Plan Review Details - Permit 06070176
Plan Review Stops For Permit 06070176
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-27 Cont ID  
Sent By alange Date 2006-09-27 Time 08:54 Rev Time 0.00
Received By alange Date 2006-09-27 Time 08:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By alange Date 2006-07-27 Time 08:15 Rev Time 0.33
Received By alange Date 2006-07-27 Time 08:15 Sent To  
Notes
2006-07-27 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 09:54 Sent To B
Notes
2006-09-17 00:00:00*** UNSAT ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE MISSING DISCONNECT
 FOR THE FEEDERS COMING FROM THE
 GENERARATOR WHICH IS REQUIRED WITHIN
 CLOSE PROXIMITY OF THE EXISTING MAIN.
 225-31, 225.3-
 PLEASE PROVIDE AN OVERVIEW OF HOUSE AND
 LOCATION OF THE SERVICE IN COMPARISON OF
 THE GEN, AND NEW DISOCNNECT REQUIRED.
  
 2) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM EXISTING MAIN
 PANEL TO NEW SUB PANEL.
 250.110,250.122.
  
 3) NOTE: PLEASE VERIFY, THE RISER SEEMS
 TO SHOW THE LV AND HV CONDUCTORS BEING
 INSTALLED IN THE SAME CONDUIT FROM
 GENERATOR.?
 THIS IS ONLY FOR CLARIFICATION.
  
 4) NOTE: PLEASE BE SURE TO PRINT NAME
 AND SIGN ALL PLANS/DESIGNS/LOAD
 CALCULATIONS BEING DONE AND CERTIFIED BY
 THE CONTRACTOR.
 PLEASE SEE HEAT LOAD OS BEING SHOWN AS
 5KW.
  
 ALL SHEETS EXCEPT MANUFACTURES/SPEC/CUT
 SHEETS ARE TO BE SIGNED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 20:56 Sent To M
Notes
2006-07-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE A RISER DIAGRAM
 INCLUDING ALL CONDUCTOR SIZE AND HOW
 THIS PANEL ETC WILL TIE INTO THE
 EXISTING SERVICE.
 PLEASE INDICATE ALL OCP , FEEDERS ETC
 FROM EXISTING.
 PLEASE CLARIFY AND SHOW THE DISCONNECT
 REQUIRED FOR FEEDERS FROM GEN TO HOUSE
 AND BEIGN GROUPED WIHT THE EXISTING
 MAINS/DISCONNECTS.
 PLEASE SHOW AN OVERVIEW FOR LOCATION OF
 ALL EQUIPMENT.
 240.4,310.16,215.5,225.31-225.39
  
 2) NOTE: PLEASE VERIFY HEAT STRIP IN AHU
 AND HOW THE LOAD WILL SHED. PLEASE KNOW,
 IF PART OF UNIT, THEN THE HEAT LOAD AT
 100% WILL BE REQUIRED TO BE FIGURED INTO
 CALCULATIONS.
 220.31
  
 3) NOTE: PLEASE PROVIDE SETBACKS OF GEN
 FOR ALL SIDES FROM PROPERTY , AND ANY
 STRUCTURES.
 PLEASE KNOW, MIN CLEARENCE ON ALL SIDES
 FOR THIS UNIT SHALL BE 3FT PR GREATER OF
 REQUIRED BY MANUFACTURE.
  
 4) NOTE: PLEASE SEE FBC 108.3 ADMIN SECT
 AS THE VALUE FOR THE SCOPE OF WORK SHALL
 INCLUDE ALL LABOR AND MATERIALS EVEN IF
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE ADJUST.
  
 5) NOTE: PLEASE KNOW ALL PLANS DESIGNS
 ETC SHALL CONTAIN THE PRINTED NAME AND
 THE SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS. MUST STATE, DRAWN BY:,,, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-07-26 Cont ID  
Sent By mperson Date 2006-07-26 Time 11:41 Rev Time 0.33
Received By mperson Date 2006-07-26 Time 11:41 Sent To B
Notes
2006-07-26 00:00:00REFERENCE: GAS #06061715

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 18:48 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 18:48 Sent To E
Notes
2006-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 14:04 Sent To E
Notes
2006-07-17 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-01 Cont ID  
Sent By alange Date 2006-07-27 Time 11:22 Rev Time 0.00
Received By alange Date 2006-07-10 Time 09:29 Sent To  
Notes
2006-07-10 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 10:48 Rev Time 0.15
Received By tgordon Date 2006-07-21 Time 10:47 Sent To P
Notes
2006-07-21 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 14:10 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 14:10 Sent To I
Notes
***NONE***