| 2006-08-07 00:00:00 | ***** UNSAT2ND REVIEW ****** |
| | |
| | **PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW ARE STILL IN NEED OF ADDRESSING. |
| | NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW. |
| | |
| | 1) NOTE: OK. |
| | |
| | |
| | 2) NOTE: NO, PLEASE SEE MISSING A |
| | DISCONNECTING MEANS FOR FEEDERS FROM |
| | GEN. THIS CAN BE ON THE LINE SIDE OF ATS |
| | OR ON THE LOAD SIDE OF THE ATS GROUPED |
| | WITH EXISTING MAIN. PLEASE SEE THE |
| | "TOGGLE" SWITCH IS NOT ACCEPATABLE AS A |
| | DISCONNECTING MEANS. THE DISCONNECT MUST |
| | BE RATED FOR THE LOAD SERVED AND |
| | GROUPED. (IT DOES NOT NEED TO CONTAIN |
| | OCP.)PLEASE SEE 225.31-225.39 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE A LAYOUT FOR ALL |
| | SERVICE EQUIPMENT. PLEASE KNOW, |
| | DISCONNECTING MEANS FOR THE FEEDER |
| | COMING FROM GEN MAY BE REQUIRED IF THE |
| | SE RATED ATS IS NOT GROUPED WITH THE |
| | EXISITNG MCB PANEL. PLEASE KNOW THE |
| | BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR |
| | THE REQUIRED MEANS OF DISCONNECT. |
| | IT SEEMS THEY ARE GROUPED BUT UNCLEAR AT |
| | THIS TIME? |
| | ** THE SE RATED ATS'S ONLY DISCONNECT |
| | THE POWER FROM THE NORMAL/FPL SIDE. |
| | 225.31-225.39,110.27 ETC. |
| | |
| | 3) NOTE:NO, PLEASE SEE THIS ALSO |
| | INCLUDES THE LOAD CALCULATIONS PAGES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, ALL PLANS SHALL |
| | BEAR THE PRINTED NAME AND THE SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR |
| | PLANS/DESIGN. |
| | FBC ADMIN SECT 106.1.2 |
| | |
| | 4) NOTE:OK, REVISED HOWEVER PLEASE SEE |
| | REVISED SURVEY IS BEING ROUTED TO ZONING |
| | SO THAT SETBACK NOW REVISED IS STILL OK. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, THE GEN WILL BE |
| | REQUIRED TO BE LOCATED A MIN OF 5' FROM |
| | THE DWELLING AND ANY OTHER SURROUNDING |
| | STRUCTURAL ELEMENTS. |
| | PLEASE KNOW, AS PER LETTER OBTAINED FROM |
| | GENERAC, THE MIN RECOMMENDED CLEARENCES |
| | FOR LIQUID COOLED UNITS IS 5FT. |
| | PLEASE SEE THAT MANUFACTURE SPECS |
| | SUBMITTED INDICATED THE MIN CLEARENCE. |
| | 110.3, |
| | ** PLEASE KNOW, THE SITE PLAN WHICH WAS |
| | STAMPED BY ZONING WILL NEED TO BE |
| | REVISED IF UNIT IS 5FT FROM DWELLING. |
| | |
| | 5) NOTE: PLEASE SEE RISER SHOWS ONLY A |
| | #8 FROM GEN TO ATS. PLEASE SEE 250.122 |
| | FOR MIN SIZE REQUIRED FOR OCP PROVIDED. |
| | (# 6 MIN). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |