| Plan Review Stops For Permit 06070459 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-10-11 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-10-11 |
Time |
09:43 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-09-29 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-09-29 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | | | | | | | DENIED | | | | | | 1) NEW DRAWINGS THAT WERE SUBMITTED ARE | | | NOT SEALED BY THE DESIGN PROFESSIOAL | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-09-12 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-09-12 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-07-21 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-07-21 |
Time |
08:09 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-12-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-09 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-09 |
Time |
15:42 |
Sent To |
PC |
|
| Notes |
| 2006-12-09 16:03:51 | REV'S OK, CHANGING FEEDERS TO 200A RATED AND CHANGING | | | BREAKER IN MC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-25 |
Time |
20:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-25 |
Time |
20:22 |
Sent To |
PC |
|
| Notes |
| 2006-10-25 20:37:29 | ***UNSAT *** | | | | | | 1) NOTE: PLEASE SEE NO GFI PROTECTION SHOWN FOR NEW | | | WHIRLPOOL EQUIPMENT. 680.71. | | | | | | 2) NOTE: PLEASE KNOW ON A RECENT INSPECTION AT THE | | | BUILDING LOCATION IT WAS DISCOVERED ALL OF THE FEEDERS | | | AND MAINS FEEDING THE 200A PANELS WHICH WERE SEEN BY | | | THIS REVIEWER AND FELLOW INSPECTOR WERE INDEED 150A | | | MAINS IN MAIN ELECTRICAL ROOMS WITH FEEDERS RATED ONLY | | | AT 150A'S. | | | | | | PLEASE VERFIY AND SHOW THIS INFORMATION ON PLANS AND | | | RISER AT THIS TIME. IF THESE ARE ONLY RATED AT 150A'S, | | | PLEASE REMOVE SOME LOADS OR RE-PULL FEEDERS. SUPPLY | | | CONDUCTOR TYOE AND CONDUIT SIZE AS CONDUIT IS NOT 2". | | | 215.5, 240.4,310.16 ETC. | | | PLEASE ALSO KNOW 310.15B6 MAY NOT BE USED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-10 |
Time |
16:27 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-10-10 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-24 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-24 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2006-09-24 00:00:00 | *** UNSAT 3RD REVIEW *** | | | | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REQUEST | | | WHICH ASKED THAT THE MANUFACTURES | | | SPECS/CUT SHEETS FOR THE PROPOSED | | | TANKLESS WATER HEATER INDICATE A LISTING | | | FROM A NRTL. (UL, MET, CSA, ETL,TUV, | | | TUV-RHEILAND ETC ETC.SHEET SUBMITTED IS | | | NOT CLEAR AND NOT LISTINS ARE SHOWN. | | | 110.3, 90.7. | | | | | | ** NEW NOTE ** | | | | | | 2) NOTE: PLEASE SEE BOTH SETS OF PLANS | | | SUBMITTED ARE NOT SEALED BY THE | | | ARCHITECT OF RECORD. | | | PLEASE SEE FS 481.221 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-07 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-07 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | ** UNSAT ** | | | | | | ** PLEASE SEE PANEL SCHEDULE/LOAD CALCS | | | BEING SUBMITTED, SOME COMMENTS ARE NEW | | | DUE TO INFORMATION NOW SHOWN. | | | | | | 1) NOTE: PLEASE CORRELATE TANKLESS WATER | | | HEATERS, ON PLANS, SPECS AND LOAD | | | CALCULATIONS. | | | PLEASE SEE SPECS INDICATE EACH AT 18KW, | | | PANEL SCHEDULE SHOWS THESE AS 9KW AND | | | THE CALCUALTIONS INDICATE 12KW UNITS? | | | PLEASE BE SURE TO ADJUST THE OCP AND | | | CONDUCTORS DEPENDING ON FINAL UNIT. | | | PLEASE ALSO BE SURE SPECS SUBMITTED FOR | | | UNIT CONTAINS A LISTING FROM A NRTL. | | | (NATIONALLY RECOGNIZED TESTING | | | LABORATORY), UL, MET, TUV, CSA, ETL ETC. | | | | | | 2) NOTE: PLEASE SEE LOAD CALCUALTIONS | | | INDICATES AN ADDITIONAL LIGHTING LOAD, | | | HOWEVER THIS IS BEING ASSUMED THAT THIS | | | IS FOR THE RECESSED LTS. PLEASE SEE THE | | | # OF FIXTURE AT "X" WATTS PER FIXTURE | | | SHOULD BE NOTED OR SHOWN. | | | 220.3B4 | | | | | | 3) NOTE: PLEASE SEE PREVIOUS NOTE S, | | | DINING AREAS AND THE LIKE PER 210.52B1, | | | 210.11C1, 220.16 | | | | | | | | | **PLEASE KNOW THE SD'S WILL BE REQUIRED | | | TO BE ARC FAULT PROTECTED 210.12, ALSO | | | EXISTING RECEPTS SERVING KITCHEN | | | COUNTER-SPACE WILL ALSO BE REQUIRED TO | | | BE GFI. 210.8A6 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-18 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-18 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2006-07-18 00:00:00 | ********* UNSAT ********** | | | | | | 1) NOTE: PLEASE INDICATE ALL ROOM AND | | | AREA DESIGNATIONS ON PLANS. | | | SOME ITEMS FOR CODE COMPLIANCE CAN NOT | | | BE VERIFIED AT THIS TIME. | | | DINING? BEDRMS ETC | | | 210.52B1, 210.11C1, ETC | | | | | | 2) NOTE: PLEASE INDICATE ALL CIRCUITING | | | ON PLANS AND CORRELATE WITH PANEL | | | SCHEDULE TO BE SUBMITTED. PLEASE SEE | | | PANEL SCHEDULE/LOAD CALCS IS OK. PLEASE | | | KNOW,UNABLE TO VERIFY THE REQUIRED | | | DEDICATED CIRCUITS FOR DINING, BATHS | | | ETC? | | | 210.52B1,210.11C1,408.4 ETC | | | | | | 3) NOTE: PLEASE SUBMIT MANUFACTURES | | | SPECS/CUT SHEETS FOR THE TL WH. PLEASE | | | SEE LOADS ARE SHOWN AT 24KW, AND YET THE | | | OCP IS SHOWN AT 60A'S? PLEASE SEE MIN | | | BRANCH CIRCUIT SIZING ETC. | | | PLEASE SEE 422.30, 422.17, | | | | | | 4) NOTE: PLEASE VERIFY OCP SHOWN FOR | | | 11KW OVEN AS THE LOAD FAR EXCEEDS THE | | | RATING OF BRANCH CIRCUIT. | | | PLEASE VERIFY 240.4,310.16, ETC | | | | | | 5) NOTE: PLEASE SEE SD WILL BE REQUIRED | | | IN ALL SLEEPING RMS OR ADAPTABLE | | | SLEEPING RMS. THESE RMS CONTAIN A CLOSET | | | OR BATHRM, THEN THEY ARE CONSIDERED | | | SLEEPING RMS. | | | PLEASE SEE NFPA-72 2002 11.5.1.1,11.8.3 | | | | | | 6) NOTE: PLEASE BE SURE PLANS REFLECT | | | THE FOLLOWING CODES. | | | NFPA-70 2002, NFPA-72 2002. | | | | | | 7) NOTE: PLEASE CLARIFY THE RECEPTS NOW | | | SHOWN IN THE CLOSET. PLEASE KNOW THAT | | | RECEPTS IN SPACES WHICH CLOSE TO EASILY | | | IGNITIBLE MATERIALS SHALL NOT BE USED | | | FOR "PLUG-IN" TYPE TRANSFORMER ETC. | | | PLEASE SEE 240.24,110.26 ETC | | | THIS IS AND HAS BEEN A DIRECT FIRE | | | HAZARD IN THIS AREA. | | | | | | 8 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-12 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-12 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-20 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-20 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE SHOW LOCATIONS OF ALL SMOKE | | | DETECTORS ON DRAWINGS. | | | | | | 2) APPLICATION MENTIONS WORK TO BE DONE | | | ON FIRE SPRINKLER SYSTEM. PLEASE SHOW ON | | | PLANS. SEPARATE SHOP DRAWINGS AND PERMIT | | | WILL BE REQUIRED PRIOR TO ANY WORK ON | | | SYSTEM. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-08 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-08 |
Time |
10:36 |
Sent To |
E |
|
| Notes |
| 2006-12-08 10:36:32 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-23 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-23 |
Time |
11:20 |
Sent To |
E |
|
| Notes |
| 2006-10-23 11:20:55 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-19 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-19 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2006-09-23 00:00:00 | TO "BOB"#5 | | 2006-09-19 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | TO "BOB"#11 | | 2006-08-23 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-07-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-11 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2006-07-17 00:00:00 | TO "BOB"#3 | | 2006-07-11 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-10-11 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-10-11 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2006-10-11 09:01:40 | NO MECHANICAL WORK SHOWN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-10 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-10 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-10 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-10 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2006-10-10 08:23:26 | DENIED; | | | PLANS ARE NOT SEALED BY ARCHITECT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-11 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-09-11 |
Time |
07:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-19 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-19 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2006-07-19 00:00:00 | DENIED; | | | PLEASE SUBMIT MANUFACTURE'S | | | SPECIFICATIONS FOR WATER HEATER AND | | | WATER SOPFTENER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|