Plan Review Details - Permit 06070002
Plan Review Stops For Permit 06070002
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-02 Cont ID  
Sent By jwitmer Date 2007-02-02 Time 07:18 Rev Time 0.77
Received By jwitmer Date 2007-02-02 Time 07:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-07 Cont ID  
Sent By jwitmer Date 2006-12-07 Time 14:41 Rev Time 2.22
Received By jwitmer Date 2006-12-07 Time 14:41 Sent To  
Notes
2006-12-07 14:49:25BUILDING PLAN REVIEW
 PERMIT: 06070002
 ADD: 1601 FORUM PLACE
 CONT: PASS INTERNATIONAL
 TEL: (954)496-3133
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMMENTS 3 & 4 REFER BACK TO THEA-1
 SHEET DEALING WITH THE CEILING DETAIL. THE
 PLANS NOW INDICATE THE USE OF EFIS SYSTEM
 WITH 5/8" DENSEGLASS GOLD.
  
  
 2A)THE REPORT SUBMITTTED ICC ES LEGACY REPORT 9838B
 HOLCIM ONE COAT STUCCO REPORT,
 THIS REPORT HAS THREE SUBSYSTEMS :
 SYSTEM NO. 1 USES 1/2 GYPSUM SHEATHING AND IS GOOD FOR
 40 PSF
  
 SYSTEM NO. 2 USES 1/2" PLYWOODA COMBUSTIBLE, NOT
 ALLOWED IN HIGH RISE USE.
  
 SYSTEM NO. 3 USESS 1/2" OSB SHEATHING AS A BACKER
 BOARD, A COMBUSTIBLE ALSO NOT ALLOWES IN HIGH RISE
 USE.
  
 PROVIDE 2 SETS OF STO EFIS PRODUCT APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2B)THE SUBMITTED PRODUCT APPROVALS NOT REVIEWED BY
 THE DESIGNER OF RECORD.
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THIS IS A HIGH-RISE BUILDING PLEASE PROVIDE
 THE POSITIVE AND NEGATIVE PRESSURES THAT WILL BE
 ENCOUNTERED FOR BOTH THE INTERIOR ZONES AND END ZONES .
 THE DEIGNER OF RECORD SHALL REVIEW THE PRODUCTS TO SEE
 IF THEY WILL MEET THE PRESSURES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-07 Cont ID  
Sent By jwitmer Date 2006-11-07 Time 16:24 Rev Time 1.22
Received By jwitmer Date 2006-11-07 Time 16:16 Sent To PC
Notes
2006-11-07 16:30:11BUILDING PLAN REVIEW
 PERMIT: 06070002
 ADD: 1601 FORUM PLACE
 CONT: PASS INTERNATIONAL
 TEL: (954)496-3133
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMMENTS 3 & 4 REFER BACK TO THEA-1
 SHEET DEALING WITH THE CEILING DETAIL. THE
 PLANS NOW INDICATE THE USE OF EFIS SYSTEM
 WITH 5/8" DENSEGLASS GOLD.
  
 2A) PROVIDE 2 SETS OF STO EFIS PRODUCT APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2B))W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THIS IS A HIGH-RISE BUILDING PLEASE PROVIDE
 THE POSITIVE AND NEGATIVE PRESSURES THAT WILL BE
 ENCOUNTERED. THE DEIGNER OF RECORD SHALL REVIEW THE
 PRODUCTS TO SEE IF THEY WILL MEET THE PRESSURES.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By jwitmer Date 2006-08-08 Time 16:35 Rev Time 2.22
Received By jwitmer Date 2006-08-08 Time 16:35 Sent To  
Notes
2006-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070002
 ADD: 1601 FORUM PLACE
 CONT: PASS INTERNATIONAL
 TEL: (954)496-3133
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) PLANS INDICATE THE USE OF FIRE
 RETARDANT TREATED PLYWOOD AS BACKING FOR
 THE EXPANDED METAL WIRE LATH. TABLE 601
 FOOTNOTE (C-2).
 2. IN TYPE I AND II CONSTRUCTION,
 FIRE-RETARDANT-TREATED WOOD SHALL BE
 ALLOWED IN BUILDINGS INCLUDING GIRDERS
 AND TRUSSES AS PART OF THE ROOF
 CONSTRUCTION WHEN THE BUILDING IS:
 I. TWO STORIES OR LESS IN HEIGHT;
 II. TYPE II CONSTRUCTION OVER TWO
 STORIES; OR
 III. TYPE I CONSTRUCTION OVER TWO
 STORIES AND THE VERTICAL DISTANCE FROM
 THE UPPER FLOOR TO THE ROOF IS 20 FEET
 OR MORE.
 THE ABOVE FOOTNOTE IS THE ONLY AREAS
 THAT PLYWOOD COULD BE USED IN ROOF
 CONSTRUCTION.
  
 4) THE OTHER ISSUE WITH PLYWOOD IS
 CONSIDERED SOLID BACKING AND FOR WIRE
 LATH SPACED 1/4" OFF THE FACE OF THE
 PLYWOOD TO ALLOW THE STUCCO TO KEY. SEE
 ASTM C-1063.WE WILL NEED TO KNOW THE
 WWEIGHT OF THE WIRE LATH TO BE USED,
 WHAT TYPE OF FRAMING WIL BEUSED TO
 SUPPORT THE WIRE LATH.
  
 5) DISCREPANCY THE PERMIT APPLICATION
 INDICATES ONLY 614 SQ FT OF BREEZEWAY IS
 TO BE REPAIRED. WHEREAS THE PLANS IN THE
 KEY PLAN 2,432 OF NEW CEILING AND 3,475
 OF NEW GROUND SURFACE ? PLEASE UPDATE
 THE PERMIT APPLICATION AND VALUE OF
 PROJECT OR THE CITY WILL USE MARSHAL &
 SWIFT TO CALCULATE THE VALUE OF THE
 PROJECT.
  
 6) WILL THERE BE NEW ROOF DECKS
 REQUIRING ROOFING PERMITS?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 09:44 Sent To  
Notes
2006-10-15 09:45:32CHANGES AND NEW SHEETS IN SETS DO NOT CHANGE THE
 ELECTRICAL SHEETS PREVIOUSLY STAMPED.
  
 OK.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 12:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-29 Cont ID  
Sent By mawillia Date 2006-12-29 Time 14:47 Rev Time 0.00
Received By mawillia Date 2006-12-29 Time 14:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By mwennerg Date 2006-11-02 Time 14:32 Rev Time 0.00
Received By mwennerg Date 2006-11-02 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-18 Cont ID  
Sent By mwennerg Date 2006-08-18 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2006-08-18 Time 13:36 Sent To  
Notes
2006-08-18 00:00:00***APPROVED***
  
 1)SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL WHERE APPLICABLE.
  
 2) PLEASE CORRULATE THE SCOPE OF WORK AS
 IT APPLIES TO SQUARE FOOTAGE OF WORK.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 14:58 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 14:58 Sent To  
Notes
2007-01-13 12:59:07TO "COMM" BD#27
2007-01-04 14:58:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 14:17 Sent To  
Notes
2006-12-05 13:31:48TO "COMM" BD#2
2006-11-21 14:18:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 16:16 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 16:16 Sent To  
Notes
2006-10-12 14:01:20TO "COMM" BD#32
2006-09-26 00:00:00WAITING FOR "COMM" BD-NEW SHEETS FOR "Z"
 AND "F"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 10:48 Rev Time 0.00
Received By tgordon Date 2006-07-06 Time 11:08 Sent To  
Notes
2006-07-19 00:00:00TO "COMM" BD#8
2006-07-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 09:50 Rev Time 0.25
Received By tgordon Date 2006-08-25 Time 09:50 Sent To  
Notes
2006-08-25 00:00:00*** PROVISO ***
 1) AS PER 2004 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-01-30 Cont ID  
Sent By jroach Date 2007-01-30 Time 08:30 Rev Time 0.00
Received By jroach Date 2007-01-30 Time 08:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-12-20 Cont ID  
Sent By jroach Date 2006-12-20 Time 18:07 Rev Time 0.00
Received By jroach Date 2006-12-20 Time 18:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By jroach Date 2006-10-23 Time 08:40 Rev Time 0.00
Received By jroach Date 2006-10-23 Time 08:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-04 Cont ID  
Sent By jroach Date 2006-08-04 Time 11:19 Rev Time 0.00
Received By jroach Date 2006-08-04 Time 11:19 Sent To  
Notes
***NONE***