| 2006-09-11 00:00:00 | *** UNSAT2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW AND SOME NEW COMMENTS |
| | DUE TO REVISED RISER BEING SUBMITTED |
| | NEED TO BE ADDRESSED. PLEASE SEE NOTES |
| | BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW WITH NEW NOTES ADDED BELOW. |
| | |
| | 1) NOTE: NO, PLEASE SEERISER DOES NOT |
| | INDICATE WHERE THIS FEED IS GOING AFTER |
| | THE ATS? |
| | PLEASE SEE NO OVER VIEW WAS SUBMITTED |
| | SHOWING THE LOCATION OF ALL THE SERVICE |
| | EQUIPMENT. |
| | PLEASE SEE THE ATS AS SUBMITTED AND |
| | SHOWN ON RISER DOES NOT CONTAIN THE |
| | REQUIRED DISONNECTING MEANS FOR THE |
| | FEEDERS COMING FROM THE GENERATOR. |
| | PLEASE KNOW, THIS MAY BE DONE BY MORE |
| | THAN ONE WAY, HOWEVER PLEASE SEE GENERAC |
| | NOW DOES MAKE A NEW ATS WHICH MEETS CODE |
| | COMPLIANCE FOR THIS WHICH PROVIDES THE |
| | DISOCNNECTING MEANS FOR THE FPL/LINE |
| | SIDE AND A DISCONNECT FOR THE FEEDERS |
| | LOCATED IN THE SAME ATS. (RTSE). |
| | ** THIS IS NO WAY THE ONLY METHID, AND |
| | IS ONLY ONE IDEA). |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE A RISER DIAGRAM |
| | INCLUDING ALL CONDUCTOR SIZES ANDHOW |
| | THIS WILL TIE INTO THE EXISTING |
| | SERVICE. |
| | PLEASE INDICATE OCP AND HOW THE NEW SE |
| | RATED ATS WILL BE FED. WHY ISTHIS UNIT |
| | SE RATED? PLEASE KNOW, THE METER MAIN IS |
| | STILL THE FIRST MEANS OF SERVICE |
| | DISCONNECT AND IT IS UNCLEAR HOW |
| | FEEDERS, OCP IS BEING CONNECTED AS SHOWN |
| | FROM EXISTING. |
| | PLEASE KNOW, IF THE NEW SE RATED ATS |
| | WILL BE THE NEW MAIN, MAY NOT PLACE LINE |
| | AND LOAD IN THE SMAE RACEWAY AND MAY NOT |
| | HAVE LINE IN W/ BRANCH CIRCUITS.230.7 |
| | PLEASE CLARIFY AND SHOW THE DISCONNECT |
| | REQUIRED FOR FEEDERS FROM GEN TO HOUSE |
| | AND BEING GROUPED WITH THE EXISTING |
| | MAINS/DISCONNECTS. |
| | PLEASE SHOW AN OVERVIEW FOR LOCATION OF |
| | ALL EQUIPMENT ON PROPERTY |
| | 240.4,310.16,215.5,225.31-225.39 |
| | |
| | 2) NOTE:OK, HOWEVER PLEASE VERIFY HOW |
| | LOAD FOR HEAT WENT DOWN? PLEASE SEE THE |
| | KW RATING AS SHOWN DOES NOT CORRELATE TO |
| | ANY COMMON HEAT STRIP.?? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR HOUSE INCLUDING ALL |
| | LOADS.PLEASE KNOW ANY HEAT LOADS (AHU) |
| | SHALL BE AT 100%OR PLEASE PROVIDE A |
| | DETAIL ON HOW LOAD SHEDDING WILL TAKE |
| | PLACE. |
| | 220.31 |
| | |
| | 3) NOTE: OK/NO, PLEASE SEE THE SETBACKS |
| | APPEAR TO BE OK, HOWEVER NO SPECS WERE |
| | SUBMITTED WHICH INDICATE THE MINIMUM |
| | CLEARENCES? PLEASE KNOW THE MIN REQUIRED |
| | WOULD BE 5FT. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE SETBACKS OF GEN |
| | FOR ALL SIDES FROM PROPERTY , AND ANY |
| | STRUCTURES. |
| | PLEASE SEE THAT THE MANUFACTURES SPECS |
| | SHOULD INCLUDE THE MIN CLEARENCES |
| | RECOMMENED BY MANUFACTURE. |
| | IT IS THE UNDERSTANDING FROM THE OFFICE |
| | FROM THE LTRS OBTAIN FROM THIS |
| | MANUFACTURE A MIN OF 5FT IS REQUIRED. |
| | |
| | 4) NOTE: NO, THIS WAS NOT DONE AND FOUR |
| | DIFFERENT ATS MODELS,ONLY TWO COULD |
| | APPLY. PLEASE KNOW, AS THIS UNIT SEEMS |
| | TO BE TAKING THE PLACE OF THE MAIN FOR |
| | THE SERVICE, IT WOULD BE REQUIRED TO BE |
| | SE RATED. PLEASE SEE HOWEVER THE ABOVE |
| | COMMENT FOR THE REQUIRED DISCONNECTING |
| | MEANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO HIGH LIGHT |
| | UNITS/ EQUIPMENT BEING USED ON SPECS. |
| | |
| | 5) NOTE: NO, THIS WAS NOTE TO SEE BBLDG |
| | COMMENTS, HOWEVER PLEASE SEE THERE ARE |
| | THREE DIFFERENT GENERATOR SLABS SHOWN ON |
| | PACKAGE. PLEASE SEE SURVEY SHOWS A SLAB |
| | WHICH DOES NOT CORRELATE TO EITHER THE |
| | ORIGINAL OR THE NEW ENGINEERING SLAB |
| | DETAILS SUBMITTED. |
| | PLEASE CORRELATE. THE NEW DETAIL |
| | SUBMITTED PROVIDES THE STRUCTURAL |
| | ATTACHMENT DETAIL REQUIRED PER NFPA-110 |
| | CHAPTER 7. |
| | |
| | ** PREVIOUS REVIEW NOTE** PLEASE SEE |
| | BLDG REVIEW NOTES, |
| | AS INFORMATION IS REQUIRED ON HOW THE |
| | GENERATOR WILL BE ATTACHED TO THE SLAB. |
| | PLEASE ALSO PROVIDE MORE INFORMATION ON |
| | SLAB. |
| | |
| | ** NEW NOTE ** |
| | |
| | 6) NOTE: PLEASE SEE THE NOTICE OF |
| | COMMENCMENT PREVIOUSLY SUBMITTED AHS NOW |
| | EXPIRED PER FS 713.13(2). PLEASE KNOW, |
| | IF WORK HAS NOT COMMENCED WITHIN 90 DAYS |
| | OF RECORDING NOC, THE NOC BECOMES VOID |
| | AND MUST BE RE-RECORDED. |
| | THIS IS ONLY REQUIRED BEFORE PICKING UP |
| | PERMIT. |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT CODE COMPLIANT |
| | COMMENTS WITH RESPECT TO THE DESIGN |
| | PROFESSIONALS. PLEASE KNOW THIS IS ONLY |
| | A NOTICE GIVEN AT THIS TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |