Plan Review Details - Permit 06070321
Plan Review Stops For Permit 06070321
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By jgomez Date 2006-08-23 Time 13:33 Rev Time 0.50
Received By jgomez Date 2006-08-23 Time 07:44 Sent To PC
Notes
2006-08-23 00:00:00PERMIT UNDER "Y".

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By jgomez Date 2006-08-11 Time 16:25 Rev Time 0.40
Received By jgomez Date 2006-08-11 Time 16:25 Sent To  
Notes
2006-08-11 00:00:00BUILDING REVIEW 2ND CHECKLIST:
  
 1- CONTRACTOR STATES IN PERMIT
 APPLICATION THAT CONCRETE TILE IS TO BE
 PLACED IN WOOD DECK BATTEN SYSTEM. DADE
 COUNTY NOA #02-1205.07 FOR MONIER
 SPANISH 'S' CONCRETE TILE DOESN'T ALLOW
 BATTEN SYSTEM INSTALLATION. SEE PAGE 4
 OF 5 OF NOA. NEED TO PROVIDE PRODUCT
 APPROVAL THAT ALLOWS BATTEN SYSTEM
 APPLICATION OR PROVIDE SOLID DECK
 SYSTEM.
 PROVIDE COMPLETE STRUCTURAL DRAWINGS AND
 SPECIFICATIONS FOR SOLID DECKING UNDER A
 SEPARATE PERMIT FOR STRUCTURAL WORK.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 AND SEC. 1609 FBC 2004.
  
 2- SELF ADHERING UNDERLAYMENT (FLORIDA
 PRODUCT APPROVAL FL3732-R1) IS NOT
 ALLOWED. SEE RAS 120 FOR TYPES OF
 UNDERLAYMENTS ALLOWED. SPECIFY WHICH
 UNDERLAYMENT IS GOING TO BE USED.
 ALSO, ACCORDING TO THE ROOF SLOPE THERE
 ARE ROOF TILE NAILING REQUIREMENTS. SEE
 RAS 120 AND PROVIDE NAILING
 SPECIFICATIONS AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By jgomez Date 2006-07-12 Time 16:24 Rev Time 0.00
Received By jgomez Date 2006-07-12 Time 16:24 Sent To  
Notes
2006-07-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- CONTRACTOR TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
 MISSING MEAN ROOF HEIGHT.
  
 2- PROVIDE UPLIFT PRESSURE CALCULATIONS
 IF BUILDING MEAN ROOF HEIGHT IS HIGHER
 THAN 30'-0" TO VERIFY COMPLIANCE OF
 CONCRETE ROOF TILE AS REQUIRED BY SEC.
 1609.7 FBC 2004.
  
 3- UNDERLAYMENT PRODUCT APPROVAL.
 A) NEED TO PROVIDE THE 2004 FLORIDA
 PRODUCT APPROVAL VERSION, NOT 2001.
 B) NEED TO PROVIDE TECHNICAL
 INFORMATION THAT WAS SUBMITTED TO GET
 FLORIDA PRODUCT APPROVAL. GO TO THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO
 DOWMLOAD ALL INFORMATION.
  
 4- PROVIDE COPY OF FLORIDA PRODUCT
 APPROVAL COVER PAGE AS REQUIRED BY CITY
 RE-ROOFING PERMITS FOR MONIER SPANISH
 "S". CONC. ROOF TILE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 13:50 Sent To B
Notes
2006-08-21 00:00:00TO "JGOMEZ" DESK/RESUB