Plan Review Details - Permit 06070179
Plan Review Stops For Permit 06070179
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-10 Cont ID  
Sent By lursu Date 2006-07-10 Time 15:07 Rev Time 0.00
Received By pschmitz Date 2006-09-25 Time 11:25 Sent To  
Notes
2006-07-10 00:00:00COPY OF APPL. SENT TO LILI
 NEW ADDRESS 1321 N MANGONIA DR WAS
 ASSIGNED TO THIS VACANT PARCEL
  
 9-25-06 ENTERED STOP IN ERROR,PES

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-13 Cont ID  
Sent By lmartine Date 2007-03-13 Time 10:49 Rev Time 0.00
Received By lmartine Date 2007-03-13 Time 10:49 Sent To  
Notes
2007-03-13 10:50:44REVISION #3

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-28 Cont ID  
Sent By lmartine Date 2007-02-28 Time 16:33 Rev Time 0.00
Received By lmartine Date 2007-02-28 Time 16:33 Sent To  
Notes
2007-02-28 17:24:06 
 REVISION
 FEBRUARY 5, 2007
  
  
 ROOF PITCH CHANGE APPROVED,
  
 PGT SINGLE HUNG WINDOW APPROVED,
  
  
  
  
  
 GLASS BLOCK NOT APPROVED ; PLEASE IDENTIFY WHICH SYSTEM
 AND PROVIDE INSTALLATION DETAILS.
  
 PGT FIXED WINDOWS NOT APPROVED; CHOOSE INSTALLATIONS
 DETAILS FROM ENGINEERING AND PROVIDE INSTALLATION
 SCHEDULE FOR STORM PANELS.
  
 THERMA--TRU DOORS AND ODL GLASS NOT APPROVED; PROVIDE
 STORM PANEL INSTALLATION SCHEDULE FOR NON--IMPACT
 GLAZED WINDOWS AND DOORS, CHECK THE MAX. ALLOWABLE
 SHUTTER SPAN OF 104" AT GLAZED DOORS AND TRANSOMS.
  
  
  
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-25 Cont ID  
Sent By rnuquist Date 2006-11-25 Time 12:15 Rev Time 0.00
Received By rnuquist Date 2006-11-25 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-26 Cont ID  
Sent By amorse Date 2006-09-26 Time 11:10 Rev Time 0.00
Received By amorse Date 2006-09-26 Time 11:10 Sent To PC
Notes
2006-09-26 00:00:00 
  
 DENIED
  
 1) THE SUBMITTED TRUSS DRAWINGS SHALL BE
 SIGNED AND SEALED BY TRUSS MANUFACTURERS
 ENGINEER. ALSO ONLY ONE COPY OF THE
 LAYOUT WAS PROVIDED AND 2 WILL BE
 REQUIRED
  
 2) PLEASE BE AWARE THAT SPECIFIC ANCHORS
 ARE TO BE LISTED FOR THE TRUSS TIE DOWNS
 AT ALL LOCATIONS (WALLS, GIRDERS,
 VALLEYS, ETC.) EITHER BY THE TRUSS
 MANUFACTURERS DESIGNER OR THE DESIGNER
 RESPONSIBLE FOR THE PROJECT
  
 3) PRODUCT APPROVALS FOR THE MULLIONS
 MISSING THE STATE OF FLORIDA COVERS
 SHEETS (FL# 6868)
  
 4) SOME PRODUCT APPROVALS WERE NOT
 REVIEWED BY THE DESIGN PROFFESIONAL AS
 REQUIRED PER 106.3.3 FBC* ( SINGLE HUNG
 WINDOWS,MULLIONS,STEEL INSULATED DOOR,
 AND STORM PANELS
  
 5) PRODUCT APPROVALS WERE SUBMITTED FOR
 CASEMENT/SH EGRESS WINDOWS. PLEASE SEE
 THAT THE REGULAR SINGLE HUNG SH25 WILL
 MEET THE EGRESS REQUIREMENTS BECAUSE IT
 IS 63" TALL AND THAT THE CASEMENT/SH
 WINDOWS HAVE A MAX HEIGHT OF 50 5/8"
 ALSO A PRODUCT APPROVAL WAS SUBMITTED
 FOR AN INSWING DOOR THAT IS NOT A FRENCH
 DOOR (GLAZED) AS STATED FOR FRONT DOOR
 ON THE DRAWINGS. PLEASE MAKE CORRECTIONS
 AND REMOVE PRODUCTS THAT ARE INCORRECT
 OR NOT USED. SUBMIT REVIEWED AND
 APPROVED ALTERNATIVES.
  
 6) ALL PERMIT APPLICATION FEES MUST BE
 PAID BEFORE FURTHER REVIEWS WILL BE MADE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By amorse Date 2006-07-17 Time 09:51 Rev Time 3.00
Received By amorse Date 2006-07-17 Time 09:51 Sent To PC
Notes
2006-07-17 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 3) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 4) IN AREAS OF QUESTIONABLE SOILS AS
 SHOWN IN THE OFFICIAL ZONING MAP ADOPTED
 BY THE CITY OF WEST PALM BEACH, A SOIL
 TEST REPORT SHALL BE SUBMITTED PER
 R401.4 PLEASE SUBMIT 2 COPIES SIGNED,
 SEALED AND DATED BY RESPONSIBLE PARTY.
 PLEASE NOTE THAT DESIGNER OF RECORD
 SHALL REVIEW AND APPROVE REPORT (COPY OF
 REPORT SUBMITTED STATES BEARING CAPACITY
 OF 1500 PSF WHILE DRAWINGS REQUIRE 2000
 PSF)
  
 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION. 2
 COPIES SIGNED, SEALED AND DATED BY
 RESPONSIBLE PARTY. (PLEASE NOTE DRAWINGS
 SUBMITTED ARE NOT SEALED BY PERSONS
 RESPONSIBLE, ALSO DRAWINGS ARE REQUIRED
 TO BE REVIEWED AND APPROVED BY DESIGNER
 OF (RECORD)
  
 6) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 ******NOTE THE FOLLOWING PRODUCT
 APPROVALS ARE REQUIRED*********
 FRENCH DOORS, GARAGE ENTRY DOOR, LINTELS
 TRANSOM WINDOWS, MULLIONS, ALSO 3
 DIFFERENT NOA'S WERE SUBMITTED FOR GLASS
 BLOCK AND THE STATE APPROVAL SHEETS WERE
 NOT (ALL PRODUCT APPROVALS WHERE
 POSSIBLE SHALL BE SUBMITTED WITH THE
 STATE COVER SHEETS
  
 7) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8) PROVIDE A SITE PLAN THAT SHOWS
 COMPLIANCE WITH LANDSCAPE REQUIREMENTS
 AND A DRAINAGE PLAN PER R401.3 FBC
  
 9) PROVIDE LINTEL SCHEDULE WITH SIZES
 AND LENGTHS TO BE USED
  
 10) SPECIFY SAFETY GLAZING REQUIRED IF
 GLASS BETWEEN TUB AND SHOWER MEET THE
 REQUIREMENTS OF R308.1 AND R308.4 FBC
  
 11) VERTICAL REINFORCEMENT MAX 6'-0" O/C
 A/1 STATES MIN
  
 12) SECTIONS 02/A3 AND 03/A3 SHOW TOP OF
 BEAM HEIGHT AT 10'-0" ELEVATIONS SHOW
 9'-4" PLEASE CLARIFY
  
 13) PROVIDE TRANSOM SIZES AND DESIGN
 PRESSURES ON THE DOOR AND WINDOW SCEDULE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-07 Cont ID  
Sent By btrobaug Date 2007-02-07 Time 07:52 Rev Time 0.50
Received By btrobaug Date 2007-02-07 Time 07:24 Sent To M
Notes
2007-02-07 07:52:39 
  
 PROVISO
  
 SUBMIT A REVISION PRIOR TO FINAL ELECTRICAL INSPECTION,
 ADDING THE RECIRCULATING PUMP TO THE PANEL SCHEDULE AND
 LOAD CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-20 Cont ID  
Sent By btrobaug Date 2006-11-20 Time 12:27 Rev Time 0.50
Received By btrobaug Date 2006-11-20 Time 11:54 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-13 Cont ID  
Sent By btrobaug Date 2006-09-13 Time 11:17 Rev Time 0.50
Received By btrobaug Date 2006-09-13 Time 07:57 Sent To M
Notes
2006-09-13 00:00:00NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC. THIS
 DOCUMENT MUST BE PRODUCED BY THE
 DESIGNER OF RECORD FOR THE PROJECT, AND
 SIGNEDAND SEALED BY SAME.
  
 2} THE RECEPTACLE IN THE MASTER BATH
 MUST COMPLY WITH 210.52(D), WITHIN 3' OF
 THE BASIN. PLEASE CORRECT ON PLANS.
  
 3} THE WHITE OUT ON THE PLAN IS NOT
 ACCEPTABLE FOR RECORD RETENTION PER
 106.1.3 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By btrobaug Date 2006-07-12 Time 18:19 Rev Time 0.50
Received By btrobaug Date 2006-07-12 Time 18:05 Sent To M
Notes
2006-07-12 00:00:00NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC.
  
 2} THE RECEPTACLE IN THE MASTER BATH
 MUST COMPLY WITH 210.52(D), WITHIN 3' OF
 THE BASIN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 14:03 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 14:03 Sent To B
Notes
2007-03-10 14:03:45TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 15:08 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 15:08 Sent To E
Notes
2007-02-06 15:08:38TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 08:16 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 08:16 Sent To E
Notes
2006-11-20 08:17:09TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:57 Sent To E
Notes
2006-09-05 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-17 Time   Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 09:05 Sent To  
Notes
2006-07-10 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-08 Cont ID  
Sent By tgordon Date 2007-02-08 Time 09:39 Rev Time 0.30
Received By tgordon Date 2007-02-08 Time 09:39 Sent To P
Notes
2007-02-08 09:40:29REVISION TO MECHANICAL PLANS AND MANUAL J CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-20 Cont ID  
Sent By tgordon Date 2006-11-20 Time 14:01 Rev Time 0.30
Received By tgordon Date 2006-11-20 Time 14:01 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-14 Cont ID  
Sent By tgordon Date 2006-09-14 Time 08:57 Rev Time 0.45
Received By tgordon Date 2006-09-14 Time 08:57 Sent To P
Notes
2006-09-14 00:00:00*** DENIED ***
 1) MECHANICAL PLANS SUBMITTED ARE
 DIFFICULT TO READ, CHANGES MADE BY HAND
 TO PLANS NEED TO BE INITIALED AND DATED
 AT EACH CHANGE, RED PEN CAN NOT BE USED
 FOR CHANGES AS IT FADES IN TIME,
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
  
 2) PLEASE CORRECT THE ADDRESS ON THE
 PLANS AND ENERGY CAL'S. 1321 N. MANGONIA
 DR. WEST PALM BEACH, FL. (NOT PALM
 BEACH).
  
 3) PLANS NEED THE PRINTED NAME, ADDRESS,
 AND PHONE NUMBER OF THE DESIGN PERSON OR
 COMPANY ON THEM.
  
 4) ENERGY CAL'S. NEED THE JURISDICTION
 NUMBER ON THEM.
  
 5) ENERGY CAL'S. ARE CALLING FOR A/C
 SYSTEM #1 TO BE 14 SEER, PLANS ARE
 CALLING FOR A/C SYSTEM #1 TO BE 13 SEER,
 THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 6) AS NOTED IN LAST REVIEW 7-13-06 NOTE
 #5, PLEASE SHOW CLOTHES DRYER VENT, AND
 BATHROOM VENTS ON MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By tgordon Date 2006-07-13 Time 08:31 Rev Time 0.20
Received By tgordon Date 2006-07-13 Time 08:31 Sent To B
Notes
2006-07-13 00:00:00*** DENIED ***
 1) MECHANICAL PLANS SUBMITTED ARE TO
 SMALL AND ARE DIFFICULT TO READ,
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 2)PLEASE SHOW GRILL SIZES ON MECHANICAL
 PLANS.
  
 3) CAN NOT READ ALL SUPPLY AIR DUCT
 SIZES, PLEASE CORRECT.
  
 4) PLEASE SHOW A/C EQUIPMENT LISTING ON
 MECHANICAL PLANS.
  
 5) PLEASE SHOW CLOTHES DRYER VENT, AND
 BATHROOM VENTS ON MECHANICAL PLANS.
  
 6) PROVIDE FOR RETURN AIR, SEE NOTE #8.
  
 7) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 8) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-02-14 Cont ID  
Sent By jleech Date 2007-02-14 Time 09:16 Rev Time 0.00
Received By jleech Date 2007-02-14 Time 09:16 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-20 Cont ID  
Sent By jleech Date 2006-11-20 Time 14:34 Rev Time 0.00
Received By jleech Date 2006-11-20 Time 14:34 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-25 Cont ID  
Sent By pschmitz Date 2006-09-25 Time 11:26 Rev Time 0.00
Received By pschmitz Date 2006-09-25 Time 11:26 Sent To  
Notes
2006-09-25 00:00:00RE-SUB

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By jleech Date 2006-07-12 Time 14:11 Rev Time 0.00
Received By jleech Date 2006-07-12 Time 14:11 Sent To E
Notes
2006-07-12 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM; MASTER
 BATHROOM LAVS ARE NOT ON THE SAME WALL.
 A VENT STACK IS NEEDED FOR EACH LAV.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 IS REQUIRED TO BE 3", FBC-2004 PLUMBING
 SEC. 406.3. CLEANOUT SHOULD BE LOCATED
 AT 48" ABOVE FINISHED FLOOR FOR SERVICE.
 ON SET OF PLANS MARKED IN RED
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-10 Cont ID  
Sent By mmclean Date 2006-07-10 Time 14:41 Rev Time 0.00
Received By mmclean Date 2006-07-10 Time 14:41 Sent To E
Notes
2006-07-10 00:00:00NOTE:
 THE PROPOSED A/C SHALL NOT BE CLOSER
 THAN 1FT FROMSIDE PROPERTY LINE.
  
 PROVISO: IF ANY CHANGES TO THE SURVEY,
 PLEASE SHOW THE LOCATION OF THE A/C
 UNIT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved