Plan Review Details - Permit 06070128
Plan Review Stops For Permit 06070128
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-14 Cont ID  
Sent By rmcdouga Date 2006-07-14 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2006-07-14 Time 07:52 Sent To  
Notes
2006-07-14 00:00:00BUILDING PROVISO
  
 1) NEW FLOORING SHALL HAVE A SOUND
 TRANSMISSION CLASS OF NOT LESS THAN 50
 FOR AIR BOURNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90 PER FBC
 1207.2.
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2006-09-14 Cont ID  
Sent By dpalmer Date 2006-09-14 Time 07:03 Rev Time 0.00
Received By dpalmer Date 2006-09-13 Time 21:15 Sent To PC
Notes
2006-09-14 00:00:00*** ELECTRICAL PLANS NOT CODE COMPLIANT,
 THE GC HAS SINCE SAID TO VOID THE
 ELECTRICAL CONTRACTOR FROM HIS PERMIT
 APPLICATION AS A SUB AND ELECTRICAL
 CONTRACTOR WILL SUBMIT HIS OWN PLANS,
 PERMITS AND FEES FOR THE ELECTRICAL DEMO
 AND ELECTRICAL INTERIOR REOMODEL.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
  
  
 1) PLANS DRAWN IN PEN OR PENCIL IS NOT
 PERMITTED AS CHANGES CAN BE DONE WITH
 OUT ANY NOTICE.
 2) PLEASE SEE LOAD CALCULATIONS AND
 PANEL SCHEDULE DOES NOT CORRELATE.
 PLEASE SEE CALCS SHOW A FEED TO "DOCK"
 YET THIS UNIT IS LOCATED ON THE 11TH FLR
 AND THERE IS NO DOCK AT THE LOCATION OF
 THIS BUILDING.
  
 FBC 106.1.2, 2002 NEC.
2006-09-13 00:00:00CALLED CONTRACTOR AND LEFT MESSAGE.
 PLANS DRAWN IN PEN.
 PANEL SCHEDULES AND LOAD CALCS NOT
 SIGNED AND PRINTED NAME.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 14:13 Sent To PC
Notes
2006-08-27 00:00:00**** UNSAT2ND REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM PREVOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW COMMENTS DUE TO
 INFORMATION/CHANGES MADE ON PLANS.
 PLEASE SEE NOTE BWLOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW AS NOTED WITH NEW
 NOTES ADDED TO BOTTOM.
  
 ** PLEASE SEE THE FOLLOWING COMMENTS,
 AND PLEASE KNOW, IT IS RECOMMENED
 ELECTRICAL BE DONE ON A SEPARATE SHEET
 AS THE OTHER REVIEWS HAVE BEEN STAMPED
 AND PASSED.
  
 1) NOTE: NO, PLEASE SEE CIRCUITING IS
 NOT YET ON PLANS WHICH CORRELATES WITH
 THE PANEL SCHEDULE SUBMITTED.
 PLEASE KNOW ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS.408.4
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE LIST ALL THE MIN REQUIRED
 DEDICATED CIRCUITS PER
 210.52,210.11,220.16 ETC
 BATH(S), SM APPL, RANGE, DISH WASHER ,
 DISP, ETYC. PLEASE SEE 240.4,310.16, FBC
 106.1.2 ADMIN SECT.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK, HOWEVER NEW JACUZZI TUB IS
 SHOWN ON PLANS WITH GFI, HOWEVER THIS
 JACUZZI IS NOT ON PANEL SCHEDULE OR IN
 LOAD CALCULATIONS?
 220.31
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE A NEW JACUZZI TUB IS
 NOTED, HOWEVER NO ELECTRICAL IS SHOWN
 FOR THIS AND NO GFI PROTECTION IS
 INDICATED.
 680.71, 240.4,310.16 ETC.
  
 5) NOTE: NO, PLEASE SEE BEDRM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE SW LEGS FOR NEW
 LTS SHOWN TO VERIFY EGRESS CONTROL FOR
 LTS.
 210.70, LS 101 7.8
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO, COULD NOT LOCATE ON PANEL
 SCHEDULE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE NEW OR
 EXISTING BATH GFI RECEPTS PER 210.52D,
 210.8A
  
 9) NOTE: OK.
  
 10) NOTE: NO, PLEASE SEE SAME NOTE.
 CODES RELEVANT TO DESIGN/SCOPE AND PLANS
 IS REQUIRED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT PLANS REFLECT
 THE FOLLOWING CODES AT A MIN.
 2002 NFPA-70, 2002 NFPA-72,
  
 ***** NEW NOTE ****
  
 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 WITH ALL OCP FOR BRANCH CIRCUITS ALONG
 WITH MIN CONDUCTORS PER 240.4,310.16
  
 12) NOTE: PLEASE SEE ONLY ONE SMALL
 APPLIANCE CIRCUIT IS BEING SHOWN IN LOAD
 CALCULATIONS.
 PLEASE SEE 210.52B1,210.11C1,220.16
  
 13) NOTE: PLEASE SEE
 210.52B1,220.11C1,220.16 FOR MIN
 CIRCUITING FOR DINING RM CIRCUIT(S).
 PLEASE ADJUST.
  
 14) NOTE: PLEASE SEE FBC 106.1.2, PLEASE
 BE SURE THE PERSON RESPONSIBLE FOR PLANS
 AND DESIGN CLEARLY PRINTS NAME AND SIGNS
 PLANS .
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 19:19 Sent To  
Notes
2006-07-15 00:00:00**** UNSAT ****
  
 ** PLEASE SEE THE FOLLOWING COMMENTS,
 AND PLEASE KNOW, IT IS RECOMMENED
 ELECTRICLA BE DONE ON A SEPARATE SHEET
 AS THE OTHER REVIEWS HAVE BEEN STAMPED
 AND PASSED.
  
 1) NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE LIST ALL THE MIN REQUIRED
 DEDICATED CIRCUITS PER
 210.52,210.11,220.16 ETC
 BATH(S), SM APPL, RANGE, DISH WASHER ,
 DISP, ETYC. PLEASE SEE 240.4,310.16, FBC
 106.1.2 ADMIN SECT.
  
 2) NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT FOR NEW SD'S BEING ADDED. 210.12B,
 2002 NEC.
  
 3) NOTE: PLEASE SEE SD SEEM TO BE
 MISSING OUTSIDE MAST BEDRM.?
 R313, NFPA-72 11.5.1.1
 ** PLEASE KNOW, ALL SD'S SHALL BE A MIN
 OF 3' FROM ALL BATH AND KITCHEN DOORS
 AND IF WITHIN 20' OF COOKING APPLIANCE,
 THE SD SHALL BE PHOTO-ELECTRIC
 EYE/RESETTING TYPE>
 NFPA-72 11.8.3
  
 4) NOTE: PLEASE SEE A NEW JACUZZI TUB IS
 NOTED, HOWEVER NO ELECTRICAL IS SHOWN
 FOR THIS AND NO GFI PROTECTION IS
 INDICATED.
 680.71, 240.4,310.16 ETC.
  
 5) NOTE: PLEASE COMPLETE SW LEGS FOR NEW
 LTS SHOWN TO VERIFY EGRESS CONTROL FOR
 LTS.
 210.70, LS 101 7.8
  
 6) NOTE: PLEASE SEE BATHS SHALL CONTAIN
 A "LIGHTING OUTLET" AS REQUIRED PER
 210.70. AN EXHAUST FAN WITH A LT IS NOT
 A LIGHTING OUTLET.
 100
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE
 ELECTRICLA PANEL AND IF NEW OR EXISTING.
 PLEASE BE SURE TO SEE
 110.26,408.7,240.24 FOR PERMITTED
 LOCATIONS AND MIN CLEARENCES REQUIRED.
  
 8) NOTE: PLEASE INDICATE THE NEW OR
 EXISTING BATH GFI RECEPTS PER 210.52D,
 210.8A
  
 9) NOTE: PLEASE INDICATE ALL RECEPTS
 SERVING KITCHEN COUNTER SPACE AS GFI/GFI
 PROTECTEDPER 210.8A6.
 AS SHOWN IS FROM THE 1993 NEC.
  
 10) NOTE: PLEASE SEE THAT PLANS REFLECT
 THE FOLLOWING CODES AT A MIN.
 2002 NFPA-70, 2002 NFPA-72,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2006-07-18 Time 09:57 Sent To  
Notes
2006-07-18 00:00:00***PROVISO***
  
 PLEASE SEE ELECTRICAL REVIEW COMMENT (3)
 REGARDING SMOKE DETECTOR LOCATIONS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 09:01 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 09:01 Sent To M
Notes
2006-10-30 09:01:54TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 16:42 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 16:42 Sent To M
Notes
2006-10-25 16:43:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 14:26 Sent To E
Notes
2006-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 11:19 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 11:19 Sent To E
Notes
2006-08-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 10:02 Rev Time 0.00
Received By mwennerg Date 2006-07-07 Time 14:44 Sent To  
Notes
2006-07-11 00:00:00TO "BOB"#15
2006-07-07 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-30 Cont ID  
Sent By tgordon Date 2006-10-30 Time 14:13 Rev Time 0.25
Received By tgordon Date 2006-10-30 Time 14:13 Sent To  
Notes
2006-10-30 14:21:00*** PROVISO ***
 1) PROVIDE RETURN AIR TO ALL REQUIRED ROOMS. PER 2004
 FBC/R M1602.4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-26 Cont ID  
Sent By tgordon Date 2006-10-26 Time 09:25 Rev Time 0.30
Received By tgordon Date 2006-10-26 Time 09:25 Sent To  
Notes
2006-10-26 09:31:56REVISED MECHANICAL PLANS
 *** DENIED ***
 1) PLANS NEED THE ENGINEER RIZANUR ALTAN SEAL ON THEN,
 PER FAC 61G15-23.002.
  
 2) AS A RESULT OF NEW DOORS BEING INSTALLED RETURN AIR
 WILL NEED TO PROVIDE FOR WERE REQUIRED, SEE NOTE #3.
  
 3) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By tgordon Date 2006-07-13 Time 14:01 Rev Time 0.20
Received By tgordon Date 2006-07-13 Time 14:01 Sent To  
Notes
2006-07-13 00:00:00*** PROVISO ***
 1) REMODEL NOT TO INTERFERE WITH
 OPERATION OF EXISTIOG A/C SYSTEM (SUPPLY
 & RETURN AIR).
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-15 Cont ID  
Sent By jleech Date 2006-07-15 Time 12:50 Rev Time 0.00
Received By jleech Date 2006-07-15 Time 12:50 Sent To  
Notes
***NONE***