Plan Review Details - Permit 06070079
Plan Review Stops For Permit 06070079
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-24 Cont ID  
Sent By mperson Date 2006-07-19 Time 15:01 Rev Time 0.50
Received By alange Date 2006-07-24 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-14 Cont ID  
Sent By dpalmer Date 2006-11-14 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2006-11-14 Time 12:59 Sent To PC
Notes
2006-11-14 16:24:37**** UNSAT *****
  
 **PLEASE SEE RISER(S) HAVE NOW BEEN COMPLETELY REVISED
 FROM ORIGINAL STAMPED PLANS. PLEASE SEE NEW COMMENTS
 BELOW BASED ON RISERS NOW SUBMITTED.
  
  
 1) NOTE: PLEASE SEE SEC'S ARE NOW BEING SHOWN AS #1'S
 WITH 200A OCP WHICH IS NOT PERMITTED.
 PLEASE SEE 240.4, 310.16 230.70, 240.20 ETC.
  
 2) NOTE: PLEASE SEE 200A BREAKERS FEEDING 150A RATED
 PANELS WHICH ARE ALSO NOT PERMITTED.
 PLEASE SEE THE NEC 230, 240, 408 ETC
  
 3) NOTE: PLEASE SEE RISER WHICH INDICATES AN EQUIPMENT
 GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.6, 250.24B.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-05 Cont ID  
Sent By dpalmer Date 2006-09-05 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2006-09-05 Time 16:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 18:43 Sent To Z
Notes
2006-08-07 00:00:00***** UNSAT ******
  
 1) NOTE: NO, PLEASE SEE RISER WAS NOT
 REVISED TO SHOW CONDUITS, PLEASE SEE ONE
 CONDUIT FROM THE METERCAN SEEM TO SHOW
 RUNNING THROUGH ONE ATS TO GET TO THE
 OTHER? PLEASE SEE PREVIOUS NOTES WITH
 REPECT TO USING THIS ATS AS A RACEWAY
 FOR SEC'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER DOES NOT
 INDICATE THE CONDUITS FROM THE ATS'S TO
 THE EXISTING PANELS. MAY NOT RUN FEEDERS
 BACK THROUGH METER CAN.
 230.7, 408 ETC.
 MAY NOT HAVE LINE AND LOAD IN THE SAME
 RACEWAY OR ENCLOSURE.
 PLEASE KNOW, RISER WILL SUBSTANTIALLY
 CHANGE FROM SUBMITTED PLANS.
  
 2) NOTE:NO, PLEASE SEE A LAYOUT WAS
 PROIVIDED, HOWEVER PLEASE SEE MISSING
 DISCONNECTING MEANS FOR FEEDERS FROM
 GENERATOR. PLEASE SEE THIS DISCONNECT
 DOES NOT REQUIRE OCP, ONLY A DISCONNECT
 RATED FOR THE LOAD SERVED AND GROUPED
 WIHT THE EXISTING (NEW) MAINS. PLEASE
 SEE THIS MAY BE PALCED ON FEEDER CONDUIT
 BEFORE THE ATS OR TWO DISCOONECTS WOULD
 BE REQUIRED AFTER THE ATS GOING INTO
 HOUSE. A 200A RATED DISCONNECT SEEMS THE
 BEST OPTION, HOWEVER ONLY A SUGGESTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT FOR ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE
 DISCONNECTING MEANS FOR THE FEEDER
 COMING FROM GEN. THIS NEED ONLY BE
 DISCONECT, DOES NOT REQUIRE OCP. THIS
 MAY BE ONE ON THE LINE SIDE OF ATS'S
 FROM GEN OR TWO DISCONNECTS ON THE LOAD
 SIDE OF THE ATS'S.PLEASE KNOW, IF THE
 EXISTING MCB PANELS ARE OUTSIDE GROUPED
 WITH THE NEW SE RATED ATS'S THEN A THE
 DISCONNECTING MEANS NOTED ABOVE WOULD
 NOT BE REQUIRED. (( PLEASE KNOW, THE
 BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR
 THE REQUIRED MEANS OF DISCONNECT.
 ** THE SE RATED ATS'S ONLY DISCONNECT
 THE POWER FROM THE NORMAL/FPL SIDE.
 225.31-225.39,110.27 ETC.
  
 3) NOTE: NO, THIS INCLUDES LOAD
 CALCULATIONS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE:OK, HOWEVER PLANS ARE BEING
 ROUTED TO ZONING FOR VERIFICATION OF SET
 BACK.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW, THE GEN WILL BE
 REQUIRED TO BE LOCATED A MIN OF 5' FROM
 THE DWELLING AND ANY OTHER SURROUNDING
 STRUCTURAL ELEMENTS.
 PLEASE KNOW, AS PER LETTER OBTAINED FROM
 GENERAC, THE MIN RECOMMENDED CLEARENCES
 FOR LIQUID COOLED UNITS IS 5FT.
 PLEASE SEE THAT MANUFACTURE SPECS
 SUBMITTED INDICATED THE MIN CLEARENCE.
 110.3,
 ** PLEASE KNOW, THE SITE PLAN WHICH WAS
 STAMPED BY ZONING WILL NEED TO BE
 REVISED IF UNIT IS 5FT FROM DWELLING.
  
 ** NEW NOTE **
 5) NOTE: PLEASE SEE TWO SMALL APPL
 CIRCUITS ARE BEING INDICATED, HOWEVER
 SHOWS 3500 VA. PLEASE SEE 220.16 (1500VA
 EACH).
 PLEASE ALSO SEE 220.18 AS THE MIN VA TO
 BE FIGURED FOR ELEC DRYERS ARE 5000VA
 PLEASE ADJUST CALCULATIONS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-16 Cont ID  
Sent By dpalmer Date 2006-07-16 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2006-07-16 Time 13:37 Sent To M
Notes
2006-07-16 00:00:00***** UNSAT ******
  
 1) NOTE: PLEASE SEE RISER DOES NOT
 INDICATE THE CONDUITS FROM THE ATS'S TO
 THE EXISTING PANELS. MAY NOT RUN FEEDERS
 BACK THROUGH METER CAN.
 230.7, 408 ETC.
 MAY NOT HAVE LINE AND LOAD IN THE SAME
 RACEWAY OR ENCLOSURE.
 PLEASE KNOW, RISER WILL SUBSTANTIALLY
 CHANGE FROM SUBMITTED PLANS.
  
 2) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE
 DISCONNECTING MEANS FOR THE FEEDER
 COMING FROM GEN. THIS NEED ONLY BE
 DISCONECT, DOES NOT REQUIRE OCP. THIS
 MAY BE ONE ON THE LINE SIDE OF ATS'S
 FROM GEN OR TWO DISCONNECTS ON THE LOAD
 SIDE OF THE ATS'S.PLEASE KNOW, IF THE
 EXISTING MCB PANELS ARE OUTSIDE GROUPED
 WITH THE NEW SE RATED ATS'S THEN A THE
 DISCONNECTING MEANS NOTED ABOVE WOULD
 NOT BE REQUIRED. (( PLEASE KNOW, THE
 BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR
 THE REQUIRED MEANS OF DISCONNECT.
 ** THE SE RATED ATS'S ONLY DISCONNECT
 THE POWER FROM THE NORMAL/FPL SIDE.
 225.31-225.39,110.27 ETC.
  
 3) NOTE: PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE: PLEASE KNOW, THE GEN WILL BE
 REQUIRED TO BE LOCATED A MIN OF 5' FROM
 THE DWELLING AND ANY OTHER SURROUNDING
 STRUCTURAL ELEMENTS.
 PLEASE KNOW, AS PER LETTER OBTAINED FROM
 GENERAC, THE MIN RECOMMENDED CLEARENCES
 FOR LIQUID COOLED UNITS IS 5FT.
 PLEASE SEE THAT MANUFACTURE SPECS
 SUBMITTED INDICATED THE MIN CLEARENCE.
 110.3,
 ** PLEASE KNOW, THE SITE PLAN WHICH WAS
 STAMPED BY ZONING WILL NEED TO BE
 REVISED IF UNIT IS 5FT FROM DWELLING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By mperson Date 2006-07-19 Time 14:49 Rev Time 0.45
Received By mperson Date 2006-07-19 Time 14:49 Sent To B
Notes
2006-07-19 00:00:00REFERENCE: GAS PERMIT #06070086

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 13:35 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 13:35 Sent To E
Notes
2006-11-09 13:36:02TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 15:14 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 15:14 Sent To E
Notes
2006-08-25 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 14:35 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 14:34 Sent To E
Notes
2006-08-02 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-10 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 16:39 Sent To E
Notes
2006-07-10 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-24 Cont ID  
Sent By alange Date 2006-07-24 Time 09:16 Rev Time 0.00
Received By alange Date 2006-07-06 Time 16:09 Sent To  
Notes
2006-07-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-07-14 Cont ID  
Sent By tgordon Date 2006-07-14 Time 12:12 Rev Time 0.10
Received By tgordon Date 2006-07-14 Time 12:12 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-05 Cont ID  
Sent By dpalmer Date 2006-09-05 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2006-09-05 Time 16:44 Sent To  
Notes
2006-09-05 00:00:00OK AND RE-STAMPED PER MICHELLE MCLEAN
2006-08-07 00:00:00REVISED SET BACKS AND LOCATION OF GEN

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-08 Cont ID  
Sent By mmclean Date 2006-07-08 Time 11:55 Rev Time 0.00
Received By mmclean Date 2006-07-08 Time 11:55 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy