Plan Review Details - Permit 06070451
| Plan Review Stops For Permit 06070451 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
P |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-04-23 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-04-23 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2007-04-23 14:48:04 | THE REVISED PLANS HAD BEEN CORRECTED WITH THE CORRECT | | | ADDRESS ,2029 OKEECHOBEE BLVD ,TO BE USED FOR BAY 2 ( | | | STAPLES) | | | | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-10-19 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-10-19 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2006-10-19 08:45:11 | BASED ON THE CONVERSATION WITH THE ENG FIRM THE | | | FOLLOWING ITEMS WERE RECEIVED : SITE PLANS, DEMO PLANS | | | AND THE SURVEY .BASED ON THESE ITEMS ,THE SITE ADDRESS | | | TO USE FOR THIS PERMIT IS 2029 OKEECHOBEE BLVD. | | | PLEASE APPLY TO THE REVISED SITE PLANS. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-24 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-24 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2006-08-24 00:00:00 | NOT CLEAR IF BAY # 1 BELONGS TO THE | | | THEATER AND BAY # 2I S STAPLES . | | | IS BAY # 3 INLCUDED IN THE RENOVATION? | | | THE APPLICATION AND SITE PLAN MUST BE | | | READ THE CORRECT ADDRESS FOR EACH BAY. | | | THE ADDRESS 2015 OKEECHOBEE BLVD IS USED | | | FOR THE ENTIRE PLAZA , OKEE SQUARE , BUT | | | FOR EACH INDIVIDUAL BAY THE CORRECT | | | ADDRESS MUST BE USED AND THE PERMITS | | | WILL BE ISSUED BASED ON THESE ADDRESSES. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-10 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-10 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2006-08-21 00:00:00 | ADDRESS ON THE APPLICATION 2035 | | | OKEECHOBEE BLVD BELONGS TO ROOMS RO GO | | | KIDS , PLS CORRECT ADDR | | 2006-08-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06070445 | | | ADD: 2015 OKEECHOBEE BLVD. | | | CONT: BOCA DEVEL. & CONST. | | | TEL: (561)391-6227 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | EX FBC CODE= 2004 EXISTING FLORIDA | | | BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) ARCHITECT STEVEN L. COHEN AR0006819 | | | IS WORKING WITH A DELINGUENT LICENSE, | | | EXPIRED 02/28/05. | | | WWW.MYFLORIDA.COM/LICENSING | | | | | | 4) PLANS ARE NOT SIGNED NOR SEALED | | | ARCHITECTURALS OR MEP PLANS. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 5) NOTE: A-1 PLANS INDICATE EXISTING | | | PASSAGEWAY, TO BE COMPLETED UNDER THE | | | SHELL PERMIT. | | | | | | 6) EX FBC 708.1 ALTERATIONS SUBJECT TO | | | THIS CHAPTER SHALL COMPLY WITH THE | | | REQUIREMENTS OF CHAPTER 13 OF THE FBC | | | BUILDING. | | | | | | 7) EX FBC 706.1 A BUILDING FACILITY, OR | | | ELEMENT THAT IS ALTERED SHALL COMPLY | | | WITH CHAPTER 11 OF THE FBC, BUILDING. | | | SHEET A-2 DOORS 5/106 & 6/107 TO COMPLY | | | WITH: 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 8) A-2 AND A-5 BOTH INDICATE SOME TYPE | | | OF SECURITY GRILL, PROVIDE ADDITIONAL | | | INFORMATION, 106.1.2. | | | | | | 9) A-2 AND A-5 BOTH INTERIOR AUTO DOORS | | | PROVIDE NOTICE OF ACCEPTANCE. | | | | | | 10) A7 DETAIL 16 DOESN'T INDICATE | | | TERMITE TREATMENT: | | | 1816.1 TERMITE PROTECTION. | | | TERMITE PROTECTION SHALL BE PROVIDED BY | | | REGISTERED TERMITICIDES, INCLUDING SOIL | | | APPLIED PESTICIDES, BAITING SYSTEMS, AND | | | PESTICIDES APPLIED TO WOOD, OR OTHER | | | APPROVED METHODS OF TERMITE PROTECTION | | | LABELED FOR USE AS A PREVENTATIVE | | | TREATMENT TO NEW CONSTRUCTION. SEE | | | SECTION 202 , REGISTERED TERMITICIDE. | | | UPON COMPLETION OF THE APPLICATION OF | | | THE TERMITE PROTECTIVE TREATMENT, A | | | CERTIFICATE OF COMPLIANCE SHALL BE | | | ISSUED TO THE BUILDING DEPARTMENT BY THE | | | LICENSED PEST CONTROL COMPANY THAT | | | CONTAINS THE FOLLOWING STATEMENT: ?THE | | | BUILDING HAS RECEIVED A COMPLETE | | | TREATMENT FOR THE PREVENTION OF | | | SUBTERRANEAN TERMITES. TREATMENT IS IN | | | ACCORDANCE WITH RULES AND LAWS | | | ESTABLISHED BY THE FLORIDA DEPARTMENT OF | | | AGRICULTURE AND CONSUMER SERVICES.? | | | | | | 11) A-3 NOTES 3,4 & 5 ALL INDICATE | | | UNPAINTED PLYWOOD TO VARIOUS HEIGHTS. | | | 603.1 ALLOWABLE MATERIALS. | | | COMBUSTIBLE MATERIALS SHALL BE PERMITTED | | | IN BUILDINGS OF TYPE I OR II | | | CONSTRUCTION IN THE FOLLOWING | | | APPLICATIONS AND IN ACCORDANCE WITH | | | SECTIONS 603.1.1 THROUGH 603.1.3 : | | | 1.FIRE-RETARDANT-TREATED WOOD SHALL | | | BE PERMITTED IN: | | | 1.1.NONBEARING PARTITIONS WHERE THE | | | REQUIRED FIRE-RESISTANCE RATING IS 2 | | | HOURS OR LESS. | | | | | | 12) PROVIDE ADDITIONAL INFORMATION HOW | | | TO COMPLY WITH:1210.2 WALLS. | | | WALLS WITHIN 2 FEET (610 MM) OF URINALS | | | AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT | | | OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND | | | EXCEPT FOR STRUCTURAL ELEMENTS, THE | | | MATERIALS USED IN SUCH WALLS SHALL BE OF | | | A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | | MOISTURE. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | 2006-08-10 00:00:00 | PROJECT UNDER REVIEW.FIELD VERIFICATION | | | IS NEEDED, |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-13 |
Time |
15:19 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2007-06-13 |
Time |
15:19 |
Sent To |
PC |
|
| Notes |
| 2007-06-13 15:22:34 | BUILDING PLAN REVIEW | | | PERMIT: 06070445 | | | ADD: 2015 OKEECHOBEE BLVD. | | | CONT: BOCA DEVEL. & CONST. | | | TEL: (561)391-6227 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | EX FBC CODE= 2004 EXISTING FLORIDA | | | BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3)COMMENT# 7 FROM THE FIRSTREVIEW DEALS | | | WITH THE AUTOMATIC SLIDING DOORS INTERIOR DOORS AT THE | | | VESTIBULE 1/100 AND 2/101,ADDITIONAL INFORMATION | | | AS TOO HOW ONE WILL GAIN EGRESS FROM THE STORE IN THE | | | EVENT OF LOSS OF POWER.PLEASE PROVIDE PROUCT APPROVAL | | | FOR OTHER DOCUMENTATION PROVIDING | | | COMPLIANCE WITH: | | | 1008.1.3.3 HORIZONTAL SLIDING DOORS. | | | IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING | | | DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS | | | IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 | | | SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1. | | | THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE | | | OF BEING OPERATED MANUALLY IN THE EVENT OF POWER | | | FAILURE. | | | 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD | | | FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3. | | | THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT | | | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND | | | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE | | | MINIMUM REQUIRED WIDTH. | | | 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO | | | EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS | | | (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT | | | TO THE OPERATING DEVICE. | | | 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE | | | APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED, | | | SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE | | | DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA | | | 80 AND SHALL COMPLY WITH SECTION 715 . | | | 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED | | | STANDBY POWER SUPPLY. | | | 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE | | | ELECTRICALLY SUPERVISED. | | | 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED | | | WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE | | | OPERATING DEVICE. | | | 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES, | | | HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS | | | CORRIDORS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-01-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-01-05 |
Time |
15:03 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2007-01-05 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2007-01-05 14:52:54 | BUILDING PLAN REVIEW | | | PERMIT: 06070445 | | | ADD: 2015 OKEECHOBEE BLVD. | | | CONT: BOCA DEVEL. & CONST. | | | TEL: (561)391-6227 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | EX FBC CODE= 2004 EXISTING FLORIDA | | | BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) COMMENT #5 FROM THE FIRST REVIEW DEALS | | | WITH THE MINIMUM REQUIREMENTS OF CHAPTER | | | 13 ENERGY CODE REQUIREMENTS | | | PLEASE SEE ELECTRICAL STATEMENTS. | | | | | | 4 COMMEENT# 7 FROM THE PREVIOUS EVIEW DEALS | | | WITH THE AUTOMATIC SLIDING DOORS,ADDITIONAL | | | INFORMATION | | | AS TOO HOW ONE WILL GAIN EGRESS FROM THE STORE IN THE | | | EVENT OF LOSS OF POWER. | | | PLEASE PROVIDE PROUCT APPROVAL FOR OTHER DOCUMENTATION | | | PROVIDING | | | COMPLIANCE WITH: | | | | | | 1008.1.3.3 HORIZONTAL SLIDING DOORS. | | | | | | IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING | | | DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS | | | IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 | | | SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1. | | | THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE | | | OF BEING OPERATED MANUALLY IN THE EVENT OF POWER | | | FAILURE. | | | 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD | | | FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3. | | | THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT | | | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND | | | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE | | | MINIMUM REQUIRED WIDTH. | | | 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO | | | EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS | | | (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT | | | TO THE OPERATING DEVICE. | | | 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE | | | APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED, | | | SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE | | | DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA | | | 80 AND SHALL COMPLY WITH SECTION 715 . | | | 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED | | | STANDBY POWER SUPPLY. | | | 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE | | | ELECTRICALLY SUPERVISED. | | | 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED | | | WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE | | | OPERATING DEVICE. | | | 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES, | | | HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS | | | CORRIDORS. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-08-15 |
Time |
11:11 |
Rev Time |
8.88 |
| Received By |
jwitmer |
Date |
2006-08-15 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2006-08-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06070445 | | | ADD: 2015 OKEECHOBEE BLVD. | | | CONT: BOCA DEVEL. & CONST. | | | TEL: (561)391-6227 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | EX FBC CODE= 2004 EXISTING FLORIDA | | | BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) ARCHITECT STEVEN L. COHEN AR0006819 | | | IS WORKING WITH A DELINGUENT LICENSE, | | | EXPIRED 02/28/05. | | | WWW.MYFLORIDA.COM/LICENSING | | | | | | 4) THE ARCHITECTURAL AS WELL AS THE MEP | | | PLANS ARE NOT SIGNED NOR SEALED. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 5) EX FBC 708.1 MINIMUM REQUIREMENTS. | | | ALTERATIONS SUBJECT TOTHIS CHAPTER SHALL | | | COMPLY WITH THE REQUIREMENTS OF CHAPTER | | | 13 OF THE FBC, BUILDING. | | | | | | 6) EX FBC 706.1 A BUILDING, FACILITY OR | | | ELEMENT THAT IS ALTERED SHALL COMPLY | | | WITH CHAPTER 11 OF THE FBC BUILDING. | | | SHEET A2 DOOR5/106 & 6/107 DO NOT MEET | | | THE REQUIREMENTS OF 11-4.13.6 | | | MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING | | | CLEARANCES AT DOORS THAT ARE | | | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE | | | AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARANCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 7) PROVIDE ADDITIONAL INFORMATION FOR | | | A) SECURITY GRILLE LOCATED AT VESTIBULE | | | B) VESTIBULE AUTO SLIDING DOORS | | | LOCATED ON SHEET A2 & A5 | | | 106.1.2* ADDITIONAL INFO. | | | | | | 8) SHEET A7 DETAIL# 16 FLOOR SLAB, | | | PROIDE INFORMATION ON TERMITE TRATMENT. | | | 1816.1 TERMITE PROTECTION. | | | TERMITE PROTECTION SHALL BE PROVIDED BY | | | REGISTERED TERMITICIDES, INCLUDING SOIL | | | APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES | | | APPLIED TO WOOD, OR OTHER | | | APPROVED METHODS OF TERMITE PROTECTION | | | LABELED FOR USE AS A PREVENTATIVE | | | TREATMENT TO NEW CONSTRUCTION. SEE | | | SECTION 202 , REGISTERED TERMITICIDE. | | | UPON COMPLETION OF THE APPLICATION OF | | | THE TERMITE PROTECTIVE TREATMENT, A | | | CERTIFICATE OF COMPLIANCE SHALL BE | | | ISSUED TO THE BUILDING DEPARTMENT BY THE | | | LICENSED PEST CONTROL COMPANY THAT | | | CONTAINS THE FOLLOWING STATEMENT: ?THE | | | BUILDING HAS RECEIVED A COMPLETE | | | TREATMENT FOR THE PREVENTION OF | | | SUBTERRANEAN TERMITES. TREATMENT IS IN | | | ACCORDANCE WITH RULES AND LAWS | | | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE | | | AND CONSUMER SERVICES.? | | | | | | 9) SHEET A-3 NOTES 3-5 INDICATE THAT | | | PLYWOOD TO BE APPLIED TO WALL ROOM | | | FINISH NOTES. IS THIS A WALL FINISH OR | | | INCASED IN THE WALL? | | | 603.1 ALLOWABLE MATERIALS. | | | COMBUSTIBLE MATERIALS SHALL BE PERMITTED | | | IN BUILDINGS OF TYPE I OR II | | | CONSTRUCTION IN THE FOLLOWING | | | APPLICATIONS AND IN ACCORDANCE WITH | | | SECTIONS 603.1.1 THROUGH 603.1.3 : | | | 1.FIRE-RETARDANT-TREATED WOOD SHALL | | | BE PERMITTED IN: | | | 1.1.NONBEARING PARTITIONS WHERE THE | | | REQUIRED FIRE-RESISTANCE RATING IS 2 | | | HOURS OR LESS. | | | 1.2.NONBEARING EXTERIOR WALLS WHERE | | | NO FIRE RATING IS REQUIRED. | | | TABLE 803.5 MERCANTILE OCCUPANCY | | | SPRINKLERED FLAME SPREAD INDEX 76-200 | | | SMOKE DEVELOPMENT 0-450. IF THE PLYWOOD | | | IS TO BE A FINISHED WALL THEN PROVIDE | | | THE FLAME SPREAD AND SMOKE DEVELOPMEENT. | | | | | | 10) A7 RESTROOMS SHOW COMPLIANCE WITH | | | RESTROOM NONABSORBENT WALLS.PROVIDE | | | MANUFACTURER INFORMATION.1210.2 WALLS. | | | WALLS WITHIN 2 FEET (610 MM) OF URINALS | | | AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT | | | OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND | | | EXCEPT FOR STRUCTURAL ELEMENTS, THE | | | MATERIALS USED IN SUCH WALLS SHALL BE OF | | | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-04-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-22 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-22 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2007-04-22 13:28:04 | | | | ******* UNSAT 3RD REVIEW ****** | | | | | | ** PLEASE SEE THAT THERE ARE STILL MANY ITEMS FROM | | | PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN ADDRESSED FOR | | | CODE COMPLIANCE. | | | | | | ** PLEASE SEE THE RESPONSE LETTER FROM THE DESIGNER | | | ONLY RESPONDED TO NOTES 1-8 AND NEW NOTES FROM LAST | | | REVIEW WERE NOT NOTED AND LETTER DID NOT CONTAIN ANY | | | RESPONSE??A RESPONSE LETTER IS NOT REQUIRED HOWEVER | | | WILL SOMETIMES HELP TO EXPLAIN ITEMS OR EXPEDITE THE | | | REVIEW PROCESS. | | | | | | | | | 1) NOTE:PLEASE SEE THE NOTE FOR THE VALUE FOR | | | COMPLETE SCOPE OF WORK STILL REMAINS. RESPONSE FROM | | | DESIGNER MENTIONS FOR CONTRACTOR TO ADDRESS HOWEVER NO | | | CHANGES TO APPLIED VALUE HAS BEEN DONE. PLEASE KNOW | | | THAT A VALUE WILL BE ASSESSED BY THIS OFFICE IF AN | | | APPROPRIATE VALUE IS NOT INDICATED. | | | AS STATED ON PREVIOUS REVIEW THE VALUE SHALL INCLUDE | | | ALL LABOR AND MATERIALS, INCLUDING ALL EQUIPMENT, A/C | | | EQUIPMENT, ELECTRICAL EQUIPMENT, LIGHTING FIXTURES ETC. | | | PLEASE KNOW A VALUE WILL BE ASSESSED USING THE FBC | | | TABLES FOR INTERIOR BUILD OUT OF THE SQ FT AND WILL BE | | | SUBSTANTIALLY INCREASED IF AN APPROPRIATE VALUE IS NOT | | | APPLIED. PLEASE SEE FS 553.79, 553.792, AND FS 489. | | | ** THE VALUE OF THE ELECTRICAL EQUIPMENT ALONE IS | | | HIGHER THAN THE APPLIED VALUE FOR THE COMPLETE SCOPE OF | | | WORK AS APPLIED. | | | *FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 2) NOTE:PLEASE COORDINATE THE ELECTRICAL SERVICE ON | | | THE BUILD OUT PLANS AS WELL AS THE ELECTRICAL PLANS FOR | | | THE SHELL PERMITTED PLANS. | | | PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT | | | CORRELATE. | | | | | | A) PLEASE SEE THE MAIN SWITCH IN TENANT SPACE | | | ELECTRICAL ROOM IS STILL BEING SHOWN AS 600AMP WITH | | | 400AMP OVER CURRENT PROTECTION YET THE RISER AND OTHER | | | PLANS INDICATE THIS DISCONNECT AS BEING 600AMP WITH | | | 600AMP OVER CURRENT PROTECTION. NOTED ON BOTH PREVIOUS | | | REVIEWS, YET PLANS STILL SHOW THIS? | | | | | | B) PLEASE THE FEEDERS ARE STILL SHOWN AS OVER HEAD TO | | | THE TENANT ELECTRICAL ROOM AND WELL AS BEING NOTED AS | | | UNDERGROUND ON SHELL PLANS AND THESE PLANS. | | | | | | C) PLEASE SEE THE FEEDER CONDUITS ARE SHOWN AS 3INCH ON | | | SOME SHEETS AND 4INCH ON OTHERS AND SHELL PLANS? | | | | | | D) PLEASE SEE THE FEEDERS NOW FROM THE MAIN ELECTRICAL | | | ROOM HAVE BEEN CHANGED FROM THE PREVIOUS 600MCM DOWN TO | | | 350MCM YET THE VOLTAGE DROP CALCULATIONS STILL INDICATE | | | 600MCM. PLEASE SEE SHELL PLANS. | | | 13-413.1ABC.1 AS NOTED ON PREVIOUS REVIEW FOR VOLTAGE | | | DROP) | | | | | | E) PLEASE SEE THE ONE-LINE DIAGRAM ON THE TENANT BUILD | | | OUT PLANS SHALL INDICATE THE OCP AND MAIN WHICH IS | | | LOCATED IN THE MAIN SWITCH BOARD ON THE SHELL PLANS. | | | 230.70, 230.71, 230.72. | | | | | | ** PLEASE COORDINATE ALL ELECTRICAL EQUIPMENT ON BOTH | | | SETS OF PLANS UNDER EACH PERMIT AND ADJUST FOR THE CODE | | | COMPLIANCE COMMENTS. | | | | | | 3) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS | | | FOR CHAPTER 13 COMPLIANCE. | | | PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES. | | | PLEASE SEE MISSING SCHEDULING OF SYSTEM. | | | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE | | | NEW LIGHTING CONTROL PANEL. | | | 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE | | | VERIFIED AS SHOWN. | | | SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE | | | LISTING FROM A NRTL(NATION RECOGNIZED TESTING | | | LABORATORY). | | | PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND | | | OCCUPANCY DEVICES. | | | PLEASE SEE MANY ROOMS WHICH STILL ONLY INDICATE A *S* | | | SWITCH FOR CONTROL OF LIGHTING. PLEASE SEE | | | 13-415.1.ABC.1.2 FOR SPACE CONTROL. | | | PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS | | | BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL | | | BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR | | | SUBMITTED BACK FOR REVIEW. | | | PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING | | | WITH MANUAL CONTROL FOR LIGHTING WHICH IS NOT POSSIBLE | | | WHEN AN AUTOMATED SYSTEM IS BEING INSTALLED AND | | | REQUIRED. | | | PLEASE CORRELATE THE FIXTURES ON PLANS WITH THAT OF THE | | | FIXTURES ON ENERGY CALCULATIONS FOR THE TYPE, WATTAGE | | | AND THE NUMBER OF FIXTURES ON PLANS AND IN | | | CALCULATIONS. | | | ** PLEASE SEE THAT THE EXACT SAME ENERGY CALCULATIONS | | | WERE SUBMITTED BACK. | | | PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW, | | | THERE MAY BE SOME FUTURE COMMENTS. | | | | | | PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A | | | WORST CASE SCENARIO. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE | | | 13-415.1.AB.1, | | | 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1 | | | PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC. | | | | | | | | | 4) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF | | | CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL | | | INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL | | | DEVICES. | | | PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES | | | SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE | | | MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2, | | | .3(4). | | | THIS IS REQUIRED FOR BASE DESIGN AND LOCATIONS FOR ADA | | | COMPLIANCE ON BASE BUILDINGS AND PLANS. | | | THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS | | | EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND | | | PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE | | | BUILDING. | | | FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2) | | | | | | 5) NOTE: PLEASE CORRELATE RISER AND PANELS. | | | PLEASE SEE THE CONDUCTORS FROM THE TRANSFORMER TO PANEL | | | P2 WAS CORRECTED TO MEET THE MINIMUM AMPERAGE REQUIRED | | | PER 240.21C6, 310.16, 240.4, HOWEVER THE | | | CONDUCTORS/FEEDERS LOCATED FROM P2 TO P3 HAVE NOT BEEN | | | CORRECTED. | | | PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT | | | SIZES MAIN CIRCUIT BREAKERS, PLEASE CORRELATE AND | | | ADJUST. | | | RISER STILL SHOWS 150A MCB AND PANEL P1 STILL SHOWS A | | | 100A MCB. | | | PLEASE SEE THE RISER SHOWS 150AMP RATED CONDUCTORS FROM | | | THE MDP TO TRANSFORMER ON A 175AMP RATED BREAKER | | | | | | 6) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON | | | EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE | | | THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP | | | EXCEEDS THE RATING OF THE 112KVA RATING. THIS IS THE | | | SAME COMMENT. PLEASE SEE THE LOAD SHOWN ON THE | | | MDP.(120,908VA) | | | PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED. | | | 230,240, 408, ETC. | | | FBC 106.1.2 ADMIN SECTION. | | | | | | 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE NOTICE | | | TO FS 553.80(2)(B) WITH RESPECT TO REPEAT CODE | | | COMPLIANT COMMENTS. | | | PLEASE SEE A FEE HAS NOW BEEN ASSESSED IN THE AMOUNT OF | | | $3,300 WHICH IS REQUIRED BEFORE PLANS MAY BE | | | RE-SUBMITTED FOR REVIEW. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-23 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-23 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2006-12-23 18:40:45 | *** UNSAT 2ND REVIEW *** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL | | | NEED TO BE ADDRESSED ALONG WITH SOME NEW NOTES. PLEASE | | | SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS | | | REVIEW AND IN THE EXACT NUMERICAL ORDER WITH NEW NOTES | | | ADDED TO THE BOTTOM OF THE FIRST REVIEW NOTES. | | | | | | ** PLEASE SEE NOTES ARE NOTED WITH A NO, OK,OR SOME | | | MAY CONTAIN A NO/OK, WHICH WOULD INDICATE PART OF THE | | | COMMENT MAY HAVE BEEN ADDRESSED HOWEVER NOT FULLY OR | | | THERE STILL MAY BE SOME UNCERTAINLY OF RESPONSE/PLANS. | | | | | | 1) NOTE:NO, PLEASE SEE THE VALUE WAS INCREASED ON | | | PERMIT APPLICATION BY $5K. AS STATED ON PREVIOUS REVIEW | | | THE VALUE SHALL INCLUDE ALL LABOR AND MATERIALS, | | | INCLUDING ALL EQUIPMENT, A/C EQUIPMENT, ELECTRICAL | | | EQUIPMENT, LIGHTING FIXTURES ETC. PLEASE KNOW A VALUE | | | WILL BE ASSESSED USING THE FBC TABLES FOR INTERIOR | | | BUILD OUT OF THE SQ FT AND WILL BE SUBSTANTIALLY | | | INCREASED IF AN APPROPRIATE VALUE IS NOT APPLIED. | | | PLEASE SEE FS 553.79, 553.792, AND FS 489. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE VALUE FOR PROPOSED SCOPE OF WORK IS WAY | | | LOW. PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK ON | | | PLANS NEEDS TO BE ADJUSTED. PLEASE SEE VALUE BE BASED | | | ON ALL LABOR AND MATERIALS WHETHER OR NOT ANY | | | EQUIPMENT, LIGHTING ETC IS OWNER SUPPLIED. | | | FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY | | | OF WEST PALM BEACH. | | | ** PLEASE ALSO PROVIDE THE DESCRIPTION ON APPLICATION | | | FOR ACTUAL SCOPE OF WORK BEING PERFORMED AS THE DETAIL | | | GIVEN SEEMS TO BE ABOUT THE SAME AS THE SHELL BLDG | | | APPLICATION. | | | ** NOTE FOR CONTRACTOR AND DOES NOT APPLY TO PLANS. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: NO/OK. PLEASE SEE THE CODES WERE ADDED TO | | | PLANS; HOWEVER THERE ARE STILL SEVERAL SECTIONS OF THE | | | CODES BEING NOTED ON PLANS WHICH ARE OUT OF THE 1996 | | | NFPA-70. | | | PLEASE KNOW WHEN SPECIFICALLY NOTED CODE SECTIONS ON | | | PLANS, AND THEN THEY MUST REFLECT AND CORRELATE WITH | | | THE CODE WHICH THEY ARE UNDER AND CORRELATE. PLEASE SEE | | | MISSING REFERENCE TO NFPA-101 2003 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING CODES AT | | | A MINIMUM FOR ELECTRICAL REVIEW. | | | 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 | | | NFPA-101 AND THE 2004 FBC. | | | PLEASE SEE THERE ARE CODE ARTICLES REFERENCED ON PLANS | | | WHICH ARE FROM THE | | | 1996 NEC> | | | PLEASE SEE REDLINED SET. | | | | | | 4) NOTE:NO, PLEASE KNOW AS OF THIS REVIEW THE PLANS | | | FOR THE MAIN BUILDING/SHELL HAS NOT BEEN IN FOR REVIEW. | | | PLEASE SEE PREVIOUS NOTES UNDER THEIR PERMIT. PLEASE | | | SEE PLANS STILL DO NOT CORRELATE AND THE SERVICE AS | | | SHOWN IS NOT PERMITTED. 230.2. | | | PLEASE KNOW IN EITHER CASE, PLANS INDICATE UNDERGROUND | | | AND OVERHEAD, 400A AND 600A, PLEASE SEE 230.70 AS NO | | | MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED | | | INSIDE THE BUILDING. (230.6) PLEASE ALSO SEE NEW NOTES | | | FOR SERVICE ITEMS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THIS PLAN AND RISER IS SHOWING A NEW AND | | | SEPARATE ELECTRICAL SERVICE WHICH DOES NOT CORRELATE | | | WITH THE SHELL BUILDING PLANS. PLEASE REVISE RISER TO | | | INCLUDE THE MAIN FEED FROM THE MAIN ELECTRICAL ROOM. | | | PLEASE ALSO SEE ELECTRICAL PLANS SHOW 400A MAIN AND | | | RISER SHOWS 600A. | | | THIS IS ONE BUILDING AND THE SEPARATION PROVIDED IN THE | | | ARCHITECTURAL AND STRUCTURAL PLANS DO NOT SEEM TO LEND | | | TO THE DEFINITION OF A "BUILDING" WHICH WOULD CONTAIN A | | | "FIRE WALL". PLEASE SEE DEFINITIONS OF "FIRE WALL" 4HR | | | RATED AND ABLE TO COLLAPSE ON BOTH SIDES WITHOUT | | | AFFECTING THE STRUCTURAL INTEGRITY OF THE OTHER | | | STRUCTURE. | | | PLEASE SEE 230.2, AND GRANTING OF AN ADDITIONAL SERVICE | | | AT THIS TIME IS NOT GRANTED. | | | | | | 5) NOTE: NO/OK, PLEASE SEE THE NOTE WAS ADDED TO THE | | | LOWER NOTE WHICH APPEARS TO BE 15A, YET SEE NOTE #1 IS | | | STILL NOTED AND SHOWN AS BEFORE. PLEASE ADJUST THIS | | | NOTE #1 WITH THE NEW NOTE ADDED TO 15A. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE PLACE NOTE ON PLANS WITH NOTE #1 AS NOTED FOR | | | PANEL SCHEDULES AND PROPOSED LOCK OFF DEVICES ON | | | BRKRS. | | | PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES MUST BE AN | | | INTEGRAL PART OF THE BREAKER AND NOT CAPABLE OF BEING | | | REMOVED WITHOUT THE BREAKER BEING REMOVED. | | | ** MANY OF THE PROPOSED DEVICES EASILY FALL OFF WHEN | | | REMOVING PANEL COVERS OR CAN BE READILY REMOVED. | | | | | | 6) NOTE:OK, HOWEVER SEE NEW NOTES. | | | | | | 7) NOTE: OK. | | | | | | 8) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS | | | FOR CHAPTER 13 COMPLIANCE. | | | PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES. PLEASE | | | SEE MISSING SCHEDULING OF SYSTEM. | | | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE | | | NEW LIGHTING CONTROL PANEL. | | | 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE | | | VERIFIED AS SHOWN. | | | SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE | | | LISTING FROM A NRTL(NATION RECOGNIZED TESTING | | | LABORATORY). | | | PLEASE SUBMIT A DETAIL FOR THIS PANEL AND HOW ALL | | | EMERGENCY AND EXIT LIGHTING WILL BE WIRED AHEAD OF ALL | | | LIGHTING CONTROLS AND OCCUPANCY DEVICES. | | | PLEASE SEE 13-415.1.ABC.3 FOR NOTES AND INDICATION OF | | | TANDEM WIRING. | | | PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND | | | OCCUPANCY DEVICES. (SOME SHOWN AND NOTED AT 10MINS | | | WHICH ARE OK). | | | PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS | | | BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL | | | BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR | | | SUBMITTED BACK FOR REVIEW. | | | PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING | | | WITH MANUAL CONTROL. THIS IS NOT POSSIBLE AS AUTOMATED | | | SYSTEMS ARE BEING INSTALLED AND REQUIRED. | | | PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW, | | | THERE MAY BE SOME FUTURE COMMENTS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A | | | WORST CASE SCENARIO. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE | | | 13-415.1.AB.1, | | | 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1 PLEASE | | | ALSO SEE NO ENERGY CALCULATIONS WERE SUBMITTED FOR | | | REVIEW. | | | PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC. | | | | | | *** NEW NOTES** | | | | | | 1) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF | | | CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL | | | INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL | | | DEVICES. | | | PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES | | | SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE | | | MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2, | | | .3(4). | | | PLEASE KNOW THIS COMMENT WAS NOT PART OF PREVIOUS | | | REVIEW AS THIS HAS NOW BECOME PART OF THE ELECTRICAL | | | REVIEW TO REVIEW DEVICES FOR CHAPTER 11 REQUIREMENTS. | | | THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS | | | EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND | | | PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE | | | BUILDING. | | | FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2) | | | | | | 2) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS ANDREPEAT COMMENTS | | | FOR CODE COMPLIANCE. | | | | | | 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE | | | BASED ON THE PANELS, LARGER CONDUCTORS FOR PANEL P2 | | | WILL BE REQUIRED. PLEASE SEE BOTH 250A MCB AND 300A MCB | | | ARE BEING SHOWN ON PLANS. | | | PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT | | | SIZES MCB'S PLEASE CORRELATE AND ADJUST. | | | | | | 4) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON | | | EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE | | | THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP | | | EXCEEDS THE RATING OF THE 112KVA RATING. | | | PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED. | | | FBC 106.1.2 ADMIN SECTION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-08 |
Time |
21:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-07 |
Time |
21:06 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | REVIEW IN PROGRESS | | | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE VALUE FOR PROPOSED | | | SCOPE OF WORK IS WAY LOW. PLEASE KNOW | | | VALUE FOR COMPLETE SCOPE OF WORK ON | | | PLANS NEEDS TO BE ADJUSTED. PLEASE SEE | | | VALUE BE BASED ON ALL LABOUR AND | | | MATERIALS WHETHER OR NOT ANY EQUIPMENT, | | | LIGHTING ETC IS OWNER SUPPLIED. | | | FBC 108.3 ADMINISTRATIVE SECTION AS | | | ADOPTED BY THE CITY OF WEST PALM BEACH. | | | ** PLEASE ALSO PROVIDE THE DESCRIPTION | | | ON APPLICATION FOR ACTUAL SCOPE OF WORK | | | BEING PERFORMED AS THE DETAIL GIVEN | | | SEEMS TO BE ABOUT THE SAME AS THE SHELL | | | BLDG APPLICATION. | | | ** NOTE FOR CONTRACTOR AND DOES NOT | | | APPLY TO PLANS. | | | | | | 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE | | | NOT SIGNED, DATED OR SEALED BY ANY OF | | | THE DESIGN PROFESSIONAL RESPONSEIBLE FOR | | | DESIGNS ETC. THIS COMMENT IS FOR ALL | | | TRADES AND ALL REVIEWS WHETHER OR NOT | | | COMMENT IS MADE BY OTHER TRADES. | | | FS 471.025, 481.221, FAC 61G15-23.002, | | | 61G1-16 | | | | | | 3) NOTE: PLEASE BE SURE THE PLANS | | | REFLECT THE FOLLOWING CODES AT A MINIMUM | | | FOR ELECTRICAL REVIEW. | | | 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 | | | NFPA-101 AND THE 2004 FBC. | | | PLEASE SEE THERE ARE CODE ARTICLES | | | REFERENCED ON PLANS WHICH ARE FROM THE | | | 1996 NEC> | | | PLEASE SEE REDLINED SET. | | | | | | 4) NOTE: PLEASE SEE THIS PLAN AND RISER | | | IS SHOWING A NEW AND SEPARATE ELECTRICAL | | | SERVICE WHICH DOES NOT CORRELATE WITH | | | THE SHELL BUILDING PLANS. PLEASE REVISE | | | RISER TOINCLUDE THE MAIN FEED FROM THE | | | MAIN ELECTRICAL ROOM. | | | PLEASE ALSO SEE ELECTRICAL PLANS SHOW | | | 400A MAIN AND RISER SHOWS 600A. | | | THIS IS ONE BUILDING AND THE SEPARATION | | | PROVIDED IN THE ARCHITECTURAL AND | | | STRUCTURAL PLANS DO NOT SEEM TO LEND TO | | | THE DEFINITION OF A "BUILDING" WHICH | | | WOULD CONTAIN A "FIRE WALL". PLEASE SEE DEFINITIONS OF | | | "FIRE WALL". (4HR RATED | | | AND ABLE TO COLLAPSE ON BOTHS SIDES | | | WITHOUT AFFECT THE STRUCTURAL INTEGRITY | | | OF THE OTHER STRUCTURE. | | | PLEASE SEE 230.2, AND GRANTING OF AN | | | ADDITIONAL SERVICE AT THIS TIME IS NOT | | | GRANTED. | | | | | | 5) NOTE: PLEASE PLACE NOTE ON PLANS WITH | | | NOTE #1 AS NOTED FOR PANEL SCHEDULES AND | | | PROPOSED LOCK OFF DEVICES ON BRKRS. | | | PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES | | | MUST BE AN INTEGRAL PART OF THE BREAKER | | | AND NOT CAPABLE OF BEING REMOVED WITHOUT | | | THE BREAKER BEING REMOVED. | | | ** MANY OF THE PROPOSED DEVICES EASLIY | | | FALL OFF WHEN REMOVING PANEL COVERS OR | | | CAN BE READILY REMOVED. | | | | | | 6) NOTE: PLEASE SEE AND CLARIFY THE | | | NUMBER OF CONDUCTORS ON THE LINE SIDE OF | | | THE TRANSFORMER AS THE TRANSFORMER IS | | | INDEED A SDS, AND A NEUTRAL CONDUCTOR | | | WOULD NOT BE BROUGHT TO THIS EQUIPMENT. | | | 250.6, 250.24B 230.50,250.20 ETC | | | | | | 7) NOTE: PLEASE SEE NOTE WHICH IS ADDED | | | TO THE BOTTOM OF FIXTURE SCHEDULE | | | MENTIONS "EM" STANDS FOR EMERGENCY | | | FIXTURE, HOWEVER PLEASE INDICATE THE | | | BATTERY BACK UP AND THE TIME. | | | LS101 7.8, 7.9 | | | FBC 106.1.2 | | | | | | 8) NOTE: PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, | | | PROVIDE A WORST CASE | | | SCENERIO. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND | | | .1.3. | | | PLEASE SEE 13-415.1.AB.1, | | | 13-415.2.ABC.1, TABLES 415.2.C.1, AND | | | 415.2.B.1 | | | PLEASE ALSO SEE NO ENERGY CALCULATIONS | | | WERE SUBMITTED FOR REVIEW. | | | PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 | | | FBC. | | | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT THE | | | ELECTRICAL PLANS. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2006-08-07 00:00:00 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2007-05-17 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-05-17 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-05-17 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2007-05-17 10:42:40 | ACCORDING TO ARCHITECT, STEVEN L. COHEN'S LETTER OF | | | MARCH 23, 2007,THIS PERMIT IS FOR INTERIOR FIT ONLY | | | PER MR. COHEN.ALL ENGINEERING SITE DATA ARE IN PERMIT | | | # 06070445 ACCORDING TO MR. STEVEN L. COHEN | | | | | | THEREFORE, THIS PERMIT DOES NOT REQUIRE ENG REVIEW. | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2007-01-05 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-01-05 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-01-05 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-08-17 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-08-17 |
Time |
09:42 |
Sent To |
Z |
|
| Notes |
| 2006-08-17 00:00:00 | FAILED FOR THE FOLLOWING REASONS: | | | | | | NEED ATLEAST THE FOLLOWING INFO: | | | | | | 1. NOTES ON DRAWING & POLLUTION | | | PREVENTION PLANS & NOTES DETAIL, SITE | | | BOUNDRY ON THE DRAWINGS BEFORE,DURING,& | | | AFTER CONSTRUCTION. | | | | | | 2. STORM WATER CAL.,PERVIOUS, IMPERVIOUS | | | AREAS CAL.,RUNOFF WATER | | | CAL.,GEOTECHNICAL ENG. REPORT,SFWMD | | | PERMIT, | | | | | | 3. PLANS MUST BE APPROVED FOR UTILITY | | | REVIEW FROM MANNY G., 45 TH STREET ENG. | | | SERVICES, BEFORE WE APPROVE. | | | | | | 4. NEED ALL NOTES ON CIVIL DRAWINGS FOR | | | CITY OF WPB STANDARDS FOR DUMPSTER | | | ENCLOSURE, SIDEWALK, DRIWAY,PARKINGS, | | | HANDICAP PARKING,PER ADA STANDARD AS | | | WELL, ETC.,ETC, | | | | | | 5. SITE ELEVATION MAP INCUDING CENTER | | | LINE ROAD ELEVATION,CURB ELE.,SIDEWALK | | | ELE.,FIRST FLOOR ELEVATION, PARKING ELE. | | | ETC., MUST MEET BUILDING CODE. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-05-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-22 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-22 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2007-05-22 16:26:24 | *****UNSAT***** | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101 (2003 | | | EDITION) AND THE FLORIDA FIRE PREVENTION CODE (2004 | | | EDITION). | | | | | | 5.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 6.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO THE | | | SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE | | | LANES). | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-28 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-28 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2006-12-28 16:28:53 | *****DENIED***** | | | | | | | | | | | | 1.PLEASE CLARIFY IF THE PROPOSED SCOPE OF WORK AT | | | THIS LOCATION IS FOR INTERIOR ALTERATION, BUILDING | | | CONSTRUCTION, OR A COMBINATION OF THE TWO.ALSO, | | | STAPLES IS LISTED AS BAY 2; ARE THERE ANY OTHER | | | TENANTS/BAYS FOR 2029 OKEECHOBEE BOULEVARD?THE USE OF | | | SUITE/TENANT/BAY SHOULD ONLY BE USED WHEN THERE ARE | | | MORE THAN ONE UNIT WITH THE SAME NUMERICAL ADDRESS. | | | | | | 2.ON DRAWING A10, SHOW/DISPLAY THE NUMERICAL ADDRESS | | | ON THE BUILING AS PER WEST PALM BEACH CODE (NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH). | | | | | | 3.DRAWING NUMBER E-1 THRU FS-2 HAVE THE INCORRECT | | | NUMERICAL ADDRESS (2015 OKEECHOBEE BLVD.) IN THE TITLE | | | SECTION OF THE PLAN. | | | | | | 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101 (2003 | | | EDITION) AND THE FLORIDA FIRE PREVENTION CODE (2004 | | | EDITION). | | | | | | 5.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 6.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO THE | | | SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE | | | LANES). | | | | | | 7.ON DRAWING AC-2, MAKE CHANGE TO GENERAL AIR | | | CONDITIONING NOTE #17 TO REFLECT THAT DUCT SMOKE | | | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | 8. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-10-10 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-10-10 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2006-10-10 10:50:54 | ***DENIED*** | | | | | | 1) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE AT | | | LEAST 6" IN HEIGHT AND CONTRASTING TO THE BACKGROUND. | | | NUMBER TO BE AT LEAST 1" IN WIDTH. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 4) NFPA 13 AND NFPA 72 2003 EDITIONS. | | | | | | 5) PLANS SHOW THE FDC BEING RELOCATED. THE CONNECTION | | | SHALL BE LOCATED NOT FURTHER THAN 150' FROM A FIRE | | | HYDRANT. | | | | | | 6) DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-04-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-17 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-17 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2007-04-17 13:42:36 | TO "COMM" BD#19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-06 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-06 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2006-12-21 16:48:25 | TO "COMM" BD#14 | | 2006-12-06 15:46:36 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-10-10 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-11 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2006-07-27 00:00:00 | TO "COMM" BD#56 | | 2006-07-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-04-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-26 |
Time |
12:09 |
Rev Time |
0.35 |
| Received By |
tgordon |
Date |
2007-04-26 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2007-04-26 12:09:30 | *** DENIED *** | | | 1) THE FIRM'S LICENSE FOR STEVEN L. COHEN AND | | | ASSOCIATES, P.A. HAS EXPIRED ON 2-28-2005 AND IS NOW | | | NULL AND VOID, PLEASE CORRECT. | | | | | | 2) ENGINEERING DESIGN ASSOCIATES, INC. CERTIFICATE OF | | | AUTHORIZATION EXPIRED 2-28-2007, PLEASE CORRECT. | | | | | | *** FAC 61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. (NULL AND VOID). | | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" | | | SEE CITY WPB AMEND. 106.1.1). | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | *** FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-22 |
Time |
09:37 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-12-22 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-19 |
Time |
16:04 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-09-19 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2006-09-19 00:00:00 | *** DENIED *** | | | 1) ARCHITECT NEEDS TO SIGN AND SEAL | | | PLANS, PER FS 61G1-16.003 . | | | | | | 2) NEED TO SHOW ENGINEERED ANCHORING | | | DETAILS FOR (A/C) CURB TO ROOF AND RTU | | | TO CURB, TO WITHSTAND 140 MPH WINDS, PER | | | 2004 FBC 1609. | | | | | | 3) PLEASE SUBMIT ENERGY CALCULATIONS, | | | PER 2004 FBC 13-101.1.6 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-05-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-05-31 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-05-30 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2007-05-31 09:47:40 | DENIED... | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE FLORIDA | | | STATUTES | | | | | | ******FROM 1ST REVIEW: | | | | | | 1. OK | | | | | | 2. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF | | | AUTHORIZATION, (BUSINESS NUMBER), IS INDICATED AS | | | DELINQUENT PER DBPR WEBSITE. THIS SHALL BE TAKEN CARE | | | OF PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1) | | | & FS 481.219. | | | ****NO RESPONSE, NOT ADDRESSED | | | | | | 3. OK | | | 4. OK | | | | | | 5. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING: | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. OK | | | | | | 6. SHT A-9 DETAIL #2 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. OK | | | B. OK | | | C. OK | | | | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | | | | ******FROM 2ND REVIEW: | | | | | | 1) SHT P-2,NOTE #16 REFERENCE TO A/C CONDENSATE | | | DRAIN. SHT A/C-2 ROOF TOP UNIT DETAIL, IS NOT SHOWING | | | DISPOSAL OF A/C CONDENSATE. PLEASE CLARIFY. | | | ****RESPONSE NOTED, BUT THE CONDENSATE SHALL NOT DRAIN | | | ONTO THE ROOF. THE CONDENSATE SHALL BE PIPED TO THE | | | ROOF DRAINS AND DRAIN INDIRECTLY OVER THE DRAINS. | | | PLEASE SUBMIT A DETAIL SHOWING THE PIPE SUPPORTS | | | INDICATING THE SPACING PER TABLE 308.5. INDICATE HOW | | | THE SUPPORTS WILL BE ATTACHED TO THE ROOF SHOWING | | | COMPLIANCE WITH 140 MPH WINDLOAD REQUIREMENTS. SHOW THE | | | ROUTING FOR THE PIPE FOR EACH A/C UNIT ON SHT P-1 OR ON | | | A ROOF PLAN SHOWING ALL ROOF DRAINS. SECTION 106.1.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-01-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-01-13 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-01-13 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2007-01-13 12:29:04 | PAUL SCHMITZ | | | [email protected] 2004 PLUMBING CODE | | | PLAN REVIEWFBC2004 FUEL GAS CODEPLAN | | | REVIEWFBC 2004 CH 11, FL ACESSIBILITY | | | CODEAMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED, NEW COMMENTS | | | | | | 1) SHT P-2 , NOTE #16 REFERENCE TO A/C CONDENSATE | | | DRAIN. | | | SHT A/C -2 ROOF TOP UNIT DETAIL, IS NOT SHOWING | | | DISPOSAL OF A/C CONDENSATE. | | | PLEASE CLARIFY. | | | | | | 2) SHT P-2WATER HEATER DETAIL | | | 607.3 THERMAL EXPANSION CONTROL. | | | A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY | | | THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN | | | ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2 | | | BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A | | | BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE | | | IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE | | | WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION | | | CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR | | | CONTROLLING PRESSURE SHALL BE INSTALLED. | | | | | | 3) SHT P-2 WATER RISER DIAGRAM | | | PLEASE CLARIFY WHAT IS BEING USED AT EACH WATER | | | SUPPLIED FIXTURE. | | | 604.9 WATER HAMMER. | | | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM | | | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER | | | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED | | | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER | | | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS | | | SHALL CONFORM TO ASSE 1010. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-12 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-05 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2006-10-12 13:53:05 | DENIED... | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE FLORIDA | | | STATUTES | | | | | | 1. ALL ARCHITECTURAL SHEETS SHALL BE SIGNED, SEALED, | | | DATED PER SECTION 106.1, FAC 61G1-16.003 & FS | | | 481.2055. | | | | | | 2. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF | | | AUTHORIZATION, (BUSINESS NUMBER), IS INDICATED AS | | | DELINQUENT PER DBPR WEBSITE. THIS SHALL BE TAKEN CARE | | | OF PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1) | | | & FS 481.219. | | | | | | 3. SHT A-7 DETAIL #2 SHOWS A URINAL IN THE WOMEN'S | | | TOILET ROOM. PLEASE CLARIFY. SECTION 106.1.1. - DETAIL | | | #2 ALSO INDICATES A SINGLE DRINKING FOUNTAIN. PLEASE | | | SHOW COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS | | | FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | | | | 4. SHT A-7 DETAIL #13 NO LAV SHOWN IN THE WOMEN'S | | | ACCESSIBLE STALL AS SHOWN ON THE FLOOR PLAN. PLEASE | | | CORRELATE ELEVATION DETAILS WITH THE FLOOR PLAN. | | | | | | 5. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.19.3 CLEAR FLOOR SPACE | | | D. 11-4.19.4 EXPOSED PIPES & SURFACES | | | E. 11-4.19.5 FAUCETS | | | | | | 6. SHT A-9 DETAIL #2 SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE | | | | | | 7. ALL PME SHEETS SHALL BE SIGNED, SEALED, DATED. | | | SECTION 106.1, FAC 61G15-23.002 & FS 471.025. | | | | | | 8. SHTS P-1 & P-2. FLOOR DRAINS ARE SHOWN ON THE FLOOR | | | PLAN IN THE MEN'S & WOMEN'S TOILET ROOMS, THE JANITOR | | | ROOM, AND THE LOUNGE ON THE ARCHITECTURAL FLOOR PLANS, | | | BUT NOT ON THE PLUMBING SHEETS. PLEASE CORRELATE | | | ARCHITECTURAL SHEETS AND THE PLUMBING FLOOR PLAN AND | | | SANITARY RISER DIAGRAM. SECTION 106.1.1. | | | | | | 9. SHTS P-1 & P-2 NO WATER OR SANITARY PIPING SHOWN TO | | | THE LOUNGE SINK. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 10. HOT WATER SUPPLY IS REQUIRED FOR THE JANITOR SINK | | | PER SECTION 607.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
|