| Plan Review Stops For Permit 06070027 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-13 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-07-13 |
Time |
10:09 |
Rev Time |
0.75 |
| Received By |
amorse |
Date |
2006-07-13 |
Time |
10:09 |
Sent To |
PC |
|
| Notes |
| 2006-07-13 00:00:00 | | | | | | | DENIED | | | | | | 1) FLOOR PLAN SHALL SHOW BEDROOM LAYOUT | | | AND WHERE THE 2 DIFFERENT WINDOWS ARE TO | | | BE INSTALLED. BE AWARE THAT THE EGRESS | | | SWING OPEN WINDOWS FROM BOTH NOA'S HAVE | | | A MAXIMUM SIZE LIMITATION OF 37"X50 5/8" | | | IF YOU PLAN TO PUT 2 TOGETHER IN THE 75" | | | OPENING A MULLION WOULD BE NECESSARY AND | | | A PRODUCT APPROVAL WILL BE REQUIRED. | | | | | | 2) PROVIDE ENGINEERED DESIGN FOR INFILL | | | ESPECIALLY WHERE THE NEW WINDOW WILL BE | | | ATTACHED, ALSO DETAIL THE NEW BUCK | | | ATTACHMENT THAT SHALL BE DESIGNED TO | | | TRANSFER THE WIND LOADS PLACED ON THE | | | WINDOW TO THE STRUCTURE PER 1714.5.4.2 | | | FBC | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-07-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-06 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | TO "MISC" BOX#1 |
|
|
|