| Plan Review Stops For Permit 06070443 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-27 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-27 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2006-09-27 00:00:00 | BUILDING PROVISO: | | | TO BE IN PLACE AT C.O.: | | | | | | 1) 424.2.17.1 OUTDOOR SWIMMING POOLS. | | | OUTDOOR SWIMMING POOLS SHALL BE PROVIDED | | | WITH A BARRIER COMPLYING WITH | | | 424.2.17.1.1 THROUGH 424.2.17.1.14. | | | | | | 424.2.17.1.5 CHILD SAFETY BARRIER | | | ASTM D5034 100 LB TENSILE STRNGTH | | | ASTM D3787 150 LB BALL BURST | | | STRENGTH | | | | | | 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED. | | | SPAS AND HEATED SWIMMING POOLS SHALL BE | | | EQUIPPED WITH A COVER DESIGNED TO | | | MINIMIZE HEAT LOSS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-08-28 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-08-28 |
Time |
11:09 |
Sent To |
P |
|
| Notes |
| 2006-08-28 00:00:00 | | | | | | | 1) 61G15-23.002 (2) IF PRACTTICING | | | THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME AND LICENSE NUMBER, | | | AS WELL AS, THE NAME,ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF | | | THE ENGINEERING BUSINESS ON EACH SHEET. | | | A TITLE BLOCK ON EACH SHEET CONTAINING | | | THE PRINTED NAME,ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, | | | THE NAME AND LICENSE NUMBER OF THE | | | ENGINEER, AND THE NAME,ADDRESS AND | | | CERTIFICATE OF AUTHORIZATION MNUMBER OF | | | THE ENGINEERING BUSINESS WILL SATISFY | | | THIS REQUIREMENT. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-07-20 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-07-20 |
Time |
17:00 |
Sent To |
PC |
|
| Notes |
| 2006-07-20 00:00:00 | | | | 1) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 2) THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | COST EXCLUDING LAND VALUE. OUR VALUATION | | | FEFERENCE IS ICC (BVD), MARSHALL-SWIFT | | | AND MEANS COST ANALYSIS SEERVICES PER | | | 108.3* | | | | | | 3) THE SQUARE FOOTAGE OF THE POOL DECK | | | IS REQUIRED FOR THE CLAIMED VALUE OF THE | | | WORK. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-26 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-26 |
Time |
09:23 |
Sent To |
P |
|
| Notes |
| 2006-09-26 00:00:00 | SEE ELECTRICAL RISER DIAGRAM PROVIDED | | | BY THE ELEC CONT ATTACHED. | | | LANS NOW DONE AND SUBMITTED BY A NEW | | | ENGINEERING FIRM WHICH IS LICENSED AND | | | ALL LICENSURE IS CURRENT WITH THE STATE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-27 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-27 |
Time |
12:18 |
Sent To |
B |
|
| Notes |
| 2006-08-27 00:00:00 | **** 3RD REVIEW *** | | | | | | 1) NOTE: PLEASE SEE MISSING PANEL | | | SCHEDULE FOR NEW POOL PANEL SHOWING THE | | | OCP FOR EACH OF THE NEW BRANCH CIRCUITS | | | ON RISER/WIRING DIAGRAM SUBMITTED. | | | 408.4,310.16,240.4 | | | FBC 106.1.2 | | | | | | 2) NOTE: PLEASE SEE PLANS ARE STILL | | | MISSING THE REQUIRED LICENSURE | | | INFORMATION REQUIRED PER FS 471.023, AND | | | FAC 61G15-23.002 | | | PLEASE KNOW, THIS COMMENT IS NOT FOR THE | | | LICENSE NUMBER OF THE PE. THIS IS FOR | | | THE FIRM AS LISTED ON TITLE BLOCK. | | | THIS OFFICE HAS LEFT MESSAGES FOR THE | | | RETURNED CALLS FROM THE ENGINEERING FIRM | | | WITH RESPECT TO THIS COMMENT. | | | PLEASE CONTACT THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS AND DEPARTMENT OF | | | BUSINESS AND PROFESSIONLA REGULATION IF | | | THERE ARE ANY FURTHER QUESTIONS. | | | ** PLEASE ALSO SEE NEW SIGNED PLANS ARE | | | DATED AS THE PREVIOUS PLANS WHICH WERE | | | DATED ON 7/5/06, HOW IS THE DATE THE | | | SAME WHEN THE PLANS HAVE BEEN REVISED. | | | PLEASE SEE FS 471.025 AND FAC AS NOED | | | ABOVE AS THE ENGINEER OF RECORD IS | | | REQUIRED TO DATE THE PLANS EACH TIME | | | THEY ARE BEING SIGNED/REVISED. | | | PLEASE KNOW, TWO SETS OF PLANS, ONE | | | ORIGINAL AND ONE REVISED IS BEING | | | RETAINED BY THIS OFFICE FOR POSSIBLE | | | REVIEW FROM THE FBPE'S AND LEGAL COUNSEL | | | TO THE BOARD. | | | | | | | | | ** PLEASE SUBMIT TWO COMPLETE SETS OF | | | REVISED PLANS, PLEASE BE SURE TO ADDRESS | | | ALL COMMENTS ABOVE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-11 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-11 |
Time |
19:13 |
Sent To |
B |
|
| Notes |
| 2006-08-11 00:00:00 | ********* UNSAT2ND REVIEW *********** | | | | | | | | | ** PLEASE SEE SOME NOTE FROM PREVIOUS | | | RENIEW WHICH STILL NEED TO BE ADDRESS. | | | NOTES BELOW ARE TAKEN DIRECTLY FROM THE | | | PERVIOUS REVIEW. | | | | | | ** PLEASE KNOW, PLANS SHALL BE SPECIFIC | | | TO EACH SITE AND DESIGN. | | | | | | 1) NOTE: NO, NOTHING SUBMITTED , SAME | | | COMMENT APPLIES. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR ALL EXISTING LOADS AND | | | NEW LOADS ADDED. | | | PLEASE INDICATE THE SIZE OF THE EXISTING | | | SERVICE. | | | 220.31B,215.5, FBC ADMIN SECT 106.1.2 | | | | | | 2) NOTE: NO, SAME COMMENT. RISER AND | | | CALCULATIONS SUBMNITTED ARE NOT FROM THE | | | NEC/NFPA-70. PLEASE SEE 2002 NEC FOR | | | LOAD CALCULATIONS ETC | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE PLANS INDICATE A NEW | | | PANEL, HOWEVER NO INFORMATION ON FEEDERS | | | AND OCP FROM SERVICE PANEL. | | | 240.4,310.16,215.5 ETC | | | | | | 3) NOTE: NO, SAME NOTE. RISER /CALCS | | | SUBMITTED ARE NOT DONE TOMIN STANDARDS | | | FROM THE NEC. 2002 220 | | | PLEASE SEE NEW NOTES ALSO. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE PROVIDE A PANEL SCHEDULE | | | FOR THE NEW PROPOSED PANEL SHOWING ALL | | | CONDUCTOR SIZES, OCP, ETC. | | | 408.4,106.1.2, 106.3.5.1.2 | | | | | | 4) NOTE: NO. PLEASE SEE HAND DRAWN | | | CHNAGES MADE TO PLASN WHICH ARE SIGNED, | | | DATED AND SEALED BY AND ENGINEER IS NOT | | | PERMITTED UNDER FLORIDA STATUES 471.025, | | | FLORIDA ADMINSITRATIVE CODE 61G15-23.002 | | | PLEASE ADDRESS COMMENT ON COMPELTE NEW | | | SHEETS, AS THE PLANS SUBMITTED HAVE BEEN | | | "VOIDED" INCLUDING SHEETS STAMPED BY THE | | | PLUMBING REVIEWER. | | | | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE SEE WIRING DIAGRAM DOES | | | NOT INCLUDE THE HEAT PUMP? WIRE SIZES? | | | CONDUIT? ETC. | | | PLEASE COMPLETE WIRING DIAGRAM. | | | 106.1.2 | | | | | | 5) NOTE: NO, VALUE WAS SHOWN ON | | | APPLICATION TO $22K, HOWEVER VALUE STILL | | | SEEMS LOW, AN ADJUSTMENT MAY BE DONE PER | | | MARSHALL'S & SWIFT GUIDE FOR FAIR MARKET | | | VALUE. | | | PLEASE PROVIDE A SIGNED CONTRACT FOR ALL | | | SCOPE OF WORK INCLUDED ON APPLICATION. | | | FBC 108.3 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE KNOW, VALUE ON PERMIT | | | APPLICATION IS VERY LOW FOR A POOL OF | | | THIS SIZE. PLEASE ADJUST VALUE OR PLEASE | | | KNOW ONE WILL BE ASSESSED BY THIS OFFICE | | | BASED ON THE "MARSHALL'S / SWIFT" GUIDE | | | AS ADOPTED INTO THE FBC PER 108.3 | | | | | | ** WHEN REQ'D** | | | 6) NOTE: PLEASE SEE FAC 61G17 AND FS | | | 421.025, PLEASE SEE THAT THE SURVEY | | | SHALL CONTAIN THE RAISED SEAL AND THE | | | ORIGINAL SIGNATURE AND DATE. | | | | | | ** NEW NOTES ** | | | | | | 7) NOTE: PLEASE SEE MISSING INFORMATION | | | ON TITLE BLOCKS AS REQUIRED UNDER FAC | | | 61G15-23.002 AND FS 471.023. | | | THIS COMMENT WAS NOT MADE ON PREVIOUS | | | REVIEW , HOWEVER IS REQUIRED. | | | A)MISSING THE PRINTED NAME AND LICENSE # | | | OF SAID ENGINEER. | | | B)MISSING THE CERTIFICATE OF | | | AUTHORIZATION NUMBER FOR FIRM AS LISTED. | | | | | | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS AND | | | REPEAT CODE COMPLIANCE COMMENTS. | | | THIS IS ONLY A NOTICE GIVEN AT THIS | | | TIME. | | | | | | 9) NOTE: PLEASE KNOW, ANY ADDTIONAL | | | INFORMATION SUCH AS LOAD CALCULATIONS , | | | ETC WHEN NOT DONE BY THE ENGINEER OF | | | RECORD, MUST CONTAIN THE PRINTED NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR SAID PLANS. FCB 106.1.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-20 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-20 |
Time |
07:19 |
Sent To |
P |
|
| Notes |
| 2006-07-20 00:00:00 | ********* UNSAT *********** | | | | | | ** PLEASE KNOW, PLANS SHALL BE SPECIFIC | | | TO EACH SITE AND DESIGN. | | | | | | 1) NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR ALL EXISTING LOADS AND | | | NEW LOADS ADDED. | | | PLEASE INDICATE THE SIZE OF THE EXISTING | | | SERVICE. | | | 220.31B,215.5, FBC ADMIN SECT 106.1.2 | | | | | | 2) NOTE: PLEASE SEE PLANS INDICATE A NEW | | | PANEL, HOWEVER NO INFORMATION ON FEEDERS | | | AND OCP FROM SERVICE PANEL. | | | 240.4,310.16,215.5 ETC | | | | | | 3) NOTE: PLEASE PROVIDE A PANEL SCHEDULE | | | FOR THE NEW PROPOSED PANEL SHWOING ALL | | | CONDUCTOR SIZES, OCP, ETC. | | | 408.4,106.1.2, 106.3.5.1.2 | | | | | | 4) NOTE: PLEASE SEE WIRING DIAGRAM DOES | | | NOT INCLUDE THE HEAT PUMP? WIRE SIZES? | | | CONDUIT? ETC. | | | PLEASE COMPLETE WIRING DIAGRAM. | | | 106.1.2 | | | | | | 5) NOTE: PLEASE KNOW, VALUE ON PERMIT | | | APPLICATION IS VERY LOW FOR A POOL OF | | | THIS SIZE. PLEASE ADJUST VVALUE OR PLEAS | | | KNOW ONE WILL BE ASSESSED BY THIS OFFICE | | | BASED ON THE "MARSHALL'S / SWIFT" GUIDE | | | AS ADOPTED INTO THE FBC PER 108.3 | | | | | | ** WHEN REQ'D** | | | 6) NOTE: PLEASE SEE FAC 61G17 AND FS | | | 421.025, PLEASE SEE THAT THE SURVEY | | | SHALL CONTAIN THE RAISED SEAL AND THE | | | ORIGINAL SIGNATURE AND DATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-09-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-23 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-23 |
Time |
15:13 |
Sent To |
E |
|
| Notes |
| 2006-09-23 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-15 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-15 |
Time |
10:15 |
Sent To |
Z |
|
| Notes |
| 2006-09-15 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-08-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-22 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-22 |
Time |
18:39 |
Sent To |
E |
|
| Notes |
| 2006-08-22 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-08-10 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
|
Time |
|
Sent To |
E |
|
| Notes |
| 2006-08-10 00:00:00 | SENT TO " DP" DESK/ RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-08-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-03 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-03 |
Time |
15:37 |
Sent To |
Z |
|
| Notes |
| 2006-08-03 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-18 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-18 |
Time |
11:52 |
Sent To |
E |
|
| Notes |
| 2006-07-18 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-07-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-11 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-09-26 |
Time |
16:19 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-09-26 |
Time |
16:19 |
Sent To |
B |
|
| Notes |
| 2006-09-26 00:00:00 | | | | | | | ******PROVISO****** | | | FBC-2004 SEC. 424.2.12.1, OR FBCR-2004 | | | SEC. R4101.12.1 PRESSURE TESTS. PER | | | MANUFACTURE RECOMMENDATIONS, NO AIR TEST | | | SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-31 |
Time |
11:14 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-08-31 |
Time |
11:14 |
Sent To |
E |
|
| Notes |
| 2006-08-31 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004, SEC. 424.2 OR | | | FBRC-2004 SEC. 4101, SWIMMING POOLS: | | | FLORIDA ADMINISTRATIVE CODE: | | | | | | THE FOLOWING INFORMATION IS REQUIRED FOR | | | PLUMBING PLAN REVIEW: | | | | | | 1)FAC-61G15-23.002 SEAL SIGNATURE AND | | | DATE SHALL BE AFFIXED: | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME, ADDRESS, | | | AND LICENSE NUMBER ON EACH SHEET. IF | | | PRACTICING THROUGH A DULY AUTHORIZED | | | ENGINEERING BUSINESS, ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME LICENSE NUM- | | | BER, AS WELL AS, THE NAME, ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF | | | THE ENGNEERING BUSINESS ON EACH SHEET. | | | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN | | | RESUBMITTING, PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-07-20 |
Time |
14:37 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2006-07-20 |
Time |
14:37 |
Sent To |
B |
|
| Notes |
| 2006-07-20 00:00:00 | | | | | | | | | | ******PROVISO****** | | | 1. LABEL VENT: "POOL SAFETY DEVICE - DO | | | NOT HANDLE" | | | 2. FBC-2004 SEC. 424.2.12.1, OR | | | FBCR-2004 SEC. R4101.12.1 PRESSURE | | | TESTS. PER MANUFACTURE RECOMMENDATIONS, | | | NO AIR TEST SHALL BE APPROVED FOR PVC | | | PIPE AND FITTINGS. | | | 3. FBC-2004 SEC. 13-612.1.ABC.2.3.3 TIME | | | CLOCKS SHALL BE INSTALLED ON PRIVATE | | | POOLS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-09-28 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-09-28 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | NOTE: THE PROPOSED POOL EQUIPMENT SHALL | | | NOT BE CLOSER THAN 10FT FROM THE REAR | | | PROPERTY LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-09-20 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-09-20 |
Time |
17:43 |
Sent To |
I |
|
| Notes |
| 2006-09-20 00:00:00 | DENIED, (NEW SHEETS) | | | 1. PLEASE SHOW THE LOCATION OF THE POOL | | | EQUIPMENT ON TWO COPY OF SURVEYS. | | | 2. THE NEW COPIES DOES NOT SHOW THE POOL | | | EQUIPMENT LOCATION ON SURVEYS. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-08-08 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-08-08 |
Time |
09:43 |
Sent To |
I |
|
| Notes |
| 2006-08-09 00:00:00 | NOTE: | | | THE PROPOSED POOL EQUIPMENT SHALL NOT BE | | | CLOSER THAN 10FT FROM REAR PROPERTY | | | LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-16 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-16 |
Time |
14:45 |
Sent To |
I |
|
| Notes |
| 2006-07-16 00:00:00 | DENIED, | | | 1. MUST SHOW THE LOCATION OF THE POOL | | | EQUIPMENT ON TWO COPY OF SUVEYS. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|