Plan Review Details - Permit 06070451
Plan Review Stops For Permit 06070451
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2007-04-23 Cont ID  
Sent By lursu Date 2007-04-23 Time 14:46 Rev Time 0.00
Received By lursu Date 2007-04-23 Time 14:46 Sent To  
Notes
2007-04-23 14:48:04THE REVISED PLANS HAD BEEN CORRECTED WITH THE CORRECT
 ADDRESS ,2029 OKEECHOBEE BLVD ,TO BE USED FOR BAY 2 (
 STAPLES)
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2006-10-19 Cont ID  
Sent By lursu Date 2006-10-19 Time 08:43 Rev Time 0.00
Received By lursu Date 2006-10-19 Time 08:43 Sent To  
Notes
2006-10-19 08:45:11BASED ON THE CONVERSATION WITH THE ENG FIRM THE
 FOLLOWING ITEMS WERE RECEIVED : SITE PLANS, DEMO PLANS
 AND THE SURVEY .BASED ON THESE ITEMS ,THE SITE ADDRESS
 TO USE FOR THIS PERMIT IS 2029 OKEECHOBEE BLVD.
 PLEASE APPLY TO THE REVISED SITE PLANS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-08-24 Cont ID  
Sent By lursu Date 2006-08-24 Time 08:30 Rev Time 0.00
Received By lursu Date 2006-08-24 Time 08:30 Sent To  
Notes
2006-08-24 00:00:00NOT CLEAR IF BAY # 1 BELONGS TO THE
 THEATER AND BAY # 2I S STAPLES .
 IS BAY # 3 INLCUDED IN THE RENOVATION?
 THE APPLICATION AND SITE PLAN MUST BE
 READ THE CORRECT ADDRESS FOR EACH BAY.
 THE ADDRESS 2015 OKEECHOBEE BLVD IS USED
 FOR THE ENTIRE PLAZA , OKEE SQUARE , BUT
 FOR EACH INDIVIDUAL BAY THE CORRECT
 ADDRESS MUST BE USED AND THE PERMITS
 WILL BE ISSUED BASED ON THESE ADDRESSES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By lursu Date 2006-08-10 Time 09:08 Rev Time 0.00
Received By lursu Date 2006-08-10 Time 09:08 Sent To  
Notes
2006-08-21 00:00:00ADDRESS ON THE APPLICATION 2035
 OKEECHOBEE BLVD BELONGS TO ROOMS RO GO
 KIDS , PLS CORRECT ADDR
2006-08-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) ARCHITECT STEVEN L. COHEN AR0006819
 IS WORKING WITH A DELINGUENT LICENSE,
 EXPIRED 02/28/05.
 WWW.MYFLORIDA.COM/LICENSING
  
 4) PLANS ARE NOT SIGNED NOR SEALED
 ARCHITECTURALS OR MEP PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) NOTE: A-1 PLANS INDICATE EXISTING
 PASSAGEWAY, TO BE COMPLETED UNDER THE
 SHELL PERMIT.
  
 6) EX FBC 708.1 ALTERATIONS SUBJECT TO
 THIS CHAPTER SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 13 OF THE FBC
 BUILDING.
  
 7) EX FBC 706.1 A BUILDING FACILITY, OR
 ELEMENT THAT IS ALTERED SHALL COMPLY
 WITH CHAPTER 11 OF THE FBC, BUILDING.
 SHEET A-2 DOORS 5/106 & 6/107 TO COMPLY
 WITH: 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 8) A-2 AND A-5 BOTH INDICATE SOME TYPE
 OF SECURITY GRILL, PROVIDE ADDITIONAL
 INFORMATION, 106.1.2.
  
 9) A-2 AND A-5 BOTH INTERIOR AUTO DOORS
 PROVIDE NOTICE OF ACCEPTANCE.
  
 10) A7 DETAIL 16 DOESN'T INDICATE
 TERMITE TREATMENT:
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 11) A-3 NOTES 3,4 & 5 ALL INDICATE
 UNPAINTED PLYWOOD TO VARIOUS HEIGHTS.
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED
 IN BUILDINGS OF TYPE I OR II
 CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3 :
 1.FIRE-RETARDANT-TREATED WOOD SHALL
 BE PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE
 REQUIRED FIRE-RESISTANCE RATING IS 2
 HOURS OR LESS.
  
 12) PROVIDE ADDITIONAL INFORMATION HOW
 TO COMPLY WITH:1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
2006-08-10 00:00:00PROJECT UNDER REVIEW.FIELD VERIFICATION
 IS NEEDED,

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 15:19 Rev Time 1.11
Received By jwitmer Date 2007-06-13 Time 15:19 Sent To PC
Notes
2007-06-13 15:22:34BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)COMMENT# 7 FROM THE FIRSTREVIEW DEALS
 WITH THE AUTOMATIC SLIDING DOORS INTERIOR DOORS AT THE
 VESTIBULE 1/100 AND 2/101,ADDITIONAL INFORMATION
 AS TOO HOW ONE WILL GAIN EGRESS FROM THE STORE IN THE
 EVENT OF LOSS OF POWER.PLEASE PROVIDE PROUCT APPROVAL
 FOR OTHER DOCUMENTATION PROVIDING
 COMPLIANCE WITH:
 1008.1.3.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1.
 THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE
 OF BEING OPERATED MANUALLY IN THE EVENT OF POWER
 FAILURE.
 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-05 Cont ID  
Sent By jwitmer Date 2007-01-05 Time 15:03 Rev Time 1.55
Received By jwitmer Date 2007-01-05 Time 15:02 Sent To  
Notes
2007-01-05 14:52:54BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMMENT #5 FROM THE FIRST REVIEW DEALS
 WITH THE MINIMUM REQUIREMENTS OF CHAPTER
 13 ENERGY CODE REQUIREMENTS
 PLEASE SEE ELECTRICAL STATEMENTS.
  
 4 COMMEENT# 7 FROM THE PREVIOUS EVIEW DEALS
 WITH THE AUTOMATIC SLIDING DOORS,ADDITIONAL
 INFORMATION
 AS TOO HOW ONE WILL GAIN EGRESS FROM THE STORE IN THE
 EVENT OF LOSS OF POWER.
 PLEASE PROVIDE PROUCT APPROVAL FOR OTHER DOCUMENTATION
 PROVIDING
 COMPLIANCE WITH:
  
 1008.1.3.3 HORIZONTAL SLIDING DOORS.
  
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1.
 THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE
 OF BEING OPERATED MANUALLY IN THE EVENT OF POWER
 FAILURE.
 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-15 Cont ID  
Sent By jwitmer Date 2006-08-15 Time 11:11 Rev Time 8.88
Received By jwitmer Date 2006-08-15 Time 11:11 Sent To  
Notes
2006-08-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) ARCHITECT STEVEN L. COHEN AR0006819
 IS WORKING WITH A DELINGUENT LICENSE,
 EXPIRED 02/28/05.
 WWW.MYFLORIDA.COM/LICENSING
  
 4) THE ARCHITECTURAL AS WELL AS THE MEP
 PLANS ARE NOT SIGNED NOR SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) EX FBC 708.1 MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TOTHIS CHAPTER SHALL
 COMPLY WITH THE REQUIREMENTS OF CHAPTER
 13 OF THE FBC, BUILDING.
  
 6) EX FBC 706.1 A BUILDING, FACILITY OR
 ELEMENT THAT IS ALTERED SHALL COMPLY
 WITH CHAPTER 11 OF THE FBC BUILDING.
 SHEET A2 DOOR5/106 & 6/107 DO NOT MEET
 THE REQUIREMENTS OF 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 7) PROVIDE ADDITIONAL INFORMATION FOR
 A) SECURITY GRILLE LOCATED AT VESTIBULE
 B) VESTIBULE AUTO SLIDING DOORS
 LOCATED ON SHEET A2 & A5
 106.1.2* ADDITIONAL INFO.
  
 8) SHEET A7 DETAIL# 16 FLOOR SLAB,
 PROIDE INFORMATION ON TERMITE TRATMENT.
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 9) SHEET A-3 NOTES 3-5 INDICATE THAT
 PLYWOOD TO BE APPLIED TO WALL ROOM
 FINISH NOTES. IS THIS A WALL FINISH OR
 INCASED IN THE WALL?
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED
 IN BUILDINGS OF TYPE I OR II
 CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3 :
 1.FIRE-RETARDANT-TREATED WOOD SHALL
 BE PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE
 REQUIRED FIRE-RESISTANCE RATING IS 2
 HOURS OR LESS.
 1.2.NONBEARING EXTERIOR WALLS WHERE
 NO FIRE RATING IS REQUIRED.
 TABLE 803.5 MERCANTILE OCCUPANCY
 SPRINKLERED FLAME SPREAD INDEX 76-200
 SMOKE DEVELOPMENT 0-450. IF THE PLYWOOD
 IS TO BE A FINISHED WALL THEN PROVIDE
 THE FLAME SPREAD AND SMOKE DEVELOPMEENT.
  
 10) A7 RESTROOMS SHOW COMPLIANCE WITH
 RESTROOM NONABSORBENT WALLS.PROVIDE
 MANUFACTURER INFORMATION.1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-22 Cont ID  
Sent By dpalmer Date 2007-04-22 Time 13:26 Rev Time 0.00
Received By dpalmer Date 2007-04-22 Time 11:26 Sent To  
Notes
2007-04-22 13:28:04 
 ******* UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE THAT THERE ARE STILL MANY ITEMS FROM
 PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN ADDRESSED FOR
 CODE COMPLIANCE.
  
 ** PLEASE SEE THE RESPONSE LETTER FROM THE DESIGNER
 ONLY RESPONDED TO NOTES 1-8 AND NEW NOTES FROM LAST
 REVIEW WERE NOT NOTED AND LETTER DID NOT CONTAIN ANY
 RESPONSE??A RESPONSE LETTER IS NOT REQUIRED HOWEVER
 WILL SOMETIMES HELP TO EXPLAIN ITEMS OR EXPEDITE THE
 REVIEW PROCESS.
  
  
 1) NOTE:PLEASE SEE THE NOTE FOR THE VALUE FOR
 COMPLETE SCOPE OF WORK STILL REMAINS. RESPONSE FROM
 DESIGNER MENTIONS FOR CONTRACTOR TO ADDRESS HOWEVER NO
 CHANGES TO APPLIED VALUE HAS BEEN DONE. PLEASE KNOW
 THAT A VALUE WILL BE ASSESSED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INDICATED.
 AS STATED ON PREVIOUS REVIEW THE VALUE SHALL INCLUDE
 ALL LABOR AND MATERIALS, INCLUDING ALL EQUIPMENT, A/C
 EQUIPMENT, ELECTRICAL EQUIPMENT, LIGHTING FIXTURES ETC.
 PLEASE KNOW A VALUE WILL BE ASSESSED USING THE FBC
 TABLES FOR INTERIOR BUILD OUT OF THE SQ FT AND WILL BE
 SUBSTANTIALLY INCREASED IF AN APPROPRIATE VALUE IS NOT
 APPLIED. PLEASE SEE FS 553.79, 553.792, AND FS 489.
 ** THE VALUE OF THE ELECTRICAL EQUIPMENT ALONE IS
 HIGHER THAN THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK AS APPLIED.
 *FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 2) NOTE:PLEASE COORDINATE THE ELECTRICAL SERVICE ON
 THE BUILD OUT PLANS AS WELL AS THE ELECTRICAL PLANS FOR
 THE SHELL PERMITTED PLANS.
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT
 CORRELATE.
  
 A) PLEASE SEE THE MAIN SWITCH IN TENANT SPACE
 ELECTRICAL ROOM IS STILL BEING SHOWN AS 600AMP WITH
 400AMP OVER CURRENT PROTECTION YET THE RISER AND OTHER
 PLANS INDICATE THIS DISCONNECT AS BEING 600AMP WITH
 600AMP OVER CURRENT PROTECTION. NOTED ON BOTH PREVIOUS
 REVIEWS, YET PLANS STILL SHOW THIS?
  
 B) PLEASE THE FEEDERS ARE STILL SHOWN AS OVER HEAD TO
 THE TENANT ELECTRICAL ROOM AND WELL AS BEING NOTED AS
 UNDERGROUND ON SHELL PLANS AND THESE PLANS.
  
 C) PLEASE SEE THE FEEDER CONDUITS ARE SHOWN AS 3INCH ON
 SOME SHEETS AND 4INCH ON OTHERS AND SHELL PLANS?
  
 D) PLEASE SEE THE FEEDERS NOW FROM THE MAIN ELECTRICAL
 ROOM HAVE BEEN CHANGED FROM THE PREVIOUS 600MCM DOWN TO
 350MCM YET THE VOLTAGE DROP CALCULATIONS STILL INDICATE
 600MCM. PLEASE SEE SHELL PLANS.
 13-413.1ABC.1 AS NOTED ON PREVIOUS REVIEW FOR VOLTAGE
 DROP)
  
 E) PLEASE SEE THE ONE-LINE DIAGRAM ON THE TENANT BUILD
 OUT PLANS SHALL INDICATE THE OCP AND MAIN WHICH IS
 LOCATED IN THE MAIN SWITCH BOARD ON THE SHELL PLANS.
 230.70, 230.71, 230.72.
  
 ** PLEASE COORDINATE ALL ELECTRICAL EQUIPMENT ON BOTH
 SETS OF PLANS UNDER EACH PERMIT AND ADJUST FOR THE CODE
 COMPLIANCE COMMENTS.
  
 3) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS
 FOR CHAPTER 13 COMPLIANCE.
 PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES.
 PLEASE SEE MISSING SCHEDULING OF SYSTEM.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW LIGHTING CONTROL PANEL.
 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE
 VERIFIED AS SHOWN.
 SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE
 LISTING FROM A NRTL(NATION RECOGNIZED TESTING
 LABORATORY).
 PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND
 OCCUPANCY DEVICES.
 PLEASE SEE MANY ROOMS WHICH STILL ONLY INDICATE A *S*
 SWITCH FOR CONTROL OF LIGHTING. PLEASE SEE
 13-415.1.ABC.1.2 FOR SPACE CONTROL.
 PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS
 BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL
 BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR
 SUBMITTED BACK FOR REVIEW.
 PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING
 WITH MANUAL CONTROL FOR LIGHTING WHICH IS NOT POSSIBLE
 WHEN AN AUTOMATED SYSTEM IS BEING INSTALLED AND
 REQUIRED.
 PLEASE CORRELATE THE FIXTURES ON PLANS WITH THAT OF THE
 FIXTURES ON ENERGY CALCULATIONS FOR THE TYPE, WATTAGE
 AND THE NUMBER OF FIXTURES ON PLANS AND IN
 CALCULATIONS.
 ** PLEASE SEE THAT THE EXACT SAME ENERGY CALCULATIONS
 WERE SUBMITTED BACK.
 PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW,
 THERE MAY BE SOME FUTURE COMMENTS.
  
 PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A
 WORST CASE SCENARIO.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1,
 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1
 PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC.
  
  
 4) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF
 CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL
 INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL
 DEVICES.
 PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES
 SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE
 MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2,
 .3(4).
 THIS IS REQUIRED FOR BASE DESIGN AND LOCATIONS FOR ADA
 COMPLIANCE ON BASE BUILDINGS AND PLANS.
 THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS
 EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND
 PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE
 BUILDING.
 FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2)
  
 5) NOTE: PLEASE CORRELATE RISER AND PANELS.
 PLEASE SEE THE CONDUCTORS FROM THE TRANSFORMER TO PANEL
 P2 WAS CORRECTED TO MEET THE MINIMUM AMPERAGE REQUIRED
 PER 240.21C6, 310.16, 240.4, HOWEVER THE
 CONDUCTORS/FEEDERS LOCATED FROM P2 TO P3 HAVE NOT BEEN
 CORRECTED.
 PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT
 SIZES MAIN CIRCUIT BREAKERS, PLEASE CORRELATE AND
 ADJUST.
 RISER STILL SHOWS 150A MCB AND PANEL P1 STILL SHOWS A
 100A MCB.
 PLEASE SEE THE RISER SHOWS 150AMP RATED CONDUCTORS FROM
 THE MDP TO TRANSFORMER ON A 175AMP RATED BREAKER
  
 6) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON
 EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE
 THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP
 EXCEEDS THE RATING OF THE 112KVA RATING. THIS IS THE
 SAME COMMENT. PLEASE SEE THE LOAD SHOWN ON THE
 MDP.(120,908VA)
 PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED.
 230,240, 408, ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE NOTICE
 TO FS 553.80(2)(B) WITH RESPECT TO REPEAT CODE
 COMPLIANT COMMENTS.
 PLEASE SEE A FEE HAS NOW BEEN ASSESSED IN THE AMOUNT OF
 $3,300 WHICH IS REQUIRED BEFORE PLANS MAY BE
 RE-SUBMITTED FOR REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By dpalmer Date 2006-12-23 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2006-12-23 Time 15:34 Sent To  
Notes
2006-12-23 18:40:45*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW NOTES. PLEASE
 SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW AND IN THE EXACT NUMERICAL ORDER WITH NEW NOTES
 ADDED TO THE BOTTOM OF THE FIRST REVIEW NOTES.
  
 ** PLEASE SEE NOTES ARE NOTED WITH A NO, OK,OR SOME
 MAY CONTAIN A NO/OK, WHICH WOULD INDICATE PART OF THE
 COMMENT MAY HAVE BEEN ADDRESSED HOWEVER NOT FULLY OR
 THERE STILL MAY BE SOME UNCERTAINLY OF RESPONSE/PLANS.
  
 1) NOTE:NO, PLEASE SEE THE VALUE WAS INCREASED ON
 PERMIT APPLICATION BY $5K. AS STATED ON PREVIOUS REVIEW
 THE VALUE SHALL INCLUDE ALL LABOR AND MATERIALS,
 INCLUDING ALL EQUIPMENT, A/C EQUIPMENT, ELECTRICAL
 EQUIPMENT, LIGHTING FIXTURES ETC. PLEASE KNOW A VALUE
 WILL BE ASSESSED USING THE FBC TABLES FOR INTERIOR
 BUILD OUT OF THE SQ FT AND WILL BE SUBSTANTIALLY
 INCREASED IF AN APPROPRIATE VALUE IS NOT APPLIED.
 PLEASE SEE FS 553.79, 553.792, AND FS 489.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR PROPOSED SCOPE OF WORK IS WAY
 LOW. PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK ON
 PLANS NEEDS TO BE ADJUSTED. PLEASE SEE VALUE BE BASED
 ON ALL LABOR AND MATERIALS WHETHER OR NOT ANY
 EQUIPMENT, LIGHTING ETC IS OWNER SUPPLIED.
 FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
 ** PLEASE ALSO PROVIDE THE DESCRIPTION ON APPLICATION
 FOR ACTUAL SCOPE OF WORK BEING PERFORMED AS THE DETAIL
 GIVEN SEEMS TO BE ABOUT THE SAME AS THE SHELL BLDG
 APPLICATION.
 ** NOTE FOR CONTRACTOR AND DOES NOT APPLY TO PLANS.
  
 2) NOTE: OK.
  
 3) NOTE: NO/OK. PLEASE SEE THE CODES WERE ADDED TO
 PLANS; HOWEVER THERE ARE STILL SEVERAL SECTIONS OF THE
 CODES BEING NOTED ON PLANS WHICH ARE OUT OF THE 1996
 NFPA-70.
 PLEASE KNOW WHEN SPECIFICALLY NOTED CODE SECTIONS ON
 PLANS, AND THEN THEY MUST REFLECT AND CORRELATE WITH
 THE CODE WHICH THEY ARE UNDER AND CORRELATE. PLEASE SEE
 MISSING REFERENCE TO NFPA-101 2003
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING CODES AT
 A MINIMUM FOR ELECTRICAL REVIEW.
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101 AND THE 2004 FBC.
 PLEASE SEE THERE ARE CODE ARTICLES REFERENCED ON PLANS
 WHICH ARE FROM THE
 1996 NEC>
 PLEASE SEE REDLINED SET.
  
 4) NOTE:NO, PLEASE KNOW AS OF THIS REVIEW THE PLANS
 FOR THE MAIN BUILDING/SHELL HAS NOT BEEN IN FOR REVIEW.
 PLEASE SEE PREVIOUS NOTES UNDER THEIR PERMIT. PLEASE
 SEE PLANS STILL DO NOT CORRELATE AND THE SERVICE AS
 SHOWN IS NOT PERMITTED. 230.2.
 PLEASE KNOW IN EITHER CASE, PLANS INDICATE UNDERGROUND
 AND OVERHEAD, 400A AND 600A, PLEASE SEE 230.70 AS NO
 MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING. (230.6) PLEASE ALSO SEE NEW NOTES
 FOR SERVICE ITEMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS PLAN AND RISER IS SHOWING A NEW AND
 SEPARATE ELECTRICAL SERVICE WHICH DOES NOT CORRELATE
 WITH THE SHELL BUILDING PLANS. PLEASE REVISE RISER TO
 INCLUDE THE MAIN FEED FROM THE MAIN ELECTRICAL ROOM.
 PLEASE ALSO SEE ELECTRICAL PLANS SHOW 400A MAIN AND
 RISER SHOWS 600A.
 THIS IS ONE BUILDING AND THE SEPARATION PROVIDED IN THE
 ARCHITECTURAL AND STRUCTURAL PLANS DO NOT SEEM TO LEND
 TO THE DEFINITION OF A "BUILDING" WHICH WOULD CONTAIN A
 "FIRE WALL". PLEASE SEE DEFINITIONS OF "FIRE WALL" 4HR
 RATED AND ABLE TO COLLAPSE ON BOTH SIDES WITHOUT
 AFFECTING THE STRUCTURAL INTEGRITY OF THE OTHER
 STRUCTURE.
 PLEASE SEE 230.2, AND GRANTING OF AN ADDITIONAL SERVICE
 AT THIS TIME IS NOT GRANTED.
  
 5) NOTE: NO/OK, PLEASE SEE THE NOTE WAS ADDED TO THE
 LOWER NOTE WHICH APPEARS TO BE 15A, YET SEE NOTE #1 IS
 STILL NOTED AND SHOWN AS BEFORE. PLEASE ADJUST THIS
 NOTE #1 WITH THE NEW NOTE ADDED TO 15A.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PLACE NOTE ON PLANS WITH NOTE #1 AS NOTED FOR
 PANEL SCHEDULES AND PROPOSED LOCK OFF DEVICES ON
 BRKRS.
 PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES MUST BE AN
 INTEGRAL PART OF THE BREAKER AND NOT CAPABLE OF BEING
 REMOVED WITHOUT THE BREAKER BEING REMOVED.
 ** MANY OF THE PROPOSED DEVICES EASILY FALL OFF WHEN
 REMOVING PANEL COVERS OR CAN BE READILY REMOVED.
  
 6) NOTE:OK, HOWEVER SEE NEW NOTES.
  
 7) NOTE: OK.
  
 8) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS
 FOR CHAPTER 13 COMPLIANCE.
 PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES. PLEASE
 SEE MISSING SCHEDULING OF SYSTEM.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW LIGHTING CONTROL PANEL.
 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE
 VERIFIED AS SHOWN.
 SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE
 LISTING FROM A NRTL(NATION RECOGNIZED TESTING
 LABORATORY).
 PLEASE SUBMIT A DETAIL FOR THIS PANEL AND HOW ALL
 EMERGENCY AND EXIT LIGHTING WILL BE WIRED AHEAD OF ALL
 LIGHTING CONTROLS AND OCCUPANCY DEVICES.
 PLEASE SEE 13-415.1.ABC.3 FOR NOTES AND INDICATION OF
 TANDEM WIRING.
 PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND
 OCCUPANCY DEVICES. (SOME SHOWN AND NOTED AT 10MINS
 WHICH ARE OK).
 PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS
 BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL
 BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR
 SUBMITTED BACK FOR REVIEW.
 PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING
 WITH MANUAL CONTROL. THIS IS NOT POSSIBLE AS AUTOMATED
 SYSTEMS ARE BEING INSTALLED AND REQUIRED.
 PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW,
 THERE MAY BE SOME FUTURE COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A
 WORST CASE SCENARIO.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1,
 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1 PLEASE
 ALSO SEE NO ENERGY CALCULATIONS WERE SUBMITTED FOR
 REVIEW.
 PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC.
  
 *** NEW NOTES**
  
 1) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF
 CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL
 INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL
 DEVICES.
 PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES
 SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE
 MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2,
 .3(4).
 PLEASE KNOW THIS COMMENT WAS NOT PART OF PREVIOUS
 REVIEW AS THIS HAS NOW BECOME PART OF THE ELECTRICAL
 REVIEW TO REVIEW DEVICES FOR CHAPTER 11 REQUIREMENTS.
 THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS
 EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND
 PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE
 BUILDING.
 FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2)
  
 2) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS ANDREPEAT COMMENTS
 FOR CODE COMPLIANCE.
  
 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 BASED ON THE PANELS, LARGER CONDUCTORS FOR PANEL P2
 WILL BE REQUIRED. PLEASE SEE BOTH 250A MCB AND 300A MCB
 ARE BEING SHOWN ON PLANS.
 PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT
 SIZES MCB'S PLEASE CORRELATE AND ADJUST.
  
 4) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON
 EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE
 THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP
 EXCEEDS THE RATING OF THE 112KVA RATING.
 PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED.
 FBC 106.1.2 ADMIN SECTION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By dpalmer Date 2006-08-08 Time 21:02 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 21:06 Sent To  
Notes
2006-08-08 00:00:00REVIEW IN PROGRESS
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE VALUE FOR PROPOSED
 SCOPE OF WORK IS WAY LOW. PLEASE KNOW
 VALUE FOR COMPLETE SCOPE OF WORK ON
 PLANS NEEDS TO BE ADJUSTED. PLEASE SEE
 VALUE BE BASED ON ALL LABOUR AND
 MATERIALS WHETHER OR NOT ANY EQUIPMENT,
 LIGHTING ETC IS OWNER SUPPLIED.
 FBC 108.3 ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
 ** PLEASE ALSO PROVIDE THE DESCRIPTION
 ON APPLICATION FOR ACTUAL SCOPE OF WORK
 BEING PERFORMED AS THE DETAIL GIVEN
 SEEMS TO BE ABOUT THE SAME AS THE SHELL
 BLDG APPLICATION.
 ** NOTE FOR CONTRACTOR AND DOES NOT
 APPLY TO PLANS.
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE
 NOT SIGNED, DATED OR SEALED BY ANY OF
 THE DESIGN PROFESSIONAL RESPONSEIBLE FOR
 DESIGNS ETC. THIS COMMENT IS FOR ALL
 TRADES AND ALL REVIEWS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
 FS 471.025, 481.221, FAC 61G15-23.002,
 61G1-16
  
 3) NOTE: PLEASE BE SURE THE PLANS
 REFLECT THE FOLLOWING CODES AT A MINIMUM
 FOR ELECTRICAL REVIEW.
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101 AND THE 2004 FBC.
 PLEASE SEE THERE ARE CODE ARTICLES
 REFERENCED ON PLANS WHICH ARE FROM THE
 1996 NEC>
 PLEASE SEE REDLINED SET.
  
 4) NOTE: PLEASE SEE THIS PLAN AND RISER
 IS SHOWING A NEW AND SEPARATE ELECTRICAL
 SERVICE WHICH DOES NOT CORRELATE WITH
 THE SHELL BUILDING PLANS. PLEASE REVISE
 RISER TOINCLUDE THE MAIN FEED FROM THE
 MAIN ELECTRICAL ROOM.
 PLEASE ALSO SEE ELECTRICAL PLANS SHOW
 400A MAIN AND RISER SHOWS 600A.
 THIS IS ONE BUILDING AND THE SEPARATION
 PROVIDED IN THE ARCHITECTURAL AND
 STRUCTURAL PLANS DO NOT SEEM TO LEND TO
 THE DEFINITION OF A "BUILDING" WHICH
 WOULD CONTAIN A "FIRE WALL". PLEASE SEE DEFINITIONS OF
 "FIRE WALL". (4HR RATED
 AND ABLE TO COLLAPSE ON BOTHS SIDES
 WITHOUT AFFECT THE STRUCTURAL INTEGRITY
 OF THE OTHER STRUCTURE.
 PLEASE SEE 230.2, AND GRANTING OF AN
 ADDITIONAL SERVICE AT THIS TIME IS NOT
 GRANTED.
  
 5) NOTE: PLEASE PLACE NOTE ON PLANS WITH
 NOTE #1 AS NOTED FOR PANEL SCHEDULES AND
 PROPOSED LOCK OFF DEVICES ON BRKRS.
 PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES
 MUST BE AN INTEGRAL PART OF THE BREAKER
 AND NOT CAPABLE OF BEING REMOVED WITHOUT
 THE BREAKER BEING REMOVED.
 ** MANY OF THE PROPOSED DEVICES EASLIY
 FALL OFF WHEN REMOVING PANEL COVERS OR
 CAN BE READILY REMOVED.
  
 6) NOTE: PLEASE SEE AND CLARIFY THE
 NUMBER OF CONDUCTORS ON THE LINE SIDE OF
 THE TRANSFORMER AS THE TRANSFORMER IS
 INDEED A SDS, AND A NEUTRAL CONDUCTOR
 WOULD NOT BE BROUGHT TO THIS EQUIPMENT.
 250.6, 250.24B 230.50,250.20 ETC
  
 7) NOTE: PLEASE SEE NOTE WHICH IS ADDED
 TO THE BOTTOM OF FIXTURE SCHEDULE
 MENTIONS "EM" STANDS FOR EMERGENCY
 FIXTURE, HOWEVER PLEASE INDICATE THE
 BATTERY BACK UP AND THE TIME.
 LS101 7.8, 7.9
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1,
 PROVIDE A WORST CASE
 SCENERIO.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1, TABLES 415.2.C.1, AND
 415.2.B.1
 PLEASE ALSO SEE NO ENERGY CALCULATIONS
 WERE SUBMITTED FOR REVIEW.
 PLEASE SEE ALL OF CHAPTER 13 IN THE 2004
 FBC.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-08-07 00:00:00IN ELEC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2007-05-17 Cont ID  
Sent By rchokshi Date 2007-05-17 Time 10:42 Rev Time 0.00
Received By rchokshi Date 2007-05-17 Time 10:32 Sent To  
Notes
2007-05-17 10:42:40ACCORDING TO ARCHITECT, STEVEN L. COHEN'S LETTER OF
 MARCH 23, 2007,THIS PERMIT IS FOR INTERIOR FIT ONLY
 PER MR. COHEN.ALL ENGINEERING SITE DATA ARE IN PERMIT
 # 06070445 ACCORDING TO MR. STEVEN L. COHEN
  
 THEREFORE, THIS PERMIT DOES NOT REQUIRE ENG REVIEW.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2007-01-05 Cont ID  
Sent By rchokshi Date 2007-01-05 Time 11:38 Rev Time 0.00
Received By rchokshi Date 2007-01-05 Time 11:38 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By rchokshi Date 2006-08-17 Time 10:21 Rev Time 0.00
Received By rchokshi Date 2006-08-17 Time 09:42 Sent To Z
Notes
2006-08-17 00:00:00FAILED FOR THE FOLLOWING REASONS:
  
 NEED ATLEAST THE FOLLOWING INFO:
  
 1. NOTES ON DRAWING & POLLUTION
 PREVENTION PLANS & NOTES DETAIL, SITE
 BOUNDRY ON THE DRAWINGS BEFORE,DURING,&
 AFTER CONSTRUCTION.
  
 2. STORM WATER CAL.,PERVIOUS, IMPERVIOUS
 AREAS CAL.,RUNOFF WATER
 CAL.,GEOTECHNICAL ENG. REPORT,SFWMD
 PERMIT,
  
 3. PLANS MUST BE APPROVED FOR UTILITY
 REVIEW FROM MANNY G., 45 TH STREET ENG.
 SERVICES, BEFORE WE APPROVE.
  
 4. NEED ALL NOTES ON CIVIL DRAWINGS FOR
 CITY OF WPB STANDARDS FOR DUMPSTER
 ENCLOSURE, SIDEWALK, DRIWAY,PARKINGS,
 HANDICAP PARKING,PER ADA STANDARD AS
 WELL, ETC.,ETC,
  
 5. SITE ELEVATION MAP INCUDING CENTER
 LINE ROAD ELEVATION,CURB ELE.,SIDEWALK
 ELE.,FIRST FLOOR ELEVATION, PARKING ELE.
 ETC., MUST MEET BUILDING CODE.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-05-22 Cont ID  
Sent By mawillia Date 2007-05-22 Time 16:26 Rev Time 0.00
Received By mawillia Date 2007-05-22 Time 16:06 Sent To  
Notes
2007-05-22 16:26:24*****UNSAT*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101 (2003
 EDITION) AND THE FLORIDA FIRE PREVENTION CODE (2004
 EDITION).
  
 5.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 6.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-28 Cont ID  
Sent By mawillia Date 2006-12-28 Time 15:11 Rev Time 0.00
Received By mawillia Date 2006-12-28 Time 15:11 Sent To  
Notes
2006-12-28 16:28:53*****DENIED*****
  
  
  
 1.PLEASE CLARIFY IF THE PROPOSED SCOPE OF WORK AT
 THIS LOCATION IS FOR INTERIOR ALTERATION, BUILDING
 CONSTRUCTION, OR A COMBINATION OF THE TWO.ALSO,
 STAPLES IS LISTED AS BAY 2; ARE THERE ANY OTHER
 TENANTS/BAYS FOR 2029 OKEECHOBEE BOULEVARD?THE USE OF
 SUITE/TENANT/BAY SHOULD ONLY BE USED WHEN THERE ARE
 MORE THAN ONE UNIT WITH THE SAME NUMERICAL ADDRESS.
  
 2.ON DRAWING A10, SHOW/DISPLAY THE NUMERICAL ADDRESS
 ON THE BUILING AS PER WEST PALM BEACH CODE (NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH).
  
 3.DRAWING NUMBER E-1 THRU FS-2 HAVE THE INCORRECT
 NUMERICAL ADDRESS (2015 OKEECHOBEE BLVD.) IN THE TITLE
 SECTION OF THE PLAN.
  
 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101 (2003
 EDITION) AND THE FLORIDA FIRE PREVENTION CODE (2004
 EDITION).
  
 5.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 6.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 7.ON DRAWING AC-2, MAKE CHANGE TO GENERAL AIR
 CONDITIONING NOTE #17 TO REFLECT THAT DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
 8.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By mwennerg Date 2006-10-10 Time 10:44 Rev Time 0.00
Received By mwennerg Date 2006-10-10 Time 10:43 Sent To  
Notes
2006-10-10 10:50:54***DENIED***
  
 1) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO THE BACKGROUND.
 NUMBER TO BE AT LEAST 1" IN WIDTH.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL.
  
 3) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 4) NFPA 13 AND NFPA 72 2003 EDITIONS.
  
 5) PLANS SHOW THE FDC BEING RELOCATED. THE CONNECTION
 SHALL BE LOCATED NOT FURTHER THAN 150' FROM A FIRE
 HYDRANT.
  
 6) DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 13:38 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 13:38 Sent To  
Notes
2007-04-17 13:42:36TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 15:45 Sent To  
Notes
2006-12-21 16:48:25TO "COMM" BD#14
2006-12-06 15:46:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-10 Cont ID  
Sent By mwennerg Date 2006-10-10 Time 11:18 Rev Time 0.00
Received By mwennerg Date 2006-07-11 Time 14:59 Sent To  
Notes
2006-07-27 00:00:00TO "COMM" BD#56
2006-07-11 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-04-26 Cont ID  
Sent By tgordon Date 2007-04-26 Time 12:09 Rev Time 0.35
Received By tgordon Date 2007-04-26 Time 12:08 Sent To  
Notes
2007-04-26 12:09:30*** DENIED ***
 1) THE FIRM'S LICENSE FOR STEVEN L. COHEN AND
 ASSOCIATES, P.A. HAS EXPIRED ON 2-28-2005 AND IS NOW
 NULL AND VOID, PLEASE CORRECT.
  
 2) ENGINEERING DESIGN ASSOCIATES, INC. CERTIFICATE OF
 AUTHORIZATION EXPIRED 2-28-2007, PLEASE CORRECT.
  
 *** FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER. (NULL AND VOID).
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 *** FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-22 Cont ID  
Sent By tgordon Date 2006-12-22 Time 09:37 Rev Time 0.30
Received By tgordon Date 2006-12-22 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-09-19 Time 16:04 Rev Time 0.45
Received By tgordon Date 2006-09-19 Time 16:04 Sent To  
Notes
2006-09-19 00:00:00*** DENIED ***
 1) ARCHITECT NEEDS TO SIGN AND SEAL
 PLANS, PER FS 61G1-16.003 .
  
 2) NEED TO SHOW ENGINEERED ANCHORING
 DETAILS FOR (A/C) CURB TO ROOF AND RTU
 TO CURB, TO WITHSTAND 140 MPH WINDS, PER
 2004 FBC 1609.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS,
 PER 2004 FBC 13-101.1.6 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-05-31 Cont ID  
Sent By kstevens Date 2007-05-31 Time 08:02 Rev Time 0.00
Received By kstevens Date 2007-05-30 Time 17:16 Sent To  
Notes
2007-05-31 09:47:40DENIED...
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE FLORIDA
 STATUTES
  
 ******FROM 1ST REVIEW:
  
 1. OK
  
 2. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION, (BUSINESS NUMBER), IS INDICATED AS
 DELINQUENT PER DBPR WEBSITE. THIS SHALL BE TAKEN CARE
 OF PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1)
 & FS 481.219.
 ****NO RESPONSE, NOT ADDRESSED
  
 3. OK
 4. OK
  
 5. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
  
 6. SHT A-9 DETAIL #2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. OK
 B. OK
 C. OK
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 ******FROM 2ND REVIEW:
  
 1) SHT P-2,NOTE #16 REFERENCE TO A/C CONDENSATE
 DRAIN. SHT A/C-2 ROOF TOP UNIT DETAIL, IS NOT SHOWING
 DISPOSAL OF A/C CONDENSATE. PLEASE CLARIFY.
 ****RESPONSE NOTED, BUT THE CONDENSATE SHALL NOT DRAIN
 ONTO THE ROOF. THE CONDENSATE SHALL BE PIPED TO THE
 ROOF DRAINS AND DRAIN INDIRECTLY OVER THE DRAINS.
 PLEASE SUBMIT A DETAIL SHOWING THE PIPE SUPPORTS
 INDICATING THE SPACING PER TABLE 308.5. INDICATE HOW
 THE SUPPORTS WILL BE ATTACHED TO THE ROOF SHOWING
 COMPLIANCE WITH 140 MPH WINDLOAD REQUIREMENTS. SHOW THE
 ROUTING FOR THE PIPE FOR EACH A/C UNIT ON SHT P-1 OR ON
 A ROOF PLAN SHOWING ALL ROOF DRAINS. SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-13 Cont ID  
Sent By pschmitz Date 2007-01-13 Time 12:03 Rev Time 0.00
Received By pschmitz Date 2007-01-13 Time 12:02 Sent To  
Notes
2007-01-13 12:29:04PAUL SCHMITZ
 [email protected] 2004 PLUMBING CODE
 PLAN REVIEWFBC2004 FUEL GAS CODEPLAN
 REVIEWFBC 2004 CH 11, FL ACESSIBILITY
 CODEAMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED, NEW COMMENTS
  
 1) SHT P-2 , NOTE #16 REFERENCE TO A/C CONDENSATE
 DRAIN.
 SHT A/C -2 ROOF TOP UNIT DETAIL, IS NOT SHOWING
 DISPOSAL OF A/C CONDENSATE.
 PLEASE CLARIFY.
  
 2) SHT P-2WATER HEATER DETAIL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2
 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A
 BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE
 IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE
 WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION
 CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 3) SHT P-2 WATER RISER DIAGRAM
 PLEASE CLARIFY WHAT IS BEING USED AT EACH WATER
 SUPPLIED FIXTURE.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By kstevens Date 2006-10-12 Time 13:30 Rev Time 0.00
Received By kstevens Date 2007-01-05 Time 14:54 Sent To  
Notes
2006-10-12 13:53:05DENIED...
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE FLORIDA
 STATUTES
  
 1. ALL ARCHITECTURAL SHEETS SHALL BE SIGNED, SEALED,
 DATED PER SECTION 106.1, FAC 61G1-16.003 & FS
 481.2055.
  
 2. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION, (BUSINESS NUMBER), IS INDICATED AS
 DELINQUENT PER DBPR WEBSITE. THIS SHALL BE TAKEN CARE
 OF PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1)
 & FS 481.219.
  
 3. SHT A-7 DETAIL #2 SHOWS A URINAL IN THE WOMEN'S
 TOILET ROOM. PLEASE CLARIFY. SECTION 106.1.1. - DETAIL
 #2 ALSO INDICATES A SINGLE DRINKING FOUNTAIN. PLEASE
 SHOW COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 4. SHT A-7 DETAIL #13 NO LAV SHOWN IN THE WOMEN'S
 ACCESSIBLE STALL AS SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE ELEVATION DETAILS WITH THE FLOOR PLAN.
  
 5. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.19.3 CLEAR FLOOR SPACE
 D. 11-4.19.4 EXPOSED PIPES & SURFACES
 E. 11-4.19.5 FAUCETS
  
 6. SHT A-9 DETAIL #2 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
  
 7. ALL PME SHEETS SHALL BE SIGNED, SEALED, DATED.
 SECTION 106.1, FAC 61G15-23.002 & FS 471.025.
  
 8. SHTS P-1 & P-2. FLOOR DRAINS ARE SHOWN ON THE FLOOR
 PLAN IN THE MEN'S & WOMEN'S TOILET ROOMS, THE JANITOR
 ROOM, AND THE LOUNGE ON THE ARCHITECTURAL FLOOR PLANS,
 BUT NOT ON THE PLUMBING SHEETS. PLEASE CORRELATE
 ARCHITECTURAL SHEETS AND THE PLUMBING FLOOR PLAN AND
 SANITARY RISER DIAGRAM. SECTION 106.1.1.
  
 9. SHTS P-1 & P-2 NO WATER OR SANITARY PIPING SHOWN TO
 THE LOUNGE SINK. PLEASE CLARIFY. SECTION 106.1.1.
  
 10. HOT WATER SUPPLY IS REQUIRED FOR THE JANITOR SINK
 PER SECTION 607.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]