| Plan Review Stops For Permit 06070070 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-07-18 |
Time |
09:24 |
Rev Time |
0.75 |
| Received By |
amorse |
Date |
2006-07-18 |
Time |
09:24 |
Sent To |
PC |
|
| Notes |
| 2006-07-18 00:00:00 | | | | | | | DENIED | | | | | | 1) PER 1019.1.2 PENETRATIONS.FBC | | | PENETRATIONS INTO AND OPENINGS THROUGH | | | AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT | | | FOR REQUIRED EXIT DOORS, EQUIPMENT AND | | | DUCTWORK NECESSARY FOR INDEPENDENT | | | PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE | | | DEPARTMENT COMMUNICATION AND ELECTRICAL | | | RACEWAY SERVING THE EXIT ENCLOSURE AND | | | TERMINATING AT A STEEL BOX NOT EXCEEDING | | | 16 SQUARE INCHES (0.010 M 2 ). SUCH | | | PENETRATIONS SHALL BE PROTECTED IN | | | ACCORDANCE WITH SECTION 712 . THERE | | | SHALL BE NO PENETRATIONS OR | | | COMMUNICATION OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT | | | ENCLOSURES. | | | | | | 2) PERMIT NUMBER 06060243 WAS ISSUED FOR | | | THE REMOVAL OF ALL PIPINNG FROM | | | STAIRWELLS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|