Plan Review Details - Permit 06070435
Plan Review Stops For Permit 06070435
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 08:40 Rev Time 0.00
Received By alange Date 2006-09-26 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-27 Cont ID  
Sent By alange Date 2006-07-27 Time 08:03 Rev Time 0.33
Received By alange Date 2006-07-27 Time 08:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 10:17 Sent To P
Notes
2006-12-06 10:40:37OK, ONLY REDLINED FOR NEUTRALS AND GRNDS TO SEPARATED
 IN THE EXISTING MCB PANEL PER 250.6, 250.24B.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-01 Cont ID  
Sent By dpalmer Date 2006-11-01 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2006-11-01 Time 16:26 Sent To P
Notes
2006-11-01 16:37:21** UNSAT 3RD REVIEW **
  
 ** PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN REVISED
 WHICH HAS CREATED SOME NEW COMMENTS.
  
 1) NOTE: PLEASE SEE RISER IS NOW SHOWING AND "EQUIPMENT
 GROUNDING CONDUCTOR" FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6, 250.24B.
  
 2) NOTE: PLEASE SEE NOW A NEW GROUNDING ELECTRODE POINT
 IS BEING SHOWN, HOWEVER NOW SIZE OF GEC OR SYSTEM
 REQUIRED PER 250.50 IS BEING SHOWN>???
  
 3) NOTE: PLEASE SEE RISER SHOWS WHAT IS TO BE A "RTSE"
 , PLEASE SUBMIT THE CORRESPONDING MANUFACTURES SPEC/CUT
 SHEET FOR THE RTSE.
  
 4) NOTE: PLEASE BE SURE ALL SHEETS CONTAIN THE PRINTED
 NAME AND SIGNATUREOF THE PERSON RESPONSIBLE FOR
 DESIGN/PLANS ETC. (PLEASE SEE LOAD CALCULATIONS).
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-11 Cont ID  
Sent By dpalmer Date 2006-09-11 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2006-09-11 Time 18:41 Sent To M
Notes
2006-09-11 00:00:00*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO REVISED RISER BEING SUBMITTED
 NEED TO BE ADDRESSED. PLEASE SEE NOTES
 BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW WITH NEW NOTES ADDED BELOW.
  
 1) NOTE: NO, PLEASE SEERISER DOES NOT
 INDICATE WHERE THIS FEED IS GOING AFTER
 THE ATS?
 PLEASE SEE NO OVER VIEW WAS SUBMITTED
 SHOWING THE LOCATION OF ALL THE SERVICE
 EQUIPMENT.
 PLEASE SEE THE ATS AS SUBMITTED AND
 SHOWN ON RISER DOES NOT CONTAIN THE
 REQUIRED DISONNECTING MEANS FOR THE
 FEEDERS COMING FROM THE GENERATOR.
 PLEASE KNOW, THIS MAY BE DONE BY MORE
 THAN ONE WAY, HOWEVER PLEASE SEE GENERAC
 NOW DOES MAKE A NEW ATS WHICH MEETS CODE
 COMPLIANCE FOR THIS WHICH PROVIDES THE
 DISOCNNECTING MEANS FOR THE FPL/LINE
 SIDE AND A DISCONNECT FOR THE FEEDERS
 LOCATED IN THE SAME ATS. (RTSE).
 ** THIS IS NO WAY THE ONLY METHID, AND
 IS ONLY ONE IDEA).
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE A RISER DIAGRAM
 INCLUDING ALL CONDUCTOR SIZES ANDHOW
 THIS WILL TIE INTO THE EXISTING
 SERVICE.
 PLEASE INDICATE OCP AND HOW THE NEW SE
 RATED ATS WILL BE FED. WHY ISTHIS UNIT
 SE RATED? PLEASE KNOW, THE METER MAIN IS
 STILL THE FIRST MEANS OF SERVICE
 DISCONNECT AND IT IS UNCLEAR HOW
 FEEDERS, OCP IS BEING CONNECTED AS SHOWN
 FROM EXISTING.
 PLEASE KNOW, IF THE NEW SE RATED ATS
 WILL BE THE NEW MAIN, MAY NOT PLACE LINE
 AND LOAD IN THE SMAE RACEWAY AND MAY NOT
 HAVE LINE IN W/ BRANCH CIRCUITS.230.7
 PLEASE CLARIFY AND SHOW THE DISCONNECT
 REQUIRED FOR FEEDERS FROM GEN TO HOUSE
 AND BEING GROUPED WITH THE EXISTING
 MAINS/DISCONNECTS.
 PLEASE SHOW AN OVERVIEW FOR LOCATION OF
 ALL EQUIPMENT ON PROPERTY
 240.4,310.16,215.5,225.31-225.39
  
 2) NOTE:OK, HOWEVER PLEASE VERIFY HOW
 LOAD FOR HEAT WENT DOWN? PLEASE SEE THE
 KW RATING AS SHOWN DOES NOT CORRELATE TO
 ANY COMMON HEAT STRIP.??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR HOUSE INCLUDING ALL
 LOADS.PLEASE KNOW ANY HEAT LOADS (AHU)
 SHALL BE AT 100%OR PLEASE PROVIDE A
 DETAIL ON HOW LOAD SHEDDING WILL TAKE
 PLACE.
 220.31
  
 3) NOTE: OK/NO, PLEASE SEE THE SETBACKS
 APPEAR TO BE OK, HOWEVER NO SPECS WERE
 SUBMITTED WHICH INDICATE THE MINIMUM
 CLEARENCES? PLEASE KNOW THE MIN REQUIRED
 WOULD BE 5FT.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE SETBACKS OF GEN
 FOR ALL SIDES FROM PROPERTY , AND ANY
 STRUCTURES.
 PLEASE SEE THAT THE MANUFACTURES SPECS
 SHOULD INCLUDE THE MIN CLEARENCES
 RECOMMENED BY MANUFACTURE.
 IT IS THE UNDERSTANDING FROM THE OFFICE
 FROM THE LTRS OBTAIN FROM THIS
 MANUFACTURE A MIN OF 5FT IS REQUIRED.
  
 4) NOTE: NO, THIS WAS NOT DONE AND FOUR
 DIFFERENT ATS MODELS,ONLY TWO COULD
 APPLY. PLEASE KNOW, AS THIS UNIT SEEMS
 TO BE TAKING THE PLACE OF THE MAIN FOR
 THE SERVICE, IT WOULD BE REQUIRED TO BE
 SE RATED. PLEASE SEE HOWEVER THE ABOVE
 COMMENT FOR THE REQUIRED DISCONNECTING
 MEANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO HIGH LIGHT
 UNITS/ EQUIPMENT BEING USED ON SPECS.
  
 5) NOTE: NO, THIS WAS NOTE TO SEE BBLDG
 COMMENTS, HOWEVER PLEASE SEE THERE ARE
 THREE DIFFERENT GENERATOR SLABS SHOWN ON
 PACKAGE. PLEASE SEE SURVEY SHOWS A SLAB
 WHICH DOES NOT CORRELATE TO EITHER THE
 ORIGINAL OR THE NEW ENGINEERING SLAB
 DETAILS SUBMITTED.
 PLEASE CORRELATE. THE NEW DETAIL
 SUBMITTED PROVIDES THE STRUCTURAL
 ATTACHMENT DETAIL REQUIRED PER NFPA-110
 CHAPTER 7.
  
 ** PREVIOUS REVIEW NOTE** PLEASE SEE
 BLDG REVIEW NOTES,
 AS INFORMATION IS REQUIRED ON HOW THE
 GENERATOR WILL BE ATTACHED TO THE SLAB.
 PLEASE ALSO PROVIDE MORE INFORMATION ON
 SLAB.
  
 ** NEW NOTE **
  
 6) NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT PREVIOUSLY SUBMITTED AHS NOW
 EXPIRED PER FS 713.13(2). PLEASE KNOW,
 IF WORK HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING NOC, THE NOC BECOMES VOID
 AND MUST BE RE-RECORDED.
 THIS IS ONLY REQUIRED BEFORE PICKING UP
 PERMIT.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS WITH RESPECT TO THE DESIGN
 PROFESSIONALS. PLEASE KNOW THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 07:18 Sent To M
Notes
2006-07-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE A RISER DIAGRAM
 INCLUDING ALL CONDUCTOR SIZES ANDHOW
 THIS WILL TIE INTO THE EXISTING
 SERVICE.
 PLEASE INDICATE OCP AND HOW THE NEW SE
 RATED ATS WILL BE FED. WHY ISTHIS UNIT
 SE RATED? PLEASE KNOW, THE METER MAIN IS
 STILL THE FIRST MEANS OF SERVICE
 DISCONNECT AND IT IS UNCLEAR HOW
 FEEDERS, OCP IS BEING CONNECTED AS SHOWN
 FROM EXISTING.
 PLEASE KNOW, IF THE NEW SE RATED ATS
 WILL BE THE NEW MAIN, MAY NOT PLACE LINE
 AND LOAD IN THE SMAE RACEWAY AND MAY NOT
 HAVE LINE IN W/ BRANCH CIRCUITS.230.7
 PLEASE CLARIFY AND SHOW THE DISCONNECT
 REQUIRED FOR FEEDERS FROM GEN TO HOUSE
 AND BEING GROUPED WITH THE EXISTING
 MAINS/DISCONNECTS.
 PLEASE SHOW AN OVERVIEW FOR LOCATION OF
 ALL EQUIPMENT ON PROPERTY
 240.4,310.16,215.5,225.31-225.39
  
 2) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR HOUSE INCLUDING ALL
 LOADS.PLEASE KNOW ANY HEAT LOADS (AHU)
 SHALL BE AT 100%OR PLEASE PROVIDE A
 DETAIL ON HOW LOAD SHEDDING WILL TAKE
 PLACE.
 220.31
  
 3) NOTE: PLEASE PROVIDE SETBACKS OF GEN
 FOR ALL SIDES FROM PROPERTY , AND ANY
 STRUCTURES.
 PLEASE SEE THAT THE MANUFACTURES SPECS
 SHOULD INCLUDE THE MIN CLEARENCES
 RECOMMENED BY MANUFACTURE.
 IT IS THE UNDERSTANDING FROM THE OFFICE
 FROM THE LTRS OBTAIN FROM THIS
 MANUFACTURE A MIN OF 5FT IS REQUIRED.
  
 4) NOTE: PLEASE BE SURE TO HIGH LIGHT
 UNITS/ EQUIPMENT BEING USED ON SPECS.
  
 5) NOTE: PLEASE SEE BLDG REVIEW NOTES,
 AS INFORMATION IS REQUIRED ON HOW THE
 GENERATOR WILL BE ATTACHED TO THE SLAB.
 PLEASE ALSO PROVIDE MORE INFORMATION ON
 SLAB.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-01-25 Cont ID  
Sent By mperson Date 2007-01-25 Time 09:43 Rev Time 0.45
Received By mperson Date 2007-01-25 Time 09:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2006-12-07 Cont ID  
Sent By mperson Date 2006-12-07 Time 08:32 Rev Time 0.33
Received By mperson Date 2006-12-07 Time 08:32 Sent To PC
Notes
2006-12-07 08:41:09DENIED 4TH TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW FROMPERVIOUS GAS PLAN REVIEW COMMENTS
 DATED 7/26/06, 9/12/06 AND11/06/06.
 A PERMIT FOR THE GENERATOR CAN NOT BE ISSUED UNTIL THE
 FOLLOWING CORRECTIONS ARE MADE TO MEET CODE
 COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE
 MEASUREMENTS OF THE UNDERGROUND PE PIPING. RECORDS
 INDICATE EXISTING GAS AT SAID ADDRESS PLEASE INDICATE
 THE EXISTING GAS ON RESUBMITTED DRAWING.PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING
 GAS AT SAID ADDRESS. PLEASE INDICATE THE CUT SECTION
 MEASUREMENTS OF ALL PIPING, UNDERGROUND, ABOVE GROUND
 AND EXISTING.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE
 UNDERGROUND PIPING MATERIAL AND SIZE. WHAT IS THE SIZE
 AND MATERIAL TYPE OF THE ABOVE GROUND AND EXISTING
 PIPING.
  
 3. (OK)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: RECORDS INDICATE EXISTING GAS TO A 40 GAL. NAT.
 GAS WATER HEATER. THE BTU LOAD TO THAT WATER HEATER
 MUST BE INDICATED ON THE DRAWING. THE BTU LOAD OF
 343,000 INDICATED FOR THE GENERATOR ON THE RESUBMITTED
 GAS ISOMETRIC IS STILL WRONG. THE CORRECT BTU LOAD IS
 437,000 PER THE SUBMITTED GENERATOR MANUFACTURE CUT
 SHEETS. PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE EXISTING GAS SYSTEM NEEDS TO BE INDICATED ON
 THE RESUBMITTED DRAWINGS WITH ITS MEASUREMENTS.
  
 6. (OK)
  
 7. (OK)
  
 8. (OK)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-11-06 Cont ID  
Sent By mperson Date 2006-11-06 Time 11:47 Rev Time 0.33
Received By mperson Date 2006-11-06 Time 11:47 Sent To PC
Notes
2006-11-06 13:46:03UNSAT (3RD TIME)
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE
 MEASURMENTS OF THE UNDERGROUND PE PIPING. WHAT ARE THE
 CUT SECTION MEASUREMENTS OF THE ABOVE GROUND PIPING?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATE THE
 UNDERGROUND PIPING MATERIAL AND SIZE. WHAT IS THE SIZE
 AND MATERIAL TYPE OF THE ABOVE GROUND PIPING?
  
 3. (OK)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: RECORDS INDICATE EXISTING GAS TO A 40 GAL. NAT.
 GASWATER HEATER, THE BTU LOAD TO THAT WATER HEATER
 MUST BE INDICATED ON THE DRAWING. THE BTU LOAD 343,000
 THAT IS INDICATED FOR THE GENERATOR IS WRONG ON THE
 RESUBMITTED ISOMETRIC, THE CORRECT BTU LOAD IS 437,000
 PER THE SUBMITTED GENERATOR MANUFACTURER SHEETS. PLEASE
 CORRECT THE BTU LOAD ON THE RESUBMITTAL.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE EXISTING GAS SYSTEM NEEDS TO BE INDICATED ON
 THE DRAING WITH ITS MEASUREMENTS.
  
 6. (OK)
  
 7. (OK)
  
 8. (OK)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By mperson Date 2006-09-12 Time 10:50 Rev Time 0.00
Received By mperson Date 2006-09-12 Time 10:50 Sent To B
Notes
2006-09-12 00:00:00REFERENCE: GAS PERMIT #06070580

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By mperson Date 2006-07-26 Time 15:02 Rev Time 0.00
Received By mperson Date 2006-07-26 Time 15:02 Sent To B
Notes
2006-07-26 00:00:00REFERENCE: GAS PERMIT #06070580

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-19 Cont ID  
Sent By adarroug Date 2007-01-19 Time 09:10 Rev Time 0.00
Received By adarroug Date 2007-01-19 Time 09:10 Sent To G
Notes
2007-01-19 09:10:57TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 15:08 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 15:08 Sent To E
Notes
2006-12-04 15:10:4412/4/06--PLANS WERE ROUTED TO "DPALMER" DESK ON 11/27

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 10:23 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 10:23 Sent To E
Notes
2006-10-27 10:29:53TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 09:54 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 09:53 Sent To E
Notes
2006-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-01 Cont ID  
Sent By adarroug Date 2006-09-01 Time 10:46 Rev Time 0.00
Received By adarroug Date 2006-09-01 Time 10:46 Sent To Z
Notes
2006-09-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-01 Cont ID  
Sent By adarroug Date 2006-08-10 Time 10:45 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 14:15 Sent To  
Notes
2006-08-10 00:00:008/10/06-CUSTOMER WAS CALLED, PACKAGE UP
 FRONT UNDER(G) NEED ORIGINAL PERMIT
 PACKAGE. THIS PACKAGE ONLY CONTAINS 2
 COPIES OF THE SITE PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 11:35 Sent To E
Notes
2006-07-18 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-07-27 Time 14:12 Rev Time 0.00
Received By adarroug Date 2006-07-12 Time 09:20 Sent To  
Notes
2006-07-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 09:14 Rev Time 0.15
Received By tgordon Date 2006-09-12 Time 09:14 Sent To P
Notes
2006-09-12 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 11:01 Rev Time 0.15
Received By tgordon Date 2006-07-21 Time 11:00 Sent To P
Notes
2006-07-21 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-05 Cont ID  
Sent By mmclean Date 2006-09-05 Time 07:40 Rev Time 0.00
Received By mmclean Date 2006-09-05 Time 07:40 Sent To I
Notes
2006-09-05 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 3.8FT FROM REAR PROPERTY
 LINE AND 6FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 13:11 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 13:11 Sent To I
Notes
2006-07-16 00:00:00DENIED,
 1. MUST PROVIDE A CURRENT SURVEY OF THE
 EXISTING STRUCTURE WITH SETBACKS FOR THE
 FRONT/SIDE/REAR. PLEASE INCLUDE THE
 UTILITY ROOMOR ANY OTHER STRUCTURE ON
 THE CURRENT SURVEY BY SURVEYOR (SURVEY
 IS TOO OLD AND OTHER WORK WAS DONE ON
 PROPERTY).
 2.MUST SHOW CLEARLY THE LOCATION OF THE
 PROPOSED GENERATOR. (PLEASE DO NOT USE
 HIGHTLIGHT FOR MARKING OF THE GENERATOR
 IT WILL NOT SHOW WHEN COPIED FOR
 FILING).
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720