Plan Review Details - Permit 06070443
Plan Review Stops For Permit 06070443
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-27 Cont ID  
Sent By mjacobs Date 2006-09-27 Time 14:31 Rev Time 0.00
Received By mjacobs Date 2006-09-27 Time 13:37 Sent To  
Notes
2006-09-27 00:00:00BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-28 Cont ID  
Sent By mjacobs Date 2006-08-28 Time 14:26 Rev Time 0.00
Received By mjacobs Date 2006-08-28 Time 11:09 Sent To P
Notes
2006-08-28 00:00:00 
  
 1) 61G15-23.002 (2) IF PRACTTICING
 THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME,ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF
 THE ENGINEERING BUSINESS ON EACH SHEET.
 A TITLE BLOCK ON EACH SHEET CONTAINING
 THE PRINTED NAME,ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE,
 THE NAME AND LICENSE NUMBER OF THE
 ENGINEER, AND THE NAME,ADDRESS AND
 CERTIFICATE OF AUTHORIZATION MNUMBER OF
 THE ENGINEERING BUSINESS WILL SATISFY
 THIS REQUIREMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By mjacobs Date 2006-07-20 Time 17:46 Rev Time 0.00
Received By mjacobs Date 2006-07-20 Time 17:00 Sent To PC
Notes
2006-07-20 00:00:00 
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 FEFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SEERVICES PER
 108.3*
  
 3) THE SQUARE FOOTAGE OF THE POOL DECK
 IS REQUIRED FOR THE CLAIMED VALUE OF THE
 WORK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-26 Cont ID  
Sent By dpalmer Date 2006-09-26 Time 10:19 Rev Time 0.00
Received By dpalmer Date 2006-09-26 Time 09:23 Sent To P
Notes
2006-09-26 00:00:00SEE ELECTRICAL RISER DIAGRAM PROVIDED
 BY THE ELEC CONT ATTACHED.
 LANS NOW DONE AND SUBMITTED BY A NEW
 ENGINEERING FIRM WHICH IS LICENSED AND
 ALL LICENSURE IS CURRENT WITH THE STATE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 12:29 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 12:18 Sent To B
Notes
2006-08-27 00:00:00**** 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE MISSING PANEL
 SCHEDULE FOR NEW POOL PANEL SHOWING THE
 OCP FOR EACH OF THE NEW BRANCH CIRCUITS
 ON RISER/WIRING DIAGRAM SUBMITTED.
 408.4,310.16,240.4
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PLANS ARE STILL
 MISSING THE REQUIRED LICENSURE
 INFORMATION REQUIRED PER FS 471.023, AND
 FAC 61G15-23.002
 PLEASE KNOW, THIS COMMENT IS NOT FOR THE
 LICENSE NUMBER OF THE PE. THIS IS FOR
 THE FIRM AS LISTED ON TITLE BLOCK.
 THIS OFFICE HAS LEFT MESSAGES FOR THE
 RETURNED CALLS FROM THE ENGINEERING FIRM
 WITH RESPECT TO THIS COMMENT.
 PLEASE CONTACT THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND DEPARTMENT OF
 BUSINESS AND PROFESSIONLA REGULATION IF
 THERE ARE ANY FURTHER QUESTIONS.
 ** PLEASE ALSO SEE NEW SIGNED PLANS ARE
 DATED AS THE PREVIOUS PLANS WHICH WERE
 DATED ON 7/5/06, HOW IS THE DATE THE
 SAME WHEN THE PLANS HAVE BEEN REVISED.
 PLEASE SEE FS 471.025 AND FAC AS NOED
 ABOVE AS THE ENGINEER OF RECORD IS
 REQUIRED TO DATE THE PLANS EACH TIME
 THEY ARE BEING SIGNED/REVISED.
 PLEASE KNOW, TWO SETS OF PLANS, ONE
 ORIGINAL AND ONE REVISED IS BEING
 RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW FROM THE FBPE'S AND LEGAL COUNSEL
 TO THE BOARD.
  
  
 ** PLEASE SUBMIT TWO COMPLETE SETS OF
 REVISED PLANS, PLEASE BE SURE TO ADDRESS
 ALL COMMENTS ABOVE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 19:13 Sent To B
Notes
2006-08-11 00:00:00********* UNSAT2ND REVIEW ***********
  
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 RENIEW WHICH STILL NEED TO BE ADDRESS.
 NOTES BELOW ARE TAKEN DIRECTLY FROM THE
 PERVIOUS REVIEW.
  
 ** PLEASE KNOW, PLANS SHALL BE SPECIFIC
 TO EACH SITE AND DESIGN.
  
 1) NOTE: NO, NOTHING SUBMITTED , SAME
 COMMENT APPLIES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR ALL EXISTING LOADS AND
 NEW LOADS ADDED.
 PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE.
 220.31B,215.5, FBC ADMIN SECT 106.1.2
  
 2) NOTE: NO, SAME COMMENT. RISER AND
 CALCULATIONS SUBMNITTED ARE NOT FROM THE
 NEC/NFPA-70. PLEASE SEE 2002 NEC FOR
 LOAD CALCULATIONS ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS INDICATE A NEW
 PANEL, HOWEVER NO INFORMATION ON FEEDERS
 AND OCP FROM SERVICE PANEL.
 240.4,310.16,215.5 ETC
  
 3) NOTE: NO, SAME NOTE. RISER /CALCS
 SUBMITTED ARE NOT DONE TOMIN STANDARDS
 FROM THE NEC. 2002 220
 PLEASE SEE NEW NOTES ALSO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A PANEL SCHEDULE
 FOR THE NEW PROPOSED PANEL SHOWING ALL
 CONDUCTOR SIZES, OCP, ETC.
 408.4,106.1.2, 106.3.5.1.2
  
 4) NOTE: NO. PLEASE SEE HAND DRAWN
 CHNAGES MADE TO PLASN WHICH ARE SIGNED,
 DATED AND SEALED BY AND ENGINEER IS NOT
 PERMITTED UNDER FLORIDA STATUES 471.025,
 FLORIDA ADMINSITRATIVE CODE 61G15-23.002
 PLEASE ADDRESS COMMENT ON COMPELTE NEW
 SHEETS, AS THE PLANS SUBMITTED HAVE BEEN
 "VOIDED" INCLUDING SHEETS STAMPED BY THE
 PLUMBING REVIEWER.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE WIRING DIAGRAM DOES
 NOT INCLUDE THE HEAT PUMP? WIRE SIZES?
 CONDUIT? ETC.
 PLEASE COMPLETE WIRING DIAGRAM.
 106.1.2
  
 5) NOTE: NO, VALUE WAS SHOWN ON
 APPLICATION TO $22K, HOWEVER VALUE STILL
 SEEMS LOW, AN ADJUSTMENT MAY BE DONE PER
 MARSHALL'S & SWIFT GUIDE FOR FAIR MARKET
 VALUE.
 PLEASE PROVIDE A SIGNED CONTRACT FOR ALL
 SCOPE OF WORK INCLUDED ON APPLICATION.
 FBC 108.3
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, VALUE ON PERMIT
 APPLICATION IS VERY LOW FOR A POOL OF
 THIS SIZE. PLEASE ADJUST VALUE OR PLEASE
 KNOW ONE WILL BE ASSESSED BY THIS OFFICE
 BASED ON THE "MARSHALL'S / SWIFT" GUIDE
 AS ADOPTED INTO THE FBC PER 108.3
  
 ** WHEN REQ'D**
 6) NOTE: PLEASE SEE FAC 61G17 AND FS
 421.025, PLEASE SEE THAT THE SURVEY
 SHALL CONTAIN THE RAISED SEAL AND THE
 ORIGINAL SIGNATURE AND DATE.
  
 ** NEW NOTES **
  
 7) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS AS REQUIRED UNDER FAC
 61G15-23.002 AND FS 471.023.
 THIS COMMENT WAS NOT MADE ON PREVIOUS
 REVIEW , HOWEVER IS REQUIRED.
 A)MISSING THE PRINTED NAME AND LICENSE #
 OF SAID ENGINEER.
 B)MISSING THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR FIRM AS LISTED.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANCE COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 9) NOTE: PLEASE KNOW, ANY ADDTIONAL
 INFORMATION SUCH AS LOAD CALCULATIONS ,
 ETC WHEN NOT DONE BY THE ENGINEER OF
 RECORD, MUST CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR SAID PLANS. FCB 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 07:33 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 07:19 Sent To P
Notes
2006-07-20 00:00:00********* UNSAT ***********
  
 ** PLEASE KNOW, PLANS SHALL BE SPECIFIC
 TO EACH SITE AND DESIGN.
  
 1) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR ALL EXISTING LOADS AND
 NEW LOADS ADDED.
 PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE.
 220.31B,215.5, FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SEE PLANS INDICATE A NEW
 PANEL, HOWEVER NO INFORMATION ON FEEDERS
 AND OCP FROM SERVICE PANEL.
 240.4,310.16,215.5 ETC
  
 3) NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 FOR THE NEW PROPOSED PANEL SHWOING ALL
 CONDUCTOR SIZES, OCP, ETC.
 408.4,106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE WIRING DIAGRAM DOES
 NOT INCLUDE THE HEAT PUMP? WIRE SIZES?
 CONDUIT? ETC.
 PLEASE COMPLETE WIRING DIAGRAM.
 106.1.2
  
 5) NOTE: PLEASE KNOW, VALUE ON PERMIT
 APPLICATION IS VERY LOW FOR A POOL OF
 THIS SIZE. PLEASE ADJUST VVALUE OR PLEAS
 KNOW ONE WILL BE ASSESSED BY THIS OFFICE
 BASED ON THE "MARSHALL'S / SWIFT" GUIDE
 AS ADOPTED INTO THE FBC PER 108.3
  
 ** WHEN REQ'D**
 6) NOTE: PLEASE SEE FAC 61G17 AND FS
 421.025, PLEASE SEE THAT THE SURVEY
 SHALL CONTAIN THE RAISED SEAL AND THE
 ORIGINAL SIGNATURE AND DATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 15:13 Sent To E
Notes
2006-09-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 10:15 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 10:15 Sent To Z
Notes
2006-09-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 18:39 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 18:39 Sent To E
Notes
2006-08-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-10 Cont ID  
Sent By mmiller Date 2006-08-10 Time 15:19 Rev Time 0.00
Received By mmiller Date   Time   Sent To E
Notes
2006-08-10 00:00:00SENT TO " DP" DESK/ RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 15:37 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 15:37 Sent To Z
Notes
2006-08-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 11:52 Sent To E
Notes
2006-07-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-20 Time   Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 16:17 Sent To  
Notes
2006-07-11 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-26 Cont ID  
Sent By mperson Date 2006-09-26 Time 16:19 Rev Time 0.33
Received By mperson Date 2006-09-26 Time 16:19 Sent To B
Notes
2006-09-26 00:00:00 
  
 ******PROVISO******
 FBC-2004 SEC. 424.2.12.1, OR FBCR-2004
 SEC. R4101.12.1 PRESSURE TESTS. PER
 MANUFACTURE RECOMMENDATIONS, NO AIR TEST
 SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-31 Cont ID  
Sent By mperson Date 2006-08-31 Time 11:14 Rev Time 0.33
Received By mperson Date 2006-08-31 Time 11:14 Sent To E
Notes
2006-08-31 00:00:00******DENIED******
 REFERENCE: FBC-2004, SEC. 424.2 OR
 FBRC-2004 SEC. 4101, SWIMMING POOLS:
 FLORIDA ADMINISTRATIVE CODE:
  
 THE FOLOWING INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW:
  
 1)FAC-61G15-23.002 SEAL SIGNATURE AND
 DATE SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-20 Cont ID  
Sent By mperson Date 2006-07-20 Time 14:37 Rev Time 0.33
Received By mperson Date 2006-07-20 Time 14:37 Sent To B
Notes
2006-07-20 00:00:00 
  
  
 ******PROVISO******
 1. LABEL VENT: "POOL SAFETY DEVICE - DO
 NOT HANDLE"
 2. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS.
 3. FBC-2004 SEC. 13-612.1.ABC.2.3.3 TIME
 CLOCKS SHALL BE INSTALLED ON PRIVATE
 POOLS.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2006-09-28 Cont ID  
Sent By mmclean Date 2006-09-28 Time 10:31 Rev Time 0.00
Received By mmclean Date 2006-09-28 Time 10:31 Sent To  
Notes
2006-09-28 00:00:00NOTE: THE PROPOSED POOL EQUIPMENT SHALL
 NOT BE CLOSER THAN 10FT FROM THE REAR
 PROPERTY LINE.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-09-20 Cont ID  
Sent By mmclean Date 2006-09-20 Time 17:43 Rev Time 0.00
Received By mmclean Date 2006-09-20 Time 17:43 Sent To I
Notes
2006-09-20 00:00:00DENIED, (NEW SHEETS)
 1. PLEASE SHOW THE LOCATION OF THE POOL
 EQUIPMENT ON TWO COPY OF SURVEYS.
 2. THE NEW COPIES DOES NOT SHOW THE POOL
 EQUIPMENT LOCATION ON SURVEYS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By mmclean Date 2006-08-08 Time 09:43 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 09:43 Sent To I
Notes
2006-08-09 00:00:00NOTE:
 THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 10FT FROM REAR PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 14:45 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 14:45 Sent To I
Notes
2006-07-16 00:00:00DENIED,
 1. MUST SHOW THE LOCATION OF THE POOL
 EQUIPMENT ON TWO COPY OF SUVEYS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720