| 2006-07-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- STRUCTURAL DRAWINGS: |
| | A) PROVIDE COMPLETE ENGINEERING |
| | PACKAGE ADDRESSING ALL STRUCTURAL WORK |
| | TO BE PERFORMED ON THE SPECIFIC |
| | BUILDING. INFORMATION SUBMITTED DOESN'T |
| | ADDRESS THIS ISSUE. IT'S GENERAL |
| | INFORMATION AND APPLIES TO CONDO UNITS, |
| | NOT TO THE POOL HOUSE. |
| | B) REVISEADDRESS OF BUILDING. |
| | C) ALL ENGINEERING INFORMATION TO BE |
| | SIGNED AND SEALED AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTES AND FLORIDA |
| | ADMINISTRATIVE CODE. |
| | D) SECOND PAGE IS MISSING THE TITLE |
| | BLOCK AND ADDRESS OF JOB. |
| | E) CONNECTOR SIMPSON H2.5A SPECIFIED ON |
| | DETAIL #1 IS A WOOD TO WOOD CONNECTOR. |
| | NEED TO SPECIFY WOOD TO MASONRY |
| | CONNECTOR. REVISE AS REQUIRED. |
| | F) DETAIL #1: SPECIFY CONNECTORS FOR |
| | NEW (2)2X12 BEAM. |
| | G) SPECIFY HOW ARE NEW 2X4 SCABS |
| | ATTACHED TO BOTTOM OF TRUSS CHORDS? |
| | H) SPECIFY SIZE OF STEEL ANGLES AND |
| | NUMBER OF BOLTS. |
| | I) SPECIFY NEW SOFFITS. |
| | J) DETAIL #5: SPECIFY ALL CONNECTORS. |
| | K) DETAIL #4: SPECIFY SPACING FOR HEX |
| | HEAD BOLTS ALONG THE BEAM. |
| | |
| | 2- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR ALL STRUCTURAL CONNECTORS |
| | SPECIFIED ON DETAILS. |
| | B) DESIGNER OF RECORD TO REVIEW AND |
| | APPROVE ALL PRODUCT APPROVALS PRIOR TO |
| | SUBMITTAL. |
| | |
| | 3- CONTRACTOR TO PROVIDE ALL INFORMATION |
| | AS REQUIRED BY CITY POLICY FOR |
| | RE-ROOFING PERMITS. SEE ATTACHED COPY. |
| | MISSING MEAN ROOF HEIGHT. |
| | |
| | 4- PROVIDE UPLIFT PRESSURE CALCULATIONS |
| | IF BUILDING MEAN ROOF HEIGHT IS HIGHER |
| | THAN 30'-0" TO VERIFY COMPLIANCE OF |
| | CONCRETE ROOF TILE AS REQUIRED BY SEC. |
| | 1609.7 FBC 2004. |
| | |
| | 5- A) REQUIRES TWO DIFFERENT PERMITS. |
| | ONE FOR ROOF STRUCTURAL REPAIRS AND THE |
| | OTHER FOR ROOFING. |
| | B) BRAKE DOWN VALUATION FOR ROOFING AND |
| | FOR STRUCTURAL REPAIRS FOR PROPER PERMIT |
| | VALUATION. |
| | |
| | 6- UNDERLAYMENT PRODUCT APPROVAL. |
| | A) NEED TO PROVIDE THE 2004 FLORIDA |
| | PRODUCT APPROVAL VERSION, NOT 2001. |
| | B) NEED TO PROVIDE TECHNICAL |
| | INFORMATION THAT WAS SUBMITTED TO GET |
| | FLORIDA PRODUCT APPROVAL. GO TO THE DCA |
| | WEBSITE WWW.FLORIDABUILDING.ORG TO |
| | DOWMLOAD ALL INFORMATION. |
| | |
| | 7- PROVIDE COPY OF FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AS REQUIRED BY CITY |
| | RE-ROOFING PERMITS FOR MONIER SPANISH |
| | "S". CONC. ROOF TILE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |