| 2006-07-10 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW: |
| | |
| | 1. PER PHONE CONVERSATION ON 7/10/06 |
| | WITH R. IRWIN GAS SYSTEM TO BE 0.5 PSI. |
| | THE SUBMITTED PRINTS INDICATE A 2LB PSI |
| | SYSTEM. NOTE: THE SUBMITTED PRINTS ARE |
| | SIGNED AND SEALED BY AN ENGINEER AND ANY |
| | CHANGES TO THE PRINT SHALL BE MADE BY |
| | THE ENGINEER OF RECORD. |
| | 2. NOTE: ANY BELOW GROUND PIPING TO BE |
| | COPPER OR OTHER APPROVED MATERIAL PER |
| | FBC-2004 FUEL GAS. GALVANIZED PIPING |
| | BELOW GROUND SHALL NOT BE USED PER |
| | FBC-2004 FUEL GAS, SECTION 404.8. PLEASE |
| | INDICATE THE BELOW GROUND MATERIAL TYPE |
| | ON THE PRINT FOR RESUBMITTAL. |
| | 3. THE POOL HEATER IS SIZED WRONG PER |
| | FBC-2004 FUEL GAS, TABLE 402.4(8) PLEASE |
| | SEE ATTACHED TABLE FOR REFERENCE FOR |
| | RESUBMITTAL |
| | 4. PER THE FLORIDA ADMINISTRATIVE CODE |
| | THE ENGINEER OF RECORD SHALL: |
| | (FAC-61G15-23.002) IF PRACTICING THROUGH |
| | A DULY AUTHORIZED ENGINEERING BUSINESS, |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME LICENSE NUMBER, AS WELL AS, THE |
| | NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGNEERING |
| | BUSINESS ON EACH SHEET. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |