| Plan Review Stops For Permit 06070094 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-11-02 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-11-02 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-20 |
Time |
10:35 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-07-20 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-01 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-31 |
Time |
07:07 |
Sent To |
I |
|
| Notes |
| 2006-11-01 07:14:30 | OK, STAMPED ELEC SHEETS. SENT BACK TO INCOMING. | | 2006-10-31 17:55:37 | REMOVED FROM INCOMING, IN ELEC FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-15 |
Time |
18:25 |
Sent To |
|
|
| Notes |
| 2006-07-15 00:00:00 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE CLARIFY THE ROOM IN | | | WHICH THE NEW VAV PANEL IS BEING | | | INSTALLED. PLEASE KNOW AND NOTE ON PLANS | | | THAT THIS RM SHALL BE AN ELEC/MECH RM | | | ONLY CONTAINING NO STORAGE. | | | 110.26,240.24,408.7 ETC. | | | SIGNAGE REQUIRED ON DOOR STATING " NO | | | STORAGE" OR WORDS TO THE EFFECT. | | | MIN 1" ON CONTRASTING BACKGROUND. | | | | | | 2) NOTE: PLEASE SPECIFY THE CURRENT NEC | | | ( NFPA-70) OF 2002. PLANS NOTE THE | | | LATEST EDITION, HOWEVER THE LATEST NEC | | | (2005 ) HAS NOT BEEN ADOPTED AS OF YET. | | | | | | 3) NOTE: PLEASE SEE TITLE BLOCKS OF | | | SHEET SHOULD CORRELATE AS A-SHEETS | | | MENTIONS THE GOVERNMENTAL BUILDING, YET | | | E-SHEETS MENTIONS THE ADMINISTRATIVE | | | OFFICE COMPLEX WHICH IS NOT THE SAME. | | | PLEASE KNOW, PER THE PERMIT APPLICATION, | | | WORK IS APPLIED FOR UNDER 301 N OLIVE | | | WHICH SHOULD BE REFLECTED ON PLANS, | | | WHICH IS THE GOV. CENTER. | | | | | | 4) NOTE: NOTE ON PLANS MENTIONS ROUTING | | | OF NEW CONDUIT AND MENTIONS NEW PANEL | | | NEAR STAIRWELL, PLEASE KNOW, THE FEEDERS | | | AND CONDUIT MAY NOT BE RUN IN STAIRWAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-11-02 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-11-02 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2006-11-02 13:44:30 | ***APPROVED*** | | | | | | 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 2) FIRE AND SMOKE DETECTOR INSTALLATIONS SHALL BE | | | TESTED FOR CLOSURE IN ACCORDANCE WITH UL 555. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-18 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-18 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2006-07-18 00:00:00 | ***PROVISO*** | | | | | | | | | 1) IN ACCORDANCE WITH LOCAL REQUIREMENTS | | | DUCT SMOKE DETECTOR INSTALLATIONS SHALL | | | BE TIED TO THE FIRE ALARM SYSTEM, AND | | | INITIATE A GENERAL FIRE ALARM WHEN | | | ACTIVATED. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-28 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-28 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2006-11-02 09:33:07 | TO "BOB"#11 | | 2006-10-28 14:47:19 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-20 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-07 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | TO "BOB"#14 | | 2006-07-07 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-02 |
Time |
15:48 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-11-02 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2006-11-02 15:52:02 | *** PROVISO *** | | | 1) CONDENSATE DRAIN TO DISCHARGE AT THE ROOF DRAIN NOT | | | ONTO THE ROOF, PER 2004 FBC/M 307.2.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-12 |
Time |
14:15 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-07-12 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | *** DENIED *** | | | 1) OPEN FLOOR DRAINS CAN NOT BE IN A | | | MECHANICAL ROOM THAT IS AN OPEN PLENUM, | | | PER 2004 FBC/P 901.2, FBC/M 601.3, AND | | | ASHARE 8.4.1.11 . | | | | | | 2) PLANS THAT HAVE AN ENGINEER'S SEAL ON | | | THEM MUST ALSO HAVE THE ENGINEER'S | | | PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER ON EACH SHEET, PER FAC | | | 61G15-23.002 . | | | | | | 3) PLEASE HAVE JOB ADDRESS ADDED TO | | | TITLE BLOCK, PER 2004 FBC 106.1.1 . | | | | | | 4) PLEASE SHOW SIZE OF ALL RETURN AIR | | | TRANSFER DUCTS, SEE NOTE #5 (A). | | | | | | 5) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|