Plan Review Details - Permit 06070462
Plan Review Stops For Permit 06070462
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-21 Cont ID  
Sent By alange Date 2006-08-21 Time 11:19 Rev Time 1.50
Received By alange Date 2006-08-21 Time 11:19 Sent To  
Notes
2006-08-21 00:00:00DENIED
  
  
 2.SUBMIT MIAMI-DADE PRODUCT APPROVAL
 FOR CAST-CRETE LINTELS.
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By alange Date 2006-07-21 Time 08:45 Rev Time 3.00
Received By alange Date 2006-07-21 Time 08:45 Sent To  
Notes
2006-07-21 00:00:00DENIED
  
  
 1.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 2.PRODUCT APPROVALS REQUIRED FOR
 STRAPS TIE-DOWNS AND LINTELS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 5.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PRIOR TO INSTALLATION. PER
 2004 FBC R-802.10.1
  
 6.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 7.R302.1 EXTERIOR WALLS.PROJECTIONS
 SHALL NOT EXTEND TO A POINT CLOSER THAN
 4 FEET FROM AN ADJACENT PROJECTION OR
 WALL.
 PROJECTIONS EXTENDING INTO THE 6-FOOT
 SEPARATION DISTANCE SHALL HAVE NOT LESS
 THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION
 ON THE UNDERSIDE. THE ABOVE PROVISIONS
 SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM
 THE POINT FROM WHICH THE SEPARATION
 DISTANCE HAS BEEN MEASURED RUNNING AND
 PARALLEL TO THE PROPERTY LINE.
  
 8.SHOW WINDOW BUCKS OFFERING FULL
 SUPPORT OF THE FRAME. PER FBC R 613.6.2
  
 9.CERTAINTEED ROOFING UNDERLAYMENT,
 ONLY THE WINTER GUARD HT IS PERMITTED
 UNDER METAL ROOFING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By btrobaug Date 2006-08-10 Time 10:02 Rev Time 0.75
Received By btrobaug Date 2006-08-10 Time 07:38 Sent To M
Notes
2006-08-10 00:00:00 
 PROVISO
  
 PLEASE RESUBMIT SHOWING ACTUAL
 CONDITIONS PRIOR TO CALLING ROUGH
 ELECTRICAL INSPECTION.
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW ONE
 WEEK (PER TRADE) FOR PLAN REVIEW.
 CORRECT THE FOLLOWING
  
  
 1} THE FEEDERS FROM THE METER/MAIN MUST
 INCLUDE THE EQUIPMENT GROUND REQUIRED BY
 250.110 AND SIZED PER 250.122. TO ALL
 PANELS.
  
 2} THE RISER SHOWS A DISCONNECT PER
 225.31 BUT LOCATION NOT SHOWN ON THE
 PLAN AT THE CABANA, WHERE IT IS REQUIRED
 PER 225.32.
  
 3} THE CABANA KITCHEN COUNTERTOP IS
 MISSING A RECEPTACLE PER 210.52(C)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By btrobaug Date 2006-07-13 Time 08:45 Rev Time 1.00
Received By btrobaug Date 2006-07-13 Time 06:15 Sent To Z
Notes
2006-07-13 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDERS FROM THE METER/MAIN MUST
 INCLUDE THE EQUIPMENT GROUND REQUIRED BY
 250.110 AND SIZED PER 250.122.
  
 2} THE #8 NEUTRAL FEEDING PANEL "D"
 APPEARS TOO SMALL FOR THE UNBALANCE.
 PROVIDE A CALCULATION PER 220.22.
  
  
 3} CIRCUITS 10&12, PANEL "B" HAVE AN OCP
 OF 35 AMPS ON #10 WIRE AND DO NOT COMPLY
 WITH 310.16 RE: 240.4(D).
  
 4} CIRCUITS 5&7 PANEL "D", SAME COMMENT
 AS ABOVE (NOTE #3).
  
 5} PLEASE SEE THE NUMBER AIR HANDLERS
 AND COMPRESSERS LISTED IN THE PANEL
 SCHEDULES DO NOT CORRELATE TO THE ACTUAL
 SYSTEMS.
  
 6} PLEASE SEE THE NOTE ON ALL "E" SHEETS
 REGARDING SMOKE DETECTORS, SHOULD
 REFERENCE 313.1 FBC (RESIDENTIAL), NOT
 905.2.
  
 7} PLEASE SEE THE CABANA NEEDS ADDED
 RECEPTACLES TO COMPLY WITH 210.52(A)
 SPACING REQUIREMENTS, AT THE ENTRY.
  
 THE RECEPTACLES WITHIN 6' OF THE WET BAR
 IN THE CABANA MUST BE GFI PROTECTED PER
 210.8(A)(7}.
  
 8} PLEASE SHOW THE "POOL PANEL" LISTED
 IN PANEL "D". LOCATE SAME ON PLAN AND ON
 THE RISER. ALSO PROVIDE A PANEL SCHEDULE
 FOR SAME. 408.4 NEC AND 106.3.5.4 FBC.
  
 9} PLEASE INDICATE THE FEEDER SIZES FOR
 PANEL "A".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-08-19 Cont ID  
Sent By pschmitz Date 2006-08-19 Time 12:27 Rev Time 0.00
Received By pschmitz Date 2006-08-19 Time 12:27 Sent To B
Notes
2006-08-19 00:00:00SEPERATE GAS PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 10:05 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 10:05 Sent To P
Notes
2006-07-15 00:00:00DENIED;
 1. PIPE SIZE FROM METER TO POOL HEATER
 IS NOT LARGE ENOUGH. FBC FUIL GSD TABLE
 402.4(2). FROM METER TO POOL HEATER TEE
 PIPE SIZE IS 1 1/2" THE TEE AT POOL
 HEATER SHOULD BE 1 1/2"X 1"X 1 1/4".
 2.LIST TOTAL BTU'S ON SYSTEM ON PLAN.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-09 Cont ID  
Sent By mmclean Date 2006-09-13 Time 14:52 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 09:36 Sent To E
Notes
2006-08-09 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 13:58 Sent To Z
Notes
2006-08-02 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-21 Cont ID  
Sent By alange Date 2006-07-21 Time 08:57 Rev Time 0.00
Received By alange Date 2006-07-11 Time 14:53 Sent To  
Notes
2006-07-11 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 13:52 Rev Time 0.30
Received By tgordon Date 2006-08-10 Time 13:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By tgordon Date 2006-07-14 Time 10:38 Rev Time 0.45
Received By tgordon Date 2006-07-14 Time 10:38 Sent To P
Notes
2006-07-14 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE AN ARCHITECT'S
 SEAL ON THEM THEREFORE HIS NAME,LICENSE
 NUMBER, AND OTHER PERTINENT INFORMATION
 MUST BE IN THE TITLE BLOCK, PER FAC
 61G1-16.004 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-19 Cont ID  
Sent By pschmitz Date 2006-08-19 Time 11:04 Rev Time 0.00
Received By pschmitz Date 2006-08-19 Time 11:04 Sent To B
Notes
2006-08-19 00:00:00SEPERATEGAS PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 09:22 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 09:22 Sent To B
Notes
2006-07-15 00:00:00DENIED;
 SANITARY RISER DIAGRAM;
 CABANA SHOWER NOT VENTED.
 AUTOMATIC CLOTHES WASHERS BRANCH DRAINS
 ARE REQUIRED TO BE 3" SEE SECTION 406.3.
 WHERE IS DEEP SEAL TRAP LOCATED ON PLAN?
 MASTER BATH HAS A W/C AND BIDET NOT 2
 W/C'S
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-13 Cont ID  
Sent By mmclean Date 2006-08-07 Time 10:34 Rev Time 0.00
Received By mmclean Date 2006-08-07 Time 10:34 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By mmclean Date 2006-07-14 Time 07:40 Rev Time 0.00
Received By mmclean Date 2006-07-14 Time 07:40 Sent To M
Notes
2006-07-14 00:00:00DENIED,
 1. PLEASE PROVIDE THE DIMENSION FOR THE
 PROPOSED DRIVEWAY (PLEASE SHOW THE TYPE
 OF MATERIAL FOR DRIVEWAY)
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
 2. MUST PULL A SEPERATE PERMIT FOR
 WALL/FENCE/GATE WITH UTILITY EASEMENT
 APPROVALS FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT, BELLSOUTH, FPL,
 FLORIDA PUBLIC UTILITIES, ADELPHIA.
 3. MUST PULL A SEPERATE PEMRIT FOR
 POOL/DECK/SPA.
 4. MUST PROVIDE THE DISTANCE OF THE MAIN
 STRUCTURE FROM THE CABANA (SEC
 91-304(B)3.
  
 NTOE: THE PROPOSED A/C SHALL NOT BE
 CLOSER THAN 1FT FROMSIDE PROPERTY
 LINE.
  
 NOTE: THE PROPOSED CABANA CANNOT BE USED
 FOR A SEPERATE LIVIGING SPACE.
  
 NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720