Plan Review Details - Permit 06070080
Plan Review Stops For Permit 06070080
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 08:09 Rev Time 0.25
Received By alange Date 2006-07-25 Time 08:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-14 Cont ID  
Sent By dpalmer Date 2006-11-14 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2006-11-14 Time 12:59 Sent To PC
Notes
2006-11-14 16:21:24**** UNSAT *****
  
 **PLEASE SEE RISER(S) HAVE NOW BEEN COMPLETELY REVISED
 FROM ORIGINAL STAMPED PLANS. PLEASE SEE NEW COMMENTS
 BELOW BASED ON RISERS NOW SUBMITTED.
  
  
 1) NOTE: PLEASE SEE SEC?S ARE NOW BEING SHOWN AS #1?S
 WITH 200A OCP WHICH IS NOT PERMITTED.
 PLEASE SEE 240.4, 310.16 230.70, 240.20 ETC.
  
 2) NOTE: PLEASE SEE 200A BREAKERS FEEDING 150A RATED
 PANELS WHICH ARE ALSO NOT PERMITTED.
 PLEASE SEE THE NEC 230, 240, 408 ETC
  
 3) NOTE: PLEASE SEE RISER WHICH INDICATES AN EQUIPMENT
 GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6, 250.24B.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By dpalmer Date 2006-09-07 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2006-09-07 Time 07:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 18:39 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 18:25 Sent To Z
Notes
2006-08-07 00:00:00***** UNSAT2ND REVIEW ******
  
 **PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW ARE STILL IN NEED OF ADDRESSING.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1) NOTE: OK.
  
  
 2) NOTE: NO, PLEASE SEE MISSING A
 DISCONNECTING MEANS FOR FEEDERS FROM
 GEN. THIS CAN BE ON THE LINE SIDE OF ATS
 OR ON THE LOAD SIDE OF THE ATS GROUPED
 WITH EXISTING MAIN. PLEASE SEE THE
 "TOGGLE" SWITCH IS NOT ACCEPATABLE AS A
 DISCONNECTING MEANS. THE DISCONNECT MUST
 BE RATED FOR THE LOAD SERVED AND
 GROUPED. (IT DOES NOT NEED TO CONTAIN
 OCP.)PLEASE SEE 225.31-225.39
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT FOR ALL
 SERVICE EQUIPMENT. PLEASE KNOW,
 DISCONNECTING MEANS FOR THE FEEDER
 COMING FROM GEN MAY BE REQUIRED IF THE
 SE RATED ATS IS NOT GROUPED WITH THE
 EXISITNG MCB PANEL. PLEASE KNOW THE
 BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR
 THE REQUIRED MEANS OF DISCONNECT.
 IT SEEMS THEY ARE GROUPED BUT UNCLEAR AT
 THIS TIME?
 ** THE SE RATED ATS'S ONLY DISCONNECT
 THE POWER FROM THE NORMAL/FPL SIDE.
 225.31-225.39,110.27 ETC.
  
 3) NOTE:NO, PLEASE SEE THIS ALSO
 INCLUDES THE LOAD CALCULATIONS PAGES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE:OK, REVISED HOWEVER PLEASE SEE
 REVISED SURVEY IS BEING ROUTED TO ZONING
 SO THAT SETBACK NOW REVISED IS STILL OK.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE KNOW, THE GEN WILL BE
 REQUIRED TO BE LOCATED A MIN OF 5' FROM
 THE DWELLING AND ANY OTHER SURROUNDING
 STRUCTURAL ELEMENTS.
 PLEASE KNOW, AS PER LETTER OBTAINED FROM
 GENERAC, THE MIN RECOMMENDED CLEARENCES
 FOR LIQUID COOLED UNITS IS 5FT.
 PLEASE SEE THAT MANUFACTURE SPECS
 SUBMITTED INDICATED THE MIN CLEARENCE.
 110.3,
 ** PLEASE KNOW, THE SITE PLAN WHICH WAS
 STAMPED BY ZONING WILL NEED TO BE
 REVISED IF UNIT IS 5FT FROM DWELLING.
  
 5) NOTE: PLEASE SEE RISER SHOWS ONLY A
 #8 FROM GEN TO ATS. PLEASE SEE 250.122
 FOR MIN SIZE REQUIRED FOR OCP PROVIDED.
 (# 6 MIN).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 13:54 Sent To M
Notes
2006-07-16 00:00:00***** UNSAT ******
  
 1) NOTE: PLEASE SEE RISER DOES NOT
 INDICATE THE CONDUCTORS FROM METER TO SE
 RATED ATS AND FROM ATS TO EXISTING
 PANEL.
 PLEASE BE SURE TO ADD EQUIPMENT
 GROUNDING AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE ALSO KNOW, ALL GRNDS
 AND NEUTRALS WILL BE REQUIRED TO BE
 SEPARATED IN THE EXISTING MCB PANEL.
  
 2) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL
 SERVICE EQUIPMENT. PLEASE KNOW,
 DISCONNECTING MEANS FOR THE FEEDER
 COMING FROM GEN MAY BE REQUIRED IF THE
 SE RATED ATS IS NOT GROUPED WITH THE
 EXISITNG MCB PANEL. PLEASE KNOW THE
 BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR
 THE REQUIRED MEANS OF DISCONNECT.
 IT SEEMS THEY ARE GROUPED BUT UNCLEAR AT
 THIS TIME?
 ** THE SE RATED ATS'S ONLY DISCONNECT
 THE POWER FROM THE NORMAL/FPL SIDE.
 225.31-225.39,110.27 ETC.
  
 3) NOTE: PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE: PLEASE KNOW, THE GEN WILL BE
 REQUIRED TO BE LOCATED A MIN OF 5' FROM
 THE DWELLING AND ANY OTHER SURROUNDING
 STRUCTURAL ELEMENTS.
 PLEASE KNOW, AS PER LETTER OBTAINED FROM
 GENERAC, THE MIN RECOMMENDED CLEARENCES
 FOR LIQUID COOLED UNITS IS 5FT.
 PLEASE SEE THAT MANUFACTURE SPECS
 SUBMITTED INDICATED THE MIN CLEARENCE.
 110.3,
 ** PLEASE KNOW, THE SITE PLAN WHICH WAS
 STAMPED BY ZONING WILL NEED TO BE
 REVISED IF UNIT IS 5FT FROM DWELLING.
  
 5) NOTE: PLEASE SEE RISER SHOWS ONLY A
 #8 FROM GEN TO ATS. PLEASE SEE 250.122
 FOR MIN SIZE REQUIRED FOR OCP PROVIDED.
 (# 6 MIN).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By mperson Date 2006-07-19 Time 15:54 Rev Time 0.45
Received By mperson Date 2006-07-19 Time 15:53 Sent To B
Notes
2006-07-19 00:00:00REFERENCE: GAS #06070081

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 13:21 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 13:21 Sent To E
Notes
2006-11-09 13:21:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 16:17 Sent To E
Notes
2006-08-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 14:54 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 14:54 Sent To Z
Notes
2006-08-25 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 14:36 Rev Time 0.00
Received By adarroug Date   Time   Sent To E
Notes
2006-08-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 08:14 Sent To E
Notes
2006-07-11 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 08:09 Rev Time 0.00
Received By alange Date 2006-07-06 Time 16:04 Sent To  
Notes
2006-07-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-07-14 Cont ID  
Sent By tgordon Date 2006-07-14 Time 12:08 Rev Time 0.15
Received By tgordon Date 2006-07-14 Time 12:08 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-26 Cont ID  
Sent By mmclean Date 2006-08-26 Time 08:00 Rev Time 0.00
Received By mmclean Date 2006-08-26 Time 08:00 Sent To I
Notes
2006-08-26 00:00:00PROVISO:
 THE PROPOSED GAS TANK SHALL NOT BE
 CLOSER THAN 16FT FROM FRONT PROPERTY
 LINE.
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 4FT FROM SIDE PROPERTY LINE.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By mmclean Date 2006-08-10 Time 16:26 Rev Time 0.00
Received By mmclean Date 2006-08-10 Time 16:26 Sent To  
Notes
2006-08-10 00:00:00DENIED,
 1. THE TANK MUST BE 16FT FROM THE FRONT
 PROPERTY LINE.
 2. PLEASE INDICATE SO ON THE TWO COPY OF
 CURRENT SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2006-08-07 00:00:00REVISED LOCATION

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-08 Cont ID  
Sent By mmclean Date 2006-07-08 Time 12:01 Rev Time 0.00
Received By mmclean Date 2006-07-08 Time 12:00 Sent To I
Notes
***NONE***