Plan Review Details - Permit 06070160
Plan Review Stops For Permit 06070160
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2006-09-11 Cont ID  
Sent By jgomez Date 2006-09-11 Time 09:48 Rev Time 0.00
Received By jgomez Date 2006-09-11 Time 07:37 Sent To  
Notes
2006-09-11 00:00:00INFORMATION SUBMITTED IS FOR BEAMS
 REPAIRS. IT SHOULD BE SUBMITTED UNDER
 PERMIT #06082049.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By jgomez Date 2006-08-23 Time 14:19 Rev Time 0.50
Received By jgomez Date 2006-08-23 Time 14:19 Sent To PC
Notes
2006-08-23 00:00:00PERMIT UNDER 'Y'.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By jgomez Date 2006-08-11 Time 16:13 Rev Time 0.50
Received By jgomez Date 2006-08-11 Time 16:13 Sent To  
Notes
2006-08-11 00:00:00BUILDING REVIEW 2ND CHECKLIST:
  
 1- CONTRACTOR STATES IN PERMIT
 APPLICATION THAT CONCRETE TILE IS TO BE
 PLACED IN WOOD DECK BATTEN SYSTEM. DADE
 COUNTY NOA #02-1205.07 FOR MONIER
 SPANISH 'S' CONCRETE TILE DOESN'T ALLOW
 BATTEN SYSTEM INSTALLATION. SEE PAGE 4
 OF 5 OF NOA. NEED TO PROVIDE PRODUCT
 APPROVAL THAT ALLOWS BATTEN SYSTEM
 APPLICATION OR PROVIDE SOLID DECK
 SYSTEM.
 PROVIDE COMPLETE STRUCTURAL DRAWINGS AND
 SPECIFICATIONS FOR SOLID DECKING UNDER A
 SEPARATE PERMIT FOR STRUCTURAL WORK.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 AND SEC. 1609 FBC 2004.
  
 2- SELF ADHERING UNDERLAYMENT (FLORIDA
 PRODUCT APPROVAL FL3732-R1) IS NOT
 ALLOWED. SEE RAS 120 FOR TYPES OF
 UNDERLAYMENTS ALLOWED. SPECIFY WHICH
 UNDERLAYMENT IS GOING TO BE USED.
 ALSO, ACCORDING TO THE ROOF SLOPE THERE
 ARE ROOF TILE NAILING REQUIREMENTS. SEE
 RAS 120 AND PROVIDE NAILING
 SPECIFICATIONS AS REQUIRED.
  
 3- ORIGINAL APPLICATION CALLED FOR
 STRUCTURAL REPAIR WORK TO BE PERFORMED.
 ALL REPAIR WORK WAS CROSSED OUT FROM THE
 PERMIT APPLICATION. CLARIFY WHO'S DOING
 THIS WORK AND NEED TO PROVIDE ALL
 STRUCTURAL INFORMATION UNDER A SEPARATE
 PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By jgomez Date 2006-07-12 Time 13:04 Rev Time 0.00
Received By jgomez Date 2006-07-12 Time 12:48 Sent To  
Notes
2006-07-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- STRUCTURAL DRAWINGS:
 A) PROVIDE COMPLETE ENGINEERING
 PACKAGE ADDRESSING ALL STRUCTURAL WORK
 TO BE PERFORMED ON THE SPECIFIC
 BUILDING. INFORMATION SUBMITTED DOESN'T
 ADDRESS THIS ISSUE. IT'S GENERAL
 INFORMATION AND APPLIES TO CONDO UNITS,
 NOT TO THE POOL HOUSE.
 B) REVISEADDRESS OF BUILDING.
 C) ALL ENGINEERING INFORMATION TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
 D) SECOND PAGE IS MISSING THE TITLE
 BLOCK AND ADDRESS OF JOB.
 E) CONNECTOR SIMPSON H2.5A SPECIFIED ON
 DETAIL #1 IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED.
 F) DETAIL #1: SPECIFY CONNECTORS FOR
 NEW (2)2X12 BEAM.
 G) SPECIFY HOW ARE NEW 2X4 SCABS
 ATTACHED TO BOTTOM OF TRUSS CHORDS?
 H) SPECIFY SIZE OF STEEL ANGLES AND
 NUMBER OF BOLTS.
 I) SPECIFY NEW SOFFITS.
 J) DETAIL #5: SPECIFY ALL CONNECTORS.
 K) DETAIL #4: SPECIFY SPACING FOR HEX
 HEAD BOLTS ALONG THE BEAM.
  
 2- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ALL STRUCTURAL CONNECTORS
 SPECIFIED ON DETAILS.
 B) DESIGNER OF RECORD TO REVIEW AND
 APPROVE ALL PRODUCT APPROVALS PRIOR TO
 SUBMITTAL.
  
 3- CONTRACTOR TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
 MISSING MEAN ROOF HEIGHT.
  
 4- PROVIDE UPLIFT PRESSURE CALCULATIONS
 IF BUILDING MEAN ROOF HEIGHT IS HIGHER
 THAN 30'-0" TO VERIFY COMPLIANCE OF
 CONCRETE ROOF TILE AS REQUIRED BY SEC.
 1609.7 FBC 2004.
  
 5- A) REQUIRES TWO DIFFERENT PERMITS.
 ONE FOR ROOF STRUCTURAL REPAIRS AND THE
 OTHER FOR ROOFING.
 B) BRAKE DOWN VALUATION FOR ROOFING AND
 FOR STRUCTURAL REPAIRS FOR PROPER PERMIT
 VALUATION.
  
 6- UNDERLAYMENT PRODUCT APPROVAL.
 A) NEED TO PROVIDE THE 2004 FLORIDA
 PRODUCT APPROVAL VERSION, NOT 2001.
 B) NEED TO PROVIDE TECHNICAL
 INFORMATION THAT WAS SUBMITTED TO GET
 FLORIDA PRODUCT APPROVAL. GO TO THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO
 DOWMLOAD ALL INFORMATION.
  
 7- PROVIDE COPY OF FLORIDA PRODUCT
 APPROVAL COVER PAGE AS REQUIRED BY CITY
 RE-ROOFING PERMITS FOR MONIER SPANISH
 "S". CONC. ROOF TILE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 18:13 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 18:13 Sent To B
Notes
2006-09-08 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 13:51 Sent To B
Notes
2006-08-21 00:00:00TO "JGOMEZ" DESK/RESUB