN.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY REQUIRE PLANS TO
 BE DONE BY AN ARCHITECT.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By mawillia Date 2006-09-06 Time 14:34 Rev Time 0.00
Received By mawillia Date 2006-09-06 Time 14:34 Sent To  
Notes
2006-09-06 00:00:00RETURNED TO LUIS MARTINEZ

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-22 Cont ID  
Sent By mawillia Date 2006-08-22 Time 12:08 Rev Time 0.00
Received By mawillia Date 2006-08-22 Time 12:08 Sent To  
Notes
2006-08-22 00:00:00**UNSAT**
  
  
  
  
 1.) THE UPDATED PLANS/SHOP DRAWINGS TO
 BE PRESENTED WITH NO INK, PENCIL, OR ANY
 OTHER MARKINGS.
  
 2.) ALL OTHER NOTES/CONCERNS OF FIRE
 PLAN REVIEW APPEAR TO HAVE BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By mwennerg Date 2006-07-19 Time 13:26 Rev Time 0.00
Received By mwennerg Date 2006-07-19 Time 13:26 Sent To  
Notes
2006-07-19 00:00:00***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENT
 REGARDING 'EXISTING' SMOKE DETECTORS.
 PLEASE INDICATE IF THIS WILL BE NEW
 INSTALLATION.
  
 2) THE SECOND BEDROOM SEEMS TO SHOW AN
 EXISTING SPRINKLER HEAD IN THE SAME AREA
 AS A SIDEWALL TYPE THAT WOULD BE
 OBSTRUCTED BY A SOFFIT. A MINIMUM OF 18"
 SHALL BE MAINTAINED BENEATH SPRINKLER
 HEADS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 4) THE SECOND BEDROOM DOES NOT SHOW A
 SPEAKER. PLEASE EXPLAIN.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 11:33 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 11:33 Sent To  
Notes
2006-08-24 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 10:36 Sent To  
Notes
2006-08-14 00:00:00TO "BOB"#13
2006-08-03 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-21 Time   Rev Time 0.00
Received By adarroug Date 2006-07-12 Time 15:42 Sent To  
Notes
2006-07-17 00:00:00TO "BOB"#5
2006-07-12 00:00:00WAITING FOR "BOB"