Plan Review Details - Permit 06070422
Plan Review Stops For Permit 06070422
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-12 Cont ID  
Sent By mjacobs Date 2007-07-12 Time 15:38 Rev Time 0.00
Received By mjacobs Date 2007-07-12 Time 15:11 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 06:41 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 05:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-14 Cont ID  
Sent By mjacobs Date 2006-10-14 Time 14:11 Rev Time 0.00
Received By mjacobs Date 2006-10-14 Time 14:11 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By mjacobs Date 2006-08-07 Time 11:51 Rev Time 0.00
Received By mjacobs Date 2006-08-07 Time 09:24 Sent To PC
Notes
2006-08-07 00:00:00 
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION. THE NEW LOCATION IS2300
 N. JOG RD (NORTH OF OKEECHOBEE BLVD)
 SUITE#2W01-2W14.
  
 2) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 TWO COPIES REQUIRED. ONLY ONE WAS
 SUBMITTED.
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4) IF THE NEW WINDOWS ARE NON-IMPACT,
 HURRICANE PROTECTION IS REQUIRED. SUBMIT
 PRODUCT APPROVALS FOR SHUTTERS FOR THE
 NEW WINDOWS.
  
 5) WHERE IS THE NEW LAUNDRY ROOM
 LOCATED?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 10:24 Sent To PC
Notes
2007-11-26 10:38:11REDLINED WATER HEATER WHICH IS MISSING FROM PANEL
 SCHEDULE.
 PLANS AND LOAD CALCULATIONS DO INDICATEA WH.
 NEED TO REVISE BEFORE FINAL.
 240.4, 310.16, 408.4.
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-10-27 Cont ID  
Sent By dpalmer Date 2007-10-27 Time 12:19 Rev Time 0.00
Received By dpalmer Date 2007-10-27 Time 12:19 Sent To PC
Notes
2007-10-27 12:19:37** DENIED REVISION **
  
 ** PLEASE SEE NOTES FROM PREVIOUS *PROVISO* ARE STILL
 IN NEED OF ADDRESSING. PLEASE ALSO SEE THERE ARE NEW
 NOTES AS PLANS HAVE BEEN REVISED WITH SOME ITEMS WHICH
 ARE NOT CODE COMPLIANT.
  
 1) NOTE: PLEASE SEE THE SMOKE ALARMS WHICH WERE TO BE
 CORRECTED TO THE EXISTING DWELLING AS WELL WAS NOT
 SUBMITTED.
 PLEASE SEE FBC R313, NFPA-72 11.5.1.1
  
 2) NOTE: PLEASE SEE THE WATER DISCONNECT IS NOW
 MISSING.
 422.31.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS NOW BEING
 SHOWN IN THE CLOSET ARE WITH THE WASHER AND DRYER AND
 ALSO DOES NOT MEET 110.26 FOR MINIMUM WORKING
 CLEARANCES PER 110.26.
 PLEASE ALSO SEE 240.24D, AND 408.7
 PANEL IS TO BE RELOCATED.
  
 4) NOTE: PLEASE SEE THE PANEL SCHEDULE WAS NOT
 COMPLETELY REVISED INDICATING ALL NEW CIRCUITS. PLEASE
 SEE SOME BRANCH CIRCUITS FOR LIGHTING AND RECEPTACLES
 HOWEVER WASHER, DRYER ETC IS THE SAME.
 PLEASE SEE IN FACT WASHER CIRCUIT IS MISSING FROM THE
 PANEL SCHEDULE.
 PLEASE ALSO SEE SMALL APPLIANCE CIRCUIT #32 FOR BRKFST
 ROOM IS SHOWN ON LIGHTING CIRCUIT FOR COVERED PATIO. IF
 EXISTING OK, IF NEW THIS DOES NOT MEET 210.52B1,
 210.11C1, 220.16
 PLEASE ADJUST PANEL SCHEDULE AS NEEDED. 408.4, 310.16,
 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE ONLY SUBMIT ELECTRICAL PLANS WHICH ARE
 BEING REVISED. PLEASE SEE THE TITLE BLOCKS OF PLANS DO
 NOT INDICATE THE REVISIONS, CLOUDS AND TRIANGLES WITH
 DATES.
 PLEASE SEE THE SHEETS CONTAIN ALL OTHER TRADES WHEN
 ONLY ELECTRICAL IS NEEDED.
 FBC 106.3.1
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-07-12 Cont ID  
Sent By dpalmer Date 2007-07-12 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2007-07-12 Time 08:07 Sent To B
Notes
2007-07-12 09:55:57*** PROVISO ***
  
 1) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS ALL CIRCUITS
 AS NEW. PLEASE REVISE TO INDICATE WHICH ARE NEW AND
 WHICH ARE EXISTING?
 408.4
  
 2) NOTE: PLEASE SEE THE SMOKE DEVICES AS INDICATE FOR
 NEW AND EXISTING DWELLING SHOULD BE INDICATED AS SA FOR
 SMOKE ALARMS.
 PLEASE SEE NFPA-72 DEFINITIONS AND 11.5.1.1.1
  
 3) NOTE: PLEASE SEE ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS SHALL BE SHOWN AND FIGURED AT 1500 VA FOR
 EACH. ONLY TWO ARE SHOWN ON LOAD CALCULATIONSYET
 THREE ARE SHOWN ON PANEL SCHEDULE.
 210.52B1, 220.16
  
 ** PLEASE REVISED THE ABOVE INFORMATION ON AN
 ELECTRICAL PLAN/SHEET AND SUBMIT WITH ANY OTHER
 POSSIBLE REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION.
 THE REVISED PLANS MUST BE ON-SITE FOR ROUGH ELECTRICAL
 INSPECTION.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-30 Time 07:42 Rev Time 0.00
Received By dpalmer Date 2006-11-30 Time 07:21 Sent To M
Notes
2006-11-30 07:43:58*** UNSAT ***
  
 *** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTED FOR
 CIRCUITING AS REQUESTED ON BOTH PREVIOUS REVIEWS. THIS
 WOULD INDICATE THE CIRCUITS (NEW) AND EXISTING, THE
 BRANCH CIRCUIT , ALONG WITH THE OVER CURRENT PROTECTION
 AND CONDUCTOR SIZES.
 310.16,240.4,408.4 ETC
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
  
 2) NOTE: PLEASE SEE NOW LOAD CALCULATIONS ARE BEING
 SUBMITTED FOR THE FIRST TIME FOR REVIEW. PLEASE SEE
 THESE NOTE VERIFY A 200A SERVICE, YET THE RISER SHOWS
 AN EXISTING 150A SERVICE? WHICH IS IT?
 PLEASE ALSO SEE THERE ARE 2/0?S BEING SHOWN FROM RISER
 TO MAIN PANEL.(EXISTING)??
 PLEASE KNOW THIS IS THE RESPONSIBILITY OF THE DESIGNER
 OF RECORD TO OBTAIN THIS INFORMATION AND PLACE THIS
 INFORMATION ON PLANS ACCURATELY.
 FBC 106.1.2 ADMIN SECTION.
 NEC 230.70, 310.16, 240.4 ETC.
  
 4) NOTE: PLEASE KNOW AS NOTED ON PREVIOUS2ND REVIEW
 WITH RESPECT TO REPEAT CODE COMPLIANT COMMENTS TO THE
 DESIGN PROFESSIONAL, A FEE OF $312.00 BASED ON 4X THE
 FEE FOR THE PORTION THE FEE ATTRIBUTED TO PLAN REVIEW
 HAS BEEN ASSESSED AS REQUIRED UNDER FS 553.80(2)(B).
 THIS FEE SHALL BE PAID BEFORE NEXT RESUBMISSION OF
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** TO DATE NO CONTACT HAS BEEN MADE TO THIS OFFICE TO
 GO OVER SAID COMMENTS OR ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 11:44 Sent To M
Notes
2006-10-01 00:00:00*****UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED AND
 PLEASE SEE NEW COMMENTS BASED ON PLANS
 AND SPECS SUBMITTED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE: NO, LOAD CALCULATIONS
 SUBMITTED, DO NOT CORRELATE WITH ANY
 CALCULATIONS BASED FROM THE NFPA-70 OR
 IS PERMITTED IN THE NEC.
 ** PLEASE SEE 220.312B AND COMPLETE.
 PLEASE SEE THERE IS A MAJOR LOAD BEING
 ADDED, HOWEVER THERE HAS BEEN NOT
 CONSIDERATION FOR THIS. PLEASE SEE SPECS
 FOR TANKLESS WATER HEATER SUBMITTED
 WHICH "HIGH-LIGHTS" A 28KW UNIT!!!! THIS
 UNITS ALONE PULLS 116A'S.
 PLEASE SEE THE LOAD ON THIS UNIT ALONE
 AND THE MIN LOADS ON THE EXISTING
 DWELLING FAR EXCEED THE RATING OF THE
 EXISTING DWELLING'S SERVICE.
 PLEASE OBTAIN A QUALIFIED PERSON WHO HAS
 ELECTRICAL BACKGROUND TO THESE AS THIS
 IS LIFE SAFETY AND FIREHAZARD AND DUE
 TO WHAT IS BEING SUBMITTED.
 PLEASE SEE NO INFORMATION AND LCOATION
 OF UNIT AT THIS TIME IS "NOT" PERMITTED.
 ** PLEASE ALSO SEE THERE IS NO NRTL(
 NATIONALLY RECOGNIZED TESTING
 LABORATORY) SHOWN ON SPECS. PLEASE ALSO
 SUBMIT TWO COPIES.
 PLEASE SEE NO NEW REVISED PANEL SCHEDULE
 WAS SUBMITTED EITHER TO VERIFY THE NEW
 CIRCUITS, CONDUCTORS, OCP, LOADS ETC.
 110.3,240.24,110.26,90.7,220.31B, 408.4,
 240.4, 310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS SHOWING ALL EXISTING AND
 NEW LOADS.
 INDICATE THE SIZE OF THE NEW TANKLESS
 WH. PLEASE SEE MANUFACTURES SPECS / CUT
 SHEETS FOR MIN CLEARENCES AND LOCATION.
 PLEASE SEE CLARIFY WHERE THE MEANS OF
 DISCONNECT IS?
 PLEASE SEE LOCATION BEING PRIMARILY
 STORAGE UNDER LAV AND LOCATION DUE TO
 EASILY IGNITIBLE MATERIALS.
 PLEASE SUBMIT THE MANUFACTURES SPECS/
 CUT SHEETS FOR THE PROPOSED UNIT.
 PLEASE SEE 110.26,422.31,110.3,240.24,
 220.31, 408.4 ETC.
  
 2) NOTE: OK.
  
 3) NOTE:NO, SAME NOTE, NOTHING SHOWN
 OR SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **PLEASE SEE
 2004 R313 AS SD'S
 ARE REQUIRED INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS. PLEASE SEE
 NFPA-72 11.5.1.1,11.8.3.
 PLEASE SHOW A BASIC LAYOUT OF THE
 EXISTING DWELLING AND THE LOCATION OF
 THE SD'S.
  
 4) NOTE: NO, NOT CLEAR A NEW LOCATION
 SEEMS TO BE SHOWN BASED ON SYMBOL OF
 WHAT THE WASHER AND DRYER SHOULD BE,
 HOWEVER NOTHING IDENTIFING NEW
 EQUIPMENT. PLEASE SEE IF NEW STACKABLE
 UNIT, PLEASE SHOW, AND PLEASE INDICATE
 IN NEW LOADS/PANEL SCHEDULE.
 220.16, 210.11C2, 220.18
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE PERMIT APPLICATION
 MENTIONS CONVERTING EXISTING LAUNDRY RM
 TO BATHRM, HOWEVER NEW LANUDRY AREA CAN
 NOT BE LOCATED. PLEASE SEE MIN HOUSING
 CODE FOR LAUNDRY FACILIES AND PLEASE SEE
 NEC FOR MIN LAUNDRY CIRCUITS.
 210.11C2, 220.16
  
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE ONE SET OF PLANS
 HAVE BEEN RETAINED BY THIS OFFICE AND
 WILL BE PLACED IN FILE WITH ALL OTHER
 PROJECTS REPEATLY BEING SUBMITTED,
 SIGNED , DATED AND SEALED BY THIS DESIGN
 PROFESSSIONAL.PLEASE SEE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR PLAN REVIEW IS NOW GIVEN AS
 NOTICE.
 PLEASE ALSO SEE FS 471.025(3) QUOTED,
 "NO LICENSEE SHALL AFFIX OR PERMIT TO
 BE AFFIXED HIS OR HER SEAL, NAME, OR
 DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID
 DOCUMENT, OR OTHER DOCUMENT THAT DEPICTS
 WORK WHICH HE OR SHE IS NOT LICENSED TO
 PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN."
 THIS IS TAKEN DIRECTLY FROM THE TEXT OUT
 OF THE FLORIDA STATUES.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 07:16 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 07:02 Sent To M
Notes
2006-07-20 00:00:00******UNSAT ********
  
 1) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS SHOWING ALL EXISTING AND
 NEW LOADS.
 INDICATE THE SIZE OF THE NEW TANKLESS
 WH. PLEASE SEE MANUFACTURES SPECS / CUT
 SHEETS FOR MIN CLEARENCES AND LOCATION.
 PLEASE SEE CLARIFY WHERE THE MEANS OF
 DISCONNECT IS?
 PLEASE SEE LOCATION BEING PRIMARILY
 STORAGE UNDER LAV AND LOCATION DUE TO
 EASILY IGNITIBLE MATERIALS.
 PLEASE SUBMIT THE MANUFACTURES SPECS/
 CUT SHEETS FOR THE PROPOSED UNIT.
 PLEASE SEE 11.26,422.31,110.3,240.24,
 220.31, 408.4 ETC.
  
 2) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 FOR MORE THAN 2' OF WALL SPACE.
  
 3) NOTE: PLEASE SEE 2004 R313 AS SD'S
 ARE REQUIRED INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS. PLEASE SEE
 NFPA-72 11.5.1.1,11.8.3.
 PLEASE SHOW A BASIC LAYOUT OF THE
 EXISTING DWELLING AND THE LOCATION OF
 THE SD'S.
  
 4) NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS CONVERTING EXISTING LAUNDRY RM
 TO BATHRM, HOWEVER NEW LANUDRY AREA CAN
 NOT BE LOCATED. PLEASE SEE MIN HOUSING
 CODE FOR LAUNDRY FACILIES AND PLEASE SEE
 NEC FOR MIN LAUNDRY CIRCUITS.
 210.11C2, 220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 16:41 Sent To E
Notes
2007-11-19 16:41:35TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 16:06 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 16:06 Sent To E
Notes
2007-10-26 16:07:25TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:09 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:08 Sent To E
Notes
2006-11-29 17:09:15SENT TO DEWEY PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 08:55 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 08:55 Sent To Z
Notes
2006-11-20 08:56:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 14:13 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 14:13 Sent To E
Notes
2006-09-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-21 Cont ID  
Sent By adarroug Date 2006-09-21 Time 10:16 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 10:16 Sent To Z
Notes
2006-09-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 11:36 Sent To E
Notes
2006-07-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-07 Time   Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 12:22 Sent To  
Notes
2006-07-11 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-30 Cont ID  
Sent By tgordon Date 2006-11-30 Time 08:08 Rev Time 0.20
Received By tgordon Date 2006-11-30 Time 08:08 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 11:31 Rev Time 0.30
Received By tgordon Date 2006-10-02 Time 11:31 Sent To P
Notes
2006-10-02 00:00:00*** DENIED ***
 1) MECHANICAL PLANS ARE OK, SEE
 ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By tgordon Date 2006-07-20 Time 09:26 Rev Time 0.25
Received By tgordon Date 2006-07-20 Time 09:26 Sent To P
Notes
2006-07-20 00:00:00 
 *** DENIED ***
 1) NEED TWO COPYS OF THE ENERGY
 CALCULATIONS, ONLY ONE WAS SUBMITTED.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 3) SHOW ON PLANS THE NEW LOCATION OF THE
 CLOTHES WASHER AND DRYER, AND THE
 CLOTHES DRYER VENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 14:08 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 14:08 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 09:44 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 09:44 Sent To B
Notes
2006-10-14 09:52:23DENIED;
 1. (NOTE 2 FROM LAST REVIEW WAS NOT ADDRESSED).PLEASE
 PROVIDE MANUFACTURE'S INSTALLATION INSTRUCTIONS
 2.AUTOMATIC CLOTHES WASHER MUST HAVE A 2" TRAP MIN. NOT
 1 1/2"CLEANOUT TO BE AT 48" AFF.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By jleech Date 2006-07-24 Time 10:34 Rev Time 0.00
Received By jleech Date 2006-07-24 Time 10:16 Sent To B
Notes
2006-07-24 00:00:00DENIED;
 1.PLEASE SHOW NEW LOCATION OF LAUNDRY
 FIXTURES. AUTOMATIC CLOTHES WASHER IS
 REQUIRED TO MEET MINIMUM PLUMBING CODE
 SEE FBC-2004 PLUMBING TABLE 403.1 R-3.
 ALSO SEE SECTION 406.3 DRAIN FOR NEW W/M
 IS REQUIRED TO BE 3".
 2.PROVIDE MANUFACTURE INSTALLATION
 INSTRUCTIONS FOR NEW WATER
 HEATER,CLEARANCES AND ACCESSABLITY COULD
 BE A PROBLEM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-26 Cont ID  
Sent By mmclean Date 2006-11-26 Time 22:24 Rev Time 0.00
Received By mmclean Date 2006-11-26 Time 22:24 Sent To I
Notes
2006-11-26 22:24:27PROVISO: ENCLOSING THE EXISTING CARPORT.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By mmclean Date 2006-09-23 Time 10:22 Rev Time 0.00
Received By mmclean Date 2006-09-23 Time 10:22 Sent To I
Notes
2006-09-23 00:00:00PROVISO: ENCLOSING THE EXISTING CARPORT.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 13:36 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 13:36 Sent To I
Notes
2006-07-16 00:00:00DENIED,
 1. PLEASE SUBMIT A COPY OF EXISTING
 SURVEY, SHOWING THE EXISTING CARPORT
 WITH SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720