Plan Review Details - Permit 06070461
Plan Review Stops For Permit 06070461
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-16 Cont ID  
Sent By amorse Date 2006-08-16 Time 16:25 Rev Time 0.00
Received By amorse Date 2006-08-16 Time 16:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-21 Cont ID  
Sent By amorse Date 2006-07-21 Time 08:27 Rev Time 0.00
Received By amorse Date 2006-07-21 Time 08:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 18:48 Sent To PC
Notes
2006-10-25 19:06:27REDLINED DISPOSAL AND DISHWASHER RECEPT LOCATION ,
 SHOWN BEHIND DISH.
 REDLINED COUNTER SPACE AS THISDOES NOT SEEM TO MEET
 210.52C1-5

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-14 Cont ID  
Sent By dpalmer Date 2006-10-14 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2006-10-14 Time 16:39 Sent To PC
Notes
2006-10-14 17:15:28**** UNSAT**
  
 1) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW
 AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 SOME CIRCUITS FOR CODE COMPLIANCE CAN NOT BE VERIFIED
 AT THIS TIME.
 FBC ADMIN SECT 106.3.5.1.2, NEC 240.4, 408.4 310.16
 ETC
  
 2) NOTE: PLEASE SEE 210.52C1-5 FOR KITCHEN GFI RECEPTS
 REQUIRED , LOCATIONS ETC. PLEASE SEE 210.8A6 FOR ALL
 RECEPTS SERVING KITCHEN COUNTER SPACE SHALL BE GFI .
  
 3) NOTE: PLEASE CORRELATE ALL ELECTRICAL CIRCUITS ON
 PANEL SCHEDULE AND BE SURE DEVICES ARE SHOWN ON PLANS.
 DISPOSAL? WATER HEATER?
 FBC ADMIN SECT. 106.1.2
  
 4) NOTE: PLEASE VERIFY THE EXISTING RISER AS SHOWN.
 THIS REVIEWER WAS JUST ON SITE AT THIS BUIDLING FOR
 OTHER UNIT AND METER ROOM SHOWED A "TYPICAL" BREAKER
 SIZE AND FEEDERS, FOR EACH OF THE PH UNITS, HOWEVER
 THESE WERE NOT 200A MCB AND NOT 200A FEEDERS. THE
 CONDUITS WERE NOT LARGE ENOUGH FOR 200A FEEDS WHEN
 BUILT.
 ** PLEASE KNOW, IF SHOWN THIS WAY ON PLANS, THIS WILL
 BE INSPECTED AND EXPECTED TO SHOW THIS. IF NOT
 ACCURATE, THEN PLANS WILL BE REQUIRED TO BE REVISED ONE
 AGAIN. IT MAY BE OF INTEREST FOR EVERYONE INVOLVED THIS
 BE VERIFIED AT THIS TIME.
 310.16, 240.4 ETC. PLEASE SPECIFY TYPE OF CONDUCTOR.
 (ALUM/COPPER). ETC
  
 5) NOTE:: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR MIN
 VA FOR EACH OF THE SMALL APPLIANCE CIRCUITS ALONG WITH
 AREAS OF THE LIKE. PLEASE SEE ONE KITCHEN CIRCUIT BEING
 SHOWN WITH NO LOAD. PLEASE SEE DINING ROOM/AREA FOR
 EXISITING.
  
 6) NOTE: PLEASE SEE BATH GFI CIRCUIT IS BEING SHOWN
 WITH 7.2 KW ON CIRCUIT. THIS APPEARS TO BE A MISPRINT
 PERHAPS FOR GEN LTS/RECEPT LOAD WHICH SHOULD BE SHOWN
 ON PANEL LOAD CALCULATIONS.
 220.31,
  
 7) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SD' S AND
 SA'S. PLEASE VERIFY IF THESE ARE INDEED SMOKE DETECTORS
 OR ARE THEY SMOKE ALARMS?
 THIS IS ONLY NOTED, AS IF THEY ARE SD'S THEN PLEASE
 INDICATE THE "SOUNDING DEVICES".
 2002 -72.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 09:48 Sent To  
Notes
2006-08-10 00:00:00REDLINED NFPA-72 , 11.8.3 FOR SD'S
 WITHIN 20' OF COOKING APPLIANCES SHALL
 MEET CERTAIN CRITERIA

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 15:00 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 14:42 Sent To  
Notes
2006-07-18 00:00:00**** UNSAT *****
  
  
 1) NOTE: PLEASE PROVIDE COMPLETED LOAD
 CALCULATIONS WITH NEW AND EXISTING LOADS
 220.31, 220.3B4
  
 2) NOTE: PLEASE SEE THE RES CODE 2004
 R313 WHICH REQUIRES NEW OR EXISTING SD'S
 TO BE INDICATED MEETING THE CURRENT CODE
 OF NFPA-72 2002 11.5.1.1,
  
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By mwennerg Date 2006-08-24 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2006-08-24 Time 14:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By mwennerg Date 2006-07-20 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2006-07-20 Time 13:58 Sent To  
Notes
2006-07-20 00:00:00***DENIED***
  
 1) PLEASE SHOW LOCATIONS OF ALL REQUIRED
 SMOKE DETECTORS
  
 2) APPLICATION MENTIONS WORK TO BE DONE
 ON FIRE SPRINKLER SYSTEM. PLEASE
 ILLUSTRATE ON PLANS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 09:45 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 09:45 Sent To E
Notes
2006-10-24 09:45:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 13:20 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 13:20 Sent To E
Notes
2006-10-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-03 Cont ID  
Sent By adarroug Date 2006-10-03 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-10-03 Time 11:31 Sent To  
Notes
2006-10-19 16:30:2810/19/06-NO REVIEWS DONE UNDER THIS PERMIT #
2006-10-03 00:00:00WAITING FOR "BOB"-REV
 TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 15:15 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 15:15 Sent To  
Notes
2006-08-09 00:00:00TO "BOB"#16
2006-07-31 00:00:00WAITING FOR "BOB"-NEW BLDG AND PLUMB
 SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-21 Time   Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 16:38 Sent To  
Notes
2006-07-17 00:00:00TO "BOB"#3
2006-07-11 00:00:00WAITING FOR "BOB

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-12 Cont ID  
Sent By jleech Date 2006-08-12 Time 12:06 Rev Time 0.00
Received By jleech Date 2006-08-12 Time 12:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By jleech Date 2006-07-19 Time 07:18 Rev Time 0.00
Received By jleech Date 2006-07-19 Time 07:18 Sent To  
Notes
***NONE***