| Plan Review Stops For Permit 06070128 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-07-14 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-07-14 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2006-07-14 00:00:00 | BUILDING PROVISO | | | | | | 1) NEW FLOORING SHALL HAVE A SOUND | | | TRANSMISSION CLASS OF NOT LESS THAN 50 | | | FOR AIR BOURNE NOISE WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 90 PER FBC | | | 1207.2. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2006-09-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-14 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-13 |
Time |
21:15 |
Sent To |
PC |
|
| Notes |
| 2006-09-14 00:00:00 | *** ELECTRICAL PLANS NOT CODE COMPLIANT, | | | THE GC HAS SINCE SAID TO VOID THE | | | ELECTRICAL CONTRACTOR FROM HIS PERMIT | | | APPLICATION AS A SUB AND ELECTRICAL | | | CONTRACTOR WILL SUBMIT HIS OWN PLANS, | | | PERMITS AND FEES FOR THE ELECTRICAL DEMO | | | AND ELECTRICAL INTERIOR REOMODEL. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | | | | | | | 1) PLANS DRAWN IN PEN OR PENCIL IS NOT | | | PERMITTED AS CHANGES CAN BE DONE WITH | | | OUT ANY NOTICE. | | | 2) PLEASE SEE LOAD CALCULATIONS AND | | | PANEL SCHEDULE DOES NOT CORRELATE. | | | PLEASE SEE CALCS SHOW A FEED TO "DOCK" | | | YET THIS UNIT IS LOCATED ON THE 11TH FLR | | | AND THERE IS NO DOCK AT THE LOCATION OF | | | THIS BUILDING. | | | | | | FBC 106.1.2, 2002 NEC. | | 2006-09-13 00:00:00 | CALLED CONTRACTOR AND LEFT MESSAGE. | | | PLANS DRAWN IN PEN. | | | PANEL SCHEDULES AND LOAD CALCS NOT | | | SIGNED AND PRINTED NAME. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-27 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-27 |
Time |
14:13 |
Sent To |
PC |
|
| Notes |
| 2006-08-27 00:00:00 | **** UNSAT2ND REVIEW **** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVOUS | | | REVIEW STILL NEED TO BE ADDRESSED ALONG | | | WITH NEW COMMENTS DUE TO | | | INFORMATION/CHANGES MADE ON PLANS. | | | PLEASE SEE NOTE BWLOW ARE TAKEN DIRECTLY | | | FROM PREVIOUS REVIEW AS NOTED WITH NEW | | | NOTES ADDED TO BOTTOM. | | | | | | ** PLEASE SEE THE FOLLOWING COMMENTS, | | | AND PLEASE KNOW, IT IS RECOMMENED | | | ELECTRICAL BE DONE ON A SEPARATE SHEET | | | AS THE OTHER REVIEWS HAVE BEEN STAMPED | | | AND PASSED. | | | | | | 1) NOTE: NO, PLEASE SEE CIRCUITING IS | | | NOT YET ON PLANS WHICH CORRELATES WITH | | | THE PANEL SCHEDULE SUBMITTED. | | | PLEASE KNOW ALL CIRCUITS SHALL BE | | | SPECIFIC TO ROOMS AND AREAS.408.4 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE TO BE SUBMITTED. | | | PLEASE LIST ALL THE MIN REQUIRED | | | DEDICATED CIRCUITS PER | | | 210.52,210.11,220.16 ETC | | | BATH(S), SM APPL, RANGE, DISH WASHER , | | | DISP, ETYC. PLEASE SEE 240.4,310.16, FBC | | | 106.1.2 ADMIN SECT. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: OK. | | | | | | 4) NOTE: OK, HOWEVER NEW JACUZZI TUB IS | | | SHOWN ON PLANS WITH GFI, HOWEVER THIS | | | JACUZZI IS NOT ON PANEL SCHEDULE OR IN | | | LOAD CALCULATIONS? | | | 220.31 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE A NEW JACUZZI TUB IS | | | NOTED, HOWEVER NO ELECTRICAL IS SHOWN | | | FOR THIS AND NO GFI PROTECTION IS | | | INDICATED. | | | 680.71, 240.4,310.16 ETC. | | | | | | 5) NOTE: NO, PLEASE SEE BEDRM. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE COMPLETE SW LEGS FOR NEW | | | LTS SHOWN TO VERIFY EGRESS CONTROL FOR | | | LTS. | | | 210.70, LS 101 7.8 | | | | | | 6) NOTE: OK. | | | | | | 7) NOTE: OK. | | | | | | 8) NOTE: NO, COULD NOT LOCATE ON PANEL | | | SCHEDULE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INDICATE THE NEW OR | | | EXISTING BATH GFI RECEPTS PER 210.52D, | | | 210.8A | | | | | | 9) NOTE: OK. | | | | | | 10) NOTE: NO, PLEASE SEE SAME NOTE. | | | CODES RELEVANT TO DESIGN/SCOPE AND PLANS | | | IS REQUIRED ON PLANS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THAT PLANS REFLECT | | | THE FOLLOWING CODES AT A MIN. | | | 2002 NFPA-70, 2002 NFPA-72, | | | | | | ***** NEW NOTE **** | | | | | | 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE | | | WITH ALL OCP FOR BRANCH CIRCUITS ALONG | | | WITH MIN CONDUCTORS PER 240.4,310.16 | | | | | | 12) NOTE: PLEASE SEE ONLY ONE SMALL | | | APPLIANCE CIRCUIT IS BEING SHOWN IN LOAD | | | CALCULATIONS. | | | PLEASE SEE 210.52B1,210.11C1,220.16 | | | | | | 13) NOTE: PLEASE SEE | | | 210.52B1,220.11C1,220.16 FOR MIN | | | CIRCUITING FOR DINING RM CIRCUIT(S). | | | PLEASE ADJUST. | | | | | | 14) NOTE: PLEASE SEE FBC 106.1.2, PLEASE | | | BE SURE THE PERSON RESPONSIBLE FOR PLANS | | | AND DESIGN CLEARLY PRINTS NAME AND SIGNS | | | PLANS . | | | | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
19:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-15 |
Time |
19:19 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | **** UNSAT **** | | | | | | ** PLEASE SEE THE FOLLOWING COMMENTS, | | | AND PLEASE KNOW, IT IS RECOMMENED | | | ELECTRICLA BE DONE ON A SEPARATE SHEET | | | AS THE OTHER REVIEWS HAVE BEEN STAMPED | | | AND PASSED. | | | | | | 1) NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH A PANEL | | | SCHEDULE TO BE SUBMITTED. | | | PLEASE LIST ALL THE MIN REQUIRED | | | DEDICATED CIRCUITS PER | | | 210.52,210.11,220.16 ETC | | | BATH(S), SM APPL, RANGE, DISH WASHER , | | | DISP, ETYC. PLEASE SEE 240.4,310.16, FBC | | | 106.1.2 ADMIN SECT. | | | | | | 2) NOTE: PLEASE LIST THE REQUIRED ARC | | | FAULT FOR NEW SD'S BEING ADDED. 210.12B, | | | 2002 NEC. | | | | | | 3) NOTE: PLEASE SEE SD SEEM TO BE | | | MISSING OUTSIDE MAST BEDRM.? | | | R313, NFPA-72 11.5.1.1 | | | ** PLEASE KNOW, ALL SD'S SHALL BE A MIN | | | OF 3' FROM ALL BATH AND KITCHEN DOORS | | | AND IF WITHIN 20' OF COOKING APPLIANCE, | | | THE SD SHALL BE PHOTO-ELECTRIC | | | EYE/RESETTING TYPE> | | | NFPA-72 11.8.3 | | | | | | 4) NOTE: PLEASE SEE A NEW JACUZZI TUB IS | | | NOTED, HOWEVER NO ELECTRICAL IS SHOWN | | | FOR THIS AND NO GFI PROTECTION IS | | | INDICATED. | | | 680.71, 240.4,310.16 ETC. | | | | | | 5) NOTE: PLEASE COMPLETE SW LEGS FOR NEW | | | LTS SHOWN TO VERIFY EGRESS CONTROL FOR | | | LTS. | | | 210.70, LS 101 7.8 | | | | | | 6) NOTE: PLEASE SEE BATHS SHALL CONTAIN | | | A "LIGHTING OUTLET" AS REQUIRED PER | | | 210.70. AN EXHAUST FAN WITH A LT IS NOT | | | A LIGHTING OUTLET. | | | 100 | | | | | | 7) NOTE: PLEASE SHOW THE LOCATION OF THE | | | ELECTRICLA PANEL AND IF NEW OR EXISTING. | | | PLEASE BE SURE TO SEE | | | 110.26,408.7,240.24 FOR PERMITTED | | | LOCATIONS AND MIN CLEARENCES REQUIRED. | | | | | | 8) NOTE: PLEASE INDICATE THE NEW OR | | | EXISTING BATH GFI RECEPTS PER 210.52D, | | | 210.8A | | | | | | 9) NOTE: PLEASE INDICATE ALL RECEPTS | | | SERVING KITCHEN COUNTER SPACE AS GFI/GFI | | | PROTECTEDPER 210.8A6. | | | AS SHOWN IS FROM THE 1993 NEC. | | | | | | 10) NOTE: PLEASE SEE THAT PLANS REFLECT | | | THE FOLLOWING CODES AT A MIN. | | | 2002 NFPA-70, 2002 NFPA-72, | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-18 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-18 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2006-07-18 00:00:00 | ***PROVISO*** | | | | | | PLEASE SEE ELECTRICAL REVIEW COMMENT (3) | | | REGARDING SMOKE DETECTOR LOCATIONS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-30 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-30 |
Time |
09:01 |
Sent To |
M |
|
| Notes |
| 2006-10-30 09:01:54 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-25 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-25 |
Time |
16:42 |
Sent To |
M |
|
| Notes |
| 2006-10-25 16:43:47 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-08 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-08 |
Time |
14:26 |
Sent To |
E |
|
| Notes |
| 2006-09-08 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
11:19 |
Sent To |
E |
|
| Notes |
| 2006-08-23 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-18 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-07 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | TO "BOB"#15 | | 2006-07-07 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-30 |
Time |
14:13 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2006-10-30 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2006-10-30 14:21:00 | *** PROVISO *** | | | 1) PROVIDE RETURN AIR TO ALL REQUIRED ROOMS. PER 2004 | | | FBC/R M1602.4. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-26 |
Time |
09:25 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-26 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2006-10-26 09:31:56 | REVISED MECHANICAL PLANS | | | *** DENIED *** | | | 1) PLANS NEED THE ENGINEER RIZANUR ALTAN SEAL ON THEN, | | | PER FAC 61G15-23.002. | | | | | | 2) AS A RESULT OF NEW DOORS BEING INSTALLED RETURN AIR | | | WILL NEED TO PROVIDE FOR WERE REQUIRED, SEE NOTE #3. | | | | | | 3) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-13 |
Time |
14:01 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-07-13 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2006-07-13 00:00:00 | *** PROVISO *** | | | 1) REMODEL NOT TO INTERFERE WITH | | | OPERATION OF EXISTIOG A/C SYSTEM (SUPPLY | | | & RETURN AIR). | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-15 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-15 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|