Plan Review Details - Permit 06070459
Plan Review Stops For Permit 06070459
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-11 Cont ID  
Sent By amorse Date 2006-10-11 Time 09:43 Rev Time 0.00
Received By amorse Date 2006-10-11 Time 09:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-29 Cont ID  
Sent By amorse Date 2006-09-29 Time 14:10 Rev Time 0.00
Received By amorse Date 2006-09-29 Time 14:10 Sent To  
Notes
2006-09-29 00:00:00 
  
 DENIED
  
 1) NEW DRAWINGS THAT WERE SUBMITTED ARE
 NOT SEALED BY THE DESIGN PROFESSIOAL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-12 Cont ID  
Sent By amorse Date 2006-09-12 Time 13:25 Rev Time 0.00
Received By amorse Date 2006-09-12 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-21 Cont ID  
Sent By amorse Date 2006-07-21 Time 08:09 Rev Time 0.00
Received By amorse Date 2006-07-21 Time 08:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 15:42 Sent To PC
Notes
2006-12-09 16:03:51REV'S OK, CHANGING FEEDERS TO 200A RATED AND CHANGING
 BREAKER IN MC.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-10-25 Cont ID  
Sent By dpalmer Date 2006-10-25 Time 20:37 Rev Time 0.00
Received By dpalmer Date 2006-10-25 Time 20:22 Sent To PC
Notes
2006-10-25 20:37:29***UNSAT ***
  
 1) NOTE: PLEASE SEE NO GFI PROTECTION SHOWN FOR NEW
 WHIRLPOOL EQUIPMENT. 680.71.
  
 2) NOTE: PLEASE KNOW ON A RECENT INSPECTION AT THE
 BUILDING LOCATION IT WAS DISCOVERED ALL OF THE FEEDERS
 AND MAINS FEEDING THE 200A PANELS WHICH WERE SEEN BY
 THIS REVIEWER AND FELLOW INSPECTOR WERE INDEED 150A
 MAINS IN MAIN ELECTRICAL ROOMS WITH FEEDERS RATED ONLY
 AT 150A'S.
  
 PLEASE VERFIY AND SHOW THIS INFORMATION ON PLANS AND
 RISER AT THIS TIME. IF THESE ARE ONLY RATED AT 150A'S,
 PLEASE REMOVE SOME LOADS OR RE-PULL FEEDERS. SUPPLY
 CONDUCTOR TYOE AND CONDUIT SIZE AS CONDUIT IS NOT 2".
 215.5, 240.4,310.16 ETC.
 PLEASE ALSO KNOW 310.15B6 MAY NOT BE USED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-10 Cont ID  
Sent By btrobaug Date 2006-10-10 Time 16:27 Rev Time 0.50
Received By btrobaug Date 2006-10-10 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 16:18 Sent To  
Notes
2006-09-24 00:00:00*** UNSAT 3RD REVIEW ***
  
  
 1) NOTE: PLEASE SEE PREVIOUS REQUEST
 WHICH ASKED THAT THE MANUFACTURES
 SPECS/CUT SHEETS FOR THE PROPOSED
 TANKLESS WATER HEATER INDICATE A LISTING
 FROM A NRTL. (UL, MET, CSA, ETL,TUV,
 TUV-RHEILAND ETC ETC.SHEET SUBMITTED IS
 NOT CLEAR AND NOT LISTINS ARE SHOWN.
 110.3, 90.7.
  
 ** NEW NOTE **
  
 2) NOTE: PLEASE SEE BOTH SETS OF PLANS
 SUBMITTED ARE NOT SEALED BY THE
 ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-07 Cont ID  
Sent By dpalmer Date 2006-09-07 Time 17:46 Rev Time 0.00
Received By dpalmer Date 2006-09-07 Time 17:31 Sent To  
Notes
2006-09-07 00:00:00** UNSAT **
  
 ** PLEASE SEE PANEL SCHEDULE/LOAD CALCS
 BEING SUBMITTED, SOME COMMENTS ARE NEW
 DUE TO INFORMATION NOW SHOWN.
  
 1) NOTE: PLEASE CORRELATE TANKLESS WATER
 HEATERS, ON PLANS, SPECS AND LOAD
 CALCULATIONS.
 PLEASE SEE SPECS INDICATE EACH AT 18KW,
 PANEL SCHEDULE SHOWS THESE AS 9KW AND
 THE CALCUALTIONS INDICATE 12KW UNITS?
 PLEASE BE SURE TO ADJUST THE OCP AND
 CONDUCTORS DEPENDING ON FINAL UNIT.
 PLEASE ALSO BE SURE SPECS SUBMITTED FOR
 UNIT CONTAINS A LISTING FROM A NRTL.
 (NATIONALLY RECOGNIZED TESTING
 LABORATORY), UL, MET, TUV, CSA, ETL ETC.
  
 2) NOTE: PLEASE SEE LOAD CALCUALTIONS
 INDICATES AN ADDITIONAL LIGHTING LOAD,
 HOWEVER THIS IS BEING ASSUMED THAT THIS
 IS FOR THE RECESSED LTS. PLEASE SEE THE
 # OF FIXTURE AT "X" WATTS PER FIXTURE
 SHOULD BE NOTED OR SHOWN.
 220.3B4
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE S,
 DINING AREAS AND THE LIKE PER 210.52B1,
 210.11C1, 220.16
  
  
 **PLEASE KNOW THE SD'S WILL BE REQUIRED
 TO BE ARC FAULT PROTECTED 210.12, ALSO
 EXISTING RECEPTS SERVING KITCHEN
 COUNTER-SPACE WILL ALSO BE REQUIRED TO
 BE GFI. 210.8A6
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 12:37 Sent To  
Notes
2006-07-18 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE INDICATE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE VERIFIED AT THIS TIME.
 DINING? BEDRMS ETC
 210.52B1, 210.11C1, ETC
  
 2) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH PANEL
 SCHEDULE TO BE SUBMITTED. PLEASE SEE
 PANEL SCHEDULE/LOAD CALCS IS OK. PLEASE
 KNOW,UNABLE TO VERIFY THE REQUIRED
 DEDICATED CIRCUITS FOR DINING, BATHS
 ETC?
 210.52B1,210.11C1,408.4 ETC
  
 3) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS FOR THE TL WH. PLEASE
 SEE LOADS ARE SHOWN AT 24KW, AND YET THE
 OCP IS SHOWN AT 60A'S? PLEASE SEE MIN
 BRANCH CIRCUIT SIZING ETC.
 PLEASE SEE 422.30, 422.17,
  
 4) NOTE: PLEASE VERIFY OCP SHOWN FOR
 11KW OVEN AS THE LOAD FAR EXCEEDS THE
 RATING OF BRANCH CIRCUIT.
 PLEASE VERIFY 240.4,310.16, ETC
  
 5) NOTE: PLEASE SEE SD WILL BE REQUIRED
 IN ALL SLEEPING RMS OR ADAPTABLE
 SLEEPING RMS. THESE RMS CONTAIN A CLOSET
 OR BATHRM, THEN THEY ARE CONSIDERED
 SLEEPING RMS.
 PLEASE SEE NFPA-72 2002 11.5.1.1,11.8.3
  
 6) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES.
 NFPA-70 2002, NFPA-72 2002.
  
 7) NOTE: PLEASE CLARIFY THE RECEPTS NOW
 SHOWN IN THE CLOSET. PLEASE KNOW THAT
 RECEPTS IN SPACES WHICH CLOSE TO EASILY
 IGNITIBLE MATERIALS SHALL NOT BE USED
 FOR "PLUG-IN" TYPE TRANSFORMER ETC.
 PLEASE SEE 240.24,110.26 ETC
 THIS IS AND HAS BEEN A DIRECT FIRE
 HAZARD IN THIS AREA.
  
 8 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-12 Cont ID  
Sent By mwennerg Date 2006-09-12 Time 16:07 Rev Time 0.00
Received By mwennerg Date 2006-09-12 Time 16:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By mwennerg Date 2006-07-20 Time 13:41 Rev Time 0.00
Received By mwennerg Date 2006-07-20 Time 13:41 Sent To  
Notes
2006-07-20 00:00:00***DENIED***
  
 1) PLEASE SHOW LOCATIONS OF ALL SMOKE
 DETECTORS ON DRAWINGS.
  
 2) APPLICATION MENTIONS WORK TO BE DONE
 ON FIRE SPRINKLER SYSTEM. PLEASE SHOW ON
 PLANS. SEPARATE SHOP DRAWINGS AND PERMIT
 WILL BE REQUIRED PRIOR TO ANY WORK ON
 SYSTEM.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-08 Cont ID  
Sent By adarroug Date 2006-12-08 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-12-08 Time 10:36 Sent To E
Notes
2006-12-08 10:36:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 11:20 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 11:20 Sent To E
Notes
2006-10-23 11:20:55TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 14:00 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 14:00 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#5
2006-09-19 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 15:34 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 15:33 Sent To  
Notes
2006-09-07 00:00:00TO "BOB"#11
2006-08-23 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-21 Time   Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 16:40 Sent To  
Notes
2006-07-17 00:00:00TO "BOB"#3
2006-07-11 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-10-11 Cont ID  
Sent By lmartine Date 2006-10-11 Time 09:00 Rev Time 0.00
Received By lmartine Date 2006-10-11 Time 09:00 Sent To  
Notes
2006-10-11 09:01:40NO MECHANICAL WORK SHOWN

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-10 Cont ID  
Sent By jleech Date 2006-10-10 Time 13:58 Rev Time 0.00
Received By jleech Date 2006-10-10 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-10 Cont ID  
Sent By jleech Date 2006-10-10 Time 08:19 Rev Time 0.00
Received By jleech Date 2006-10-10 Time 08:19 Sent To  
Notes
2006-10-10 08:23:26DENIED;
 PLANS ARE NOT SEALED BY ARCHITECT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-11 Cont ID  
Sent By jleech Date 2006-09-11 Time 07:42 Rev Time 0.00
Received By jleech Date 2006-09-11 Time 07:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By jleech Date 2006-07-19 Time 07:03 Rev Time 0.00
Received By jleech Date 2006-07-19 Time 07:03 Sent To  
Notes
2006-07-19 00:00:00DENIED;
 PLEASE SUBMIT MANUFACTURE'S
 SPECIFICATIONS FOR WATER HEATER AND
 WATER SOPFTENER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695