Plan Review Details - Permit 06061761
Plan Review Stops For Permit 06061761
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-09-08 Cont ID  
Sent By spalmer Date 2006-09-08 Time 15:25 Rev Time 0.15
Received By spalmer Date 2006-09-08 Time 15:25 Sent To  
Notes
2006-09-08 00:00:00OKAY PER LILI URSU

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-25 Cont ID  
Sent By mjacobs Date 2006-10-25 Time 11:42 Rev Time 0.00
Received By mjacobs Date 2006-10-25 Time 11:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 14:21 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 11:25 Sent To  
Notes
2006-10-02 00:00:00 
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 NOTE: THESE ARE THE SAME COMMENTS FROM
 THE REVIEW DATED 9/6/06 WHICH WERE NOT
 ADDRESSED. PLEASE SEE INFORMATION IN
 PACKAGE REGUARDING THEBUSINESS
 CERTIFICATE AUTHORIZATION NUMBER. READ
 THE COMMENTS BELOW FOR MORE INFORMATION
 REGUARDING THE TITLE BLOCK AND "CA"
 NUMBERS.
  
 1) OK.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 61G15-23.002
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZE
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS , THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. SEE 61G1-16.004/471.025/481.219
  
 4) OK.
  
 5) 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-06 Cont ID  
Sent By mjacobs Date 2006-09-06 Time 16:09 Rev Time 0.00
Received By mjacobs Date 2006-09-06 Time 10:58 Sent To  
Notes
2006-09-06 00:00:00 
  
 1) OK.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 61G15-23.002
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZE
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS , THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. SEE 61G1-16.004/471.025/481.219
  
 4) OK.
  
 5) 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By mjacobs Date 2006-07-20 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2006-07-20 Time 06:17 Sent To  
Notes
2006-07-20 00:00:00 
  
 1) 106.1.1 INFORMATION ON DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5). INDICATE THE SUITE# ON EACH
 PAGE FOR RECORD AND INSPECTION PURPOSES
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 61G15-23.002
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZE
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER, AS WELL AS , THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON EACH
 SHEET. SEE 61G1-16.004/471.025/481.219
  
 4) IF THE EXTERIOR STOREFRONT AND DOORS
 ARE NEW, SUBMIT THE PRODUCTR APPROVALS
 FOR THESE ITEMS. IF THE STOREFRONT AND
 DOORS ARE NOT IMPACT RESISTANT,PROOVIDE
 PRODUCT APPROVALS FOR STORM PROTECTION.
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 13:10 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-04-27 Cont ID  
Sent By dpalmer Date 2007-04-27 Time 08:10 Rev Time 0.00
Received By dpalmer Date 2007-04-26 Time 16:52 Sent To PC
Notes
2007-04-27 08:11:09** UNSAT **
  
  
 PLANS REQUIRE CITY PLACE STAMP.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 13:40 Sent To PC
Notes
2007-02-25 13:55:16*** UNSAT ***
  
 1) NOTE: PLEASE SEE LETTERS FROM DESIGN TEAM SHALL BEAR
 THE TITLE BLOCKS AS REQUIRED UNDER FAC 61G15-23.002 AND
 FS 471.023.
 ALL INFORMATION ON SAID TITLE BLOCKS IS REQUIRED.
 PLEASE ALSO SEE FS 471.025 WHICH REQUIRES THE DESIGNER
 OF RECORD TO DATE WHEN THEY ARE SIGNED AND SEAL.
  
 2) NOTE: PLEASE SEE THE CORRECT SITE, LOCATION, ADDRESS
 AND PERMIT NUMBER SHALL BE REFLECTED ON DOCUMENTS.
 PLEASE SEE LETTER SHOW A PERMIT NUMBER WHICH IS NOT
 PART OF OUR RECORD, SHOWS LOCATION NOT IN THIS
 JURISDICTION.
  
 3) NOTE: PLEASE SEE PLANS WHICH WERE REDLINED ON
 ISSUANCE WITH NOTES IN COMPUTER FOR REDLINES TO BE
 CORRECTED ALONG WITH ANY OTHER REVISIONS BEFORE *ROUGH
 ELECTRICAL INSPECTION* AND NOW IT HAS BECOME TIME FOR
 FINAL AND NO CORRECTIONS OR ADJUSTMENTS FOR REDLINED
 PLANS WAS EVER SUBMITTED FOR REVIEW AND STAMPING.
 PLEASE HAVE THE NOTES ON PLANS REVISED WITH THAT IF THE
 REVISED INFORMATION AS STATED ON LETTERS SUBMITTED.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 12:35 Sent To PC
Notes
2006-10-28 13:16:38**** REDLINED PLANS.
  
  
  
 1) MISSING LIGHTING CONTROL(S) FOR SEPARATE SPACE(S).
 (BATH). AUTO SHUT-OFF REQUIRED EITHER TIMER OR OCC
 SENSOR TYPE DEVICE.
 TIMER TYPE 4HRS MAX, OCC TYPE 30MINS MAX.
 13-415.1.ABC.1.1, .1.2
  
 ** THE ABOVE SHOULD BE REVISED ALONG WIHT ANY OTHER
 REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-20 Cont ID  
Sent By dpalmer Date 2006-10-20 Time 21:18 Rev Time 0.00
Received By dpalmer Date 2006-10-20 Time 20:07 Sent To  
Notes
2006-10-20 21:18:45***** UNSAT 4TH REVIEW *******
  
 1) NOTE: PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS
 ARE DONE UNDER THE 2000 IECC??
 PLEASE SEE ALL PREVIOUS NOTES FROM ALL PREVIOUS REVIEWS
 WHICH REQUIRES PERFORMANCE CALCULATIONS TO BE DONE PER
 FBC 2004. PLEASE KNOW, IT IS THE UNDER STANDING OF THIS
 REVIEWER THAT"COMCHECK " WHICH IS BEING USED HAS A
 2004 FBC PERFORMANCE EQUIVALENT OR THERE-ABOUTS WHICH
 SHOULD HAVE EQUAL VALUES ETC.
 PLEASE KNOW, WE CAN NOT ACCEPT UNDER FLORIDA STATUES
 CALCULATIONS, PLANS ETC DONE UNDER CODES WHICH ARE NOT
 ADOPTED UNDER THE FLORIDA BUILDING CODE WHICH IS
 ADOPTED INTO THE FLORIDA STATUES.
 PLEASE SEE ALL ROOMS INCLUDING BATH RMS CONTAINING
 FLOOR TO CEILING HEIGHT PARTITIONS REQUIRE OVER RIDE
 DEVICES AS STATED IN ALL PREVIOUS REVIEWS.
 PLEASE SEE 13-415.1.ABC.1.2
  
 ** PLEASE KNOW, A CALL WAS PLACED TO THE ENGINEER'S
 OFFICE AND A MESSAGE WAS LEF T FOR MR. PATRICAK DAVITT
 AT APPROX 8PMTO CALL THIS OFFICE ASAP.IF THE
 MESSAGE IS OBTAINED BY MR. DAVITT , THIS REVIEWER WILL
 BE IN THE OFFICE BOTH SAT AND SUN ALL DAY FOR
 CONSULTATION.
  
 PLEASE CONTACTTHIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-21 Cont ID  
Sent By dpalmer Date 2006-09-21 Time 20:48 Rev Time 0.00
Received By dpalmer Date 2006-09-21 Time 19:53 Sent To  
Notes
2006-09-21 00:00:00****** UNSAT 3RD REVIEW *******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW AS THEY ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE NEW NOTES BELOW PREVIOUS
 NOTES.
  
  
 1) NOTE: OK.
 PLEASE SURE TO REPLACE ANY SHEETS AS
 NEEDED BASED ON THIS REVIEW OF NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ONCE ALL REVIEWS
 ARE DONE AND BEFORE RSUBMITTING PLANS
 ALL OLD/VOIDED SHEETS SHALL BE
 COMPLETELY REMOVED FROM SETS AND ONLY
 THE NEW REVISED SHEETS SHALL BE INSERTED
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE SET OF THE OLD/VOIDED
 REMOVED SHEETS SHOULD BE SUBMITTED AS
 REFERENCE.
 106.1 ADMIN SECT FBC.
  
 2) NOTE: NO, 3RD REQUEST, PLEASE SEE
 SOME NUMBER OF "F97-000003792" IS NOW
 BEING PLACED ON PLANS FOR THE
 CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED. PLEASE SEE THIS NUMER IS NO
 SUCH NUMBER AS LISTED WITH THE STATE OF
 FLORIDA'S DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE KNOW,
 EVEN ENTERING IN JUST 3792 , COMES UP AS
 A "NULL AND VOID" FOR AN INTERIOR
 DESIGNER. PLEASE SEE A SERCH FOR ANY
 NAME LISTED UNDER "LITTLE" CAME UP WITH
 A COMPANY LOCATED IN NORTH CAROLINA,
 WHICH IS "INC". THESE SHEETS IN WHICH I
 HAVE PRINTED OUT FROM THE STATE ARE
 BEING ATTACHED TO MY COMMENTS.
 PLEASE STILL SEE THE MISSING "PRINTED"
 LICENSE NUMBER FOR THE ARCHITECT ON
 TITLE BLOCKS WHICH GOES ALONG WITH THE
 PINTED NAME WHICH WAS DONE.
 ENGINEERING FIRM WAS CORRECTED.
  
 ** PREVIOUS REVIEW NOTE, REVIEW #2**
  
 NO, PLEASE SEE TITLE BLOCKS FOR
 ARCHITECTURAL FIRM IS STILL MISSING THE
 REQUIRED FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE "CERITIFICATE OF
 AUTHORIZATION NUMBER".
 PLEASE ALSO SEE THE MISSING 'PRINTED
 NAME AND LICENSE NUMBER FOR THE
 ARCHITECT. 61G1-16.004, FS 481.219
  
 ** THIS IS REQUIRED FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR
 ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME AND
 PRINTED LICENSE NUMBER FOR SAID
 ARCHITECT ALSO.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 PLANS AND FOR ALL SHEETS CONTAINING THIS
 TITLE BLOCK WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: OK.
  
 4) NOTE:NO, PLEASE SEE SOME NEC
 ARTICLES IN NOTES ON E-4 ARE STILL BEING
 SHOWN FROM THE 1996 CODE.
 THIS COULD BE REDLINED, HOWEVER PLEASE
 CORRECT OR REMOVE. THIS IS BEING
 REDLINED WHERE ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 OK, HOWEVER PLEASE SEE SOME
 CODE ARTICLE NUMBERS AS SHOWN IN NOTES
 ETC ARE NOT FROM THE CURRENT NEC, 2002.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL THE CURRENT
 CODES ARE REFLECTED AS ADOPTED BY THE
 STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING SHALL BE INDICATED ON PLANS.
 PLEASE ALSO SEE SOME CODES REFLECTED ON
 PLANS ARE FROM THE "1996" NEC.
 PLEASE REF; 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, AND 2004 FBC.
  
 5) NOTE: OK, HOWEVER NOW THE MAIN
 DISCONNECT FROM LANDLOARD GUTTER IS
 BEING SHOWN IN FRONT OF THE METER.
 (LINESIDE). PLEASE SEE THESE NEED
 REVERSING.
  
 ** PREVIOUS REVIEW NOTE, REVIEW #2**
 NO, PLEASE SEE THE RESPONSE FOR
 THE SERVICE IS NOTED, HOWEVER PLEASE
 KNOW THIS IS A NEW TENAT SPACE BEING
 DERIVED FROM THE EXISTING MAIN SERVICE
 TO THE BUILDING. THE INFORMATION FOR THE
 EXISTING METER AND MAIN ETC IS "NOT" ON
 PREVIOUS PLANS AS THIS IS A NEW SPACE
 BEING CREATED.
 PLEASE COMPLETE RISER INCLUDING
 INFORMATION FOR NEW METER WITH "FLOATING
 NEUTRAL", SIZE, AND MAINETC.
 PLEASE KNOW, THE RISER AS SHOWN SHOWS
 SERVICE TO THIS SPACE AS BEING
 UN-METERED FROM THE LAND LORDS MAIN
 PANEL, YET THIS IS NOT HOW SERVICE IS AT
 BUILDING OR HOW NEW SERVICE IS PROVIDED.
 PLEASE SEE MISSING METERING FOR SPACE
 ETC.
 PLEASE SEE OTHER COMMENTS BELOW WITH
 RESPECT TO LOADS AND AIC RATINGS.
 230.70,230.72, 240.4,310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE THE PERMIT FOR
 CREATING THIS TENANT SPACE SHOWS THE HV
 277/480V ELECTRICAL PANEL BEING
 INSTALLED BY THEM.??
 IN EITHER CASE, AFTER COORDINATION ON
 DESIGNERS BEHALF, IF THIS SCOPE OF WORK
 IS GOING TO INCLUDE THE INSTALATION OF
 PANEL INTO TENANT SPACE. PLEASE IDENTIFY
 THE EXISTING LOAD ON THE 1200A MAIN
 SHOWN ALONG WITH NEW LOAD OF THIS
 TENANT.
 PLEASE INCLUDE THE CONDUCTORS FROM
 GUTTER TO METER, METER TO MAIN ETC.
 IF THE PANEL "H" WHICH IS SHOWN ON THESE
 PLANS OR PANEL "A" WHICH IS SHOWN ON THE
 OTHER IS GOING TO BE INSTALLED UNDER
 THIS PERMIT PLEASE REVISE.
 PLEASE INDICATE BY NOTE THAT A
 "FLOATING NEUTRAL" SHALL BE INSTALLED.
 250.6,250.24B,310.16,240.4, 215.5, ETC
  
 6) NOTE: OK.
  
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: NO, COMPLIANCE HAS NOT BEEN
 MET AS OF YET. PLEASE SEE THE
 ENERG/LIGHTING CALCULATIONS ARE NOW
 BEING SUBMITTED FOR REVIEW FOR THE FIRST
 TIME. PLEASE SEE THE ITEMS FOR CONTROLS
 ETC ARE NOT CHECKED ON COMPLIANCE CHECK
 LIST. PLEASE SEE THE NUMBER OF FIXTURES
 ON PLANS EXCEED THAT OF THE NUMBER OF
 FIXTURES IN CALCULATIONS. PLEASE ALSO
 SEE FBC TABLES FOR SPACE BY SPACE
 ALLOWANCES.
 ** CONTROLS AND OVER-RIDES SEEM TO BE
 OK.
  
  
 **PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE A CONTACTOR IS
 BEING SHOWN, HOWEVER COMPLIANCE FOR THE
 2004 FBC CHAPTER 13 STILL NEEDS TO BE
 SHOWN. PLEASE SEE MISSIGN OVER-RIDES
 LOCATED IN AREAS IN EGRESS/INGRESS INTO
 SPACE, LOCATIONS SO THE OCCUPANT CAN SEE
 ALL LIGHTING BEING CONTROLLED/OVER-RIDEN
 ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED
 FOR THE OVER-RIDE DEVICES, ALL OR
 DEVICES SHALL AUTOMATICALLY SHUT OFF AS
 PRE-DETERMINED BY THE CODE. TIMES WERE
 GIVEN ON PREVIOUS REVIEW.
 PLEASE SEE MISSING LIGHTING DENSITIES
 ETC.
 NO CALCULATIONS WERE SUBMITTED FOR NEW
 SPACE.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3,
 13-415.1.AB.1,13-415.2.ABC.1, TABLES FOR
 LPD'S, 415.2.C1, 415.2.B.1 ETC.
 PLEASE KNOW, ALL CODES WERE NOTE GIVEN,
 HOWEVER REFERENCE TO THE 2004 FBC
 CHAPTER 13 WAS GIVEN.
 PLEASE KNOW, THE LC PANELBEING SHOWN
 IS OK, HOWEVER SEE OTHER ITEMS AS NOTED.
 PLEASE KNOW, COULD NOT LOCATE THE TIME
 SCHEDULING.
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SHOW THE TIME SCHEDULING, THE
 LOCATION OF THE REQUIRED OVER RIDES
 DEVICES, AND THE TYPE OF PROPOSED OVER
 RIDE DEVICES.
 PLEASE KNOW, IF A TIMER TYPE, A MAX OF
 4HRS SHALL BE INDICATED. IF AN OCC
 SENSORS, MOTION TYPE DEVICE ETC IS BEING
 SHOWN , A MAX TIME OF 30 MINS SHALL BE
 INDICATED.
  
 14) NOTE: OK.
  
 15) NOTE: OK.
  
 *** NEW NOTES **
  
 1) NOTE: OK.
  
 2) NOTE: OK, AS THE INFORMATIONWAS
 SUBMITTED, HOWEVER NOT CORRECT AS THIS
 TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-01 Cont ID  
Sent By dpalmer Date 2006-09-01 Time 13:47 Rev Time 0.00
Received By dpalmer Date 2006-09-01 Time 12:00 Sent To  
Notes
2006-09-01 00:00:00****** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW AS THEY ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE NEW NOTES BELOW PREVIOUS
 NOTES.
  
  
 1) NOTE: OK, HOWEVER PLEASE SEE PLANS
 ARE NOT ATTACHED INTO SETS. ALL SHEETS
 ARE LOOSE AND NOT FASTENED TOGETHER.
 PLEASE KNOW THIS A STANDING NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ONCE ALL REVIEWS
 ARE DONE AND BEFORE RSUBMITTING PLANS
 ALL OLD/VOIDED SHEETS SHALL BE
 COMPLETELTY REMOVED FROM SETS AND ONLY
 THE NEW REVISED SHEETS SHALL BE INSERTED
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE SET OF THE OLD/VOIDED
 REMOVED SHEETS SHOULD BE SUBMITTED AS
 REFERENCE.
 106.1 ADMIN SECT FBC.
  
 2) NOTE: NO, PLEASE SEE TITLE BLOCKS FOR
 ARCHITECTURAL FIRM IS STILL MISSING THE
 REQUIRED FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE "CERITIFICATE OF
 AUTHORIZATION NUMBER".
 PLEASE ALSO SEE THE MISSING 'PRINTED
 NAME AND LICENSE NUMBER FOR THE
 ARCHITECT. 61G1-16.004, FS 481.219
  
 **PLEASE ALSO SEE UPON VERIFICATION OF
 LICENSING FOR THE ENGINEERING FIRM, THE
 NAME OF COMPANY AS LISTED ON TITLE
 BLOCKS FOR MEP'S AND AS LICENSED WITH
 THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATIONS DOES NOT
 CORRELATE. PLEASE SEE COPY OF PRINT OUT
 FROM DPBR. PLEASE KNOW, THIS WAS
 CONFIRMED WITH THE STATE'S LEGAL COUNSEL
 TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S.
 61G15-23.002, FS 471.023 (ENG'S)
  
 ** THIS IS REQUIRED FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR
 ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME AND
 PRINTED LICENSE NUMBER FOR SAID
 ARCHITECT ALSO.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 PLANS AND FOR ALL SHEETS CONTAINING THIS
 TITLE BLOCK WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: OK.
  
 4) NOTE: OK, HOWEVER PLEASE SEE SOME
 CODE ARTICLE NUMBERS AS SHOWN IN NOTES
 ETC ARE NOT FROM THE CURRENT NEC, 2002.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL THE CURRENT
 CODES ARE REFLECTED AS ADOPTED BY THE
 STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING SHALL BE INDICATED ON PLANS.
 PLEASE ALSO SEE SOME CODES REFLECTED ON
 PLANS ARE FROM THE "1996" NEC.
 PLEASE REF; 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, AND 2004 FBC.
  
 5) NOTE: NO, PLEASE SEE THE RESPONSE FOR
 THE SERVICE IS NOTED, HOWEVER PLEASE
 KNOW THIS IS A NEW TENAT SPACE BEING
 DERIVED FROM THE EXISTING MAIN SERVICE
 TO THE BUILDING. THE INFORMATION FOR THE
 EXISTING METER AND MAIN ETC IS "NOT" ON
 PREVIOUS PLANS AS THIS IS A NEW SPACE
 BEING CREATED.
 PLEASE COMPLETE RISER INCLUDING
 INFORMATION FOR NEW METER WITH "FLATING
 NEUTRAL", SIZE, AND MAINETC.
 PLEASE KNOW, THE RISER AS SHOWN SHOWS
 SERVICE TO THIS SPACE AS BEING
 UN-METERED FROM THE LAND LORDS MAIN
 PANEL, YET THIS IS NOT HOW SERVICE IS AT
 BUILDING OR HOW NEW SERVICE IS PROVIDED.
 PLEASE SEE MISSING METERING FOR SPACE
 ETC.
 PLEASE SEE OTHER COMMENTS BELOW WITH
 RESPECT TO LOADS AND AIC RATINGS.
 230.70,230.72, 240.4,310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE PERMIT FOR
 CREATING THIS TENANT SPACE SHOWS THE HV
 277/480V ELECTRICAL PANEL BEING
 INSTALLED BY THEM.??
 IN EITHER CASE, AFTER COORDINATION ON
 DESIGNERS BEHALF, IF THIS SCOPE OF WORK
 IS GOING TO INCLUDE THE INSTALATION OF
 PANEL INTO TENANT SPACE. PLEASE IDENTIFY
 THE EXISTING LOAD ON THE 1200A MAIN
 SHOWN ALONG WITH NEW LOAD OF THIS
 TENANT.
 PLEASE INCLUDE THE CONDUCTORS FROM
 GUTTER TO METER, METER TO MAIN ETC.
 IF THE PANEL "H" WHICH IS SHOWN ON THESE
 PLANS OR PANEL "A" WHICH IS SHOWN ON THE
 OTHER IS GOING TO BE INSTALLED UNDER
 THIS PERMIT PLEASE REVISE.
 PLEASE INDICATE BY NOTE THAT A
 "FLOATING NEUTRAL" SHALL BE INSTALLED.
 250.6,250.24B,310.16,240.4, 215.5, ETC
  
 6) NOTE: NO, AS NOTED ABOVE. IT WAS KNOW
 TO THIS OFFICE OF THE RATINGS SHOWN FOR
 PANEL "H" AND PANEL "L". THIS COMMENT
 WAS FOR THE NEW MAIN FOR SPACE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE AIC RATING
 FOR NEW MAIN.
 110.9.
  
 7) NOTE: OK.
  
 8) NOTE: NO, PLEASE SEE THIS IS THE SAME
 NOTE, PLEASE SEE SOME INFORMATION ON
 PANELS IS VERY FAINT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULES AND
 RISER AS MANY ITEMS ARE VERY LIGHT IN
 THE PRINT ANDNOT EASILY READABLE.
 PLEASE BE SURE PLANS ARE RE-PRINTED TO
 BE CLEAR AND VISABLE.
 106.1.3 ADMIN SECT
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: NO, PLEASE SEE A CONTACTOR IS
 BEING SHOWN, HOWEVER COMPLIANCE FOR THE
 2004 FBC CHAPTER 13 STILL NEEDS TO BE
 SHOWN. PLEASE SEE MISSIGN OVER-RIDES
 LOCATED IN AREAS IN EGRESS/INGRESS INTO
 SPACE, LOCATIONS SO THE OCCUPANT CAN SEE
 ALL LIGHTING BEING CONTROLLED/OVER-RIDEN
 ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED
 FOR THE OVER-RIDE DEVICES, ALL OR
 DEVICES SHALL AUTOMATICALLY SHUT OFF AS
 PRE-DETERMINED BY THE CODE. TIMES WERE
 GIVEN ON PREVIOUS REVIEW.
 PLEASE SEE MISSING LIGHTING DENSITIES
 ETC.
 NO CALCULATIONS WERE SUBMITTED FOR NEW
 SPACE.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3,
 13-415.1.AB.1,13-415.2.ABC.1, TABLES FOR
 LPD'S, 415.2.C1, 415.2.B.1 ETC.
 PLEASE KNOW, ALL CODES WERE NOTE GIVEN,
 HOWEVER REFERENCE TO THE 2004 FBC
 CHAPTER 13 WAS GIVEN.
 PLEASE KNOW, THE LC PANELBEING SHOWN
 IS OK, HOWEVER SEE OTHER ITEMS AS NOTED.
 PLEASE KNOW, COULD NOT LOCATE THE TIME
 SCHEDULING.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SHOW THE TIME SCHEDULING, THE
 LOCATION OF THE REQUIRED OVER RIDES
 DEVICES, AND THE TYPE OF PROPOSED OVER
 RIDE DEVICES.
 PLEASE KNOW, IF A TIMER TYPE, A MAX OF
 4HRS SHALL BE INDICATED. IF AN OCC
 SENSORS, MOTION TYPE DEVICE ETC IS BEING
 SHOWN , A MAX TIME OF 30 MINS SHALL BE
 INDICATED.
  
 14) NOTE: OK.
  
 15) NOTE: OK.
  
 *** NEW NOTE **
  
 1) NOTE: PLEASE KNOW, ANY "LOCK OFF
 DEVICE" SHALL BE AN INTEGRAL PART OF THE
 CIRCUIT BREAKER. PLEASE KNOW MANY OF THE
 "SNAP/CLIP- ON " TYPES DO NOT MEET CODE
 COMPLIACNE, LISTING OR ARE ACCEPTABLE TO
 THIS AHJ.
 PLEASE PLACE NOTE ON PLANS FOR THE LOCK
 OFF DEVICE BEING PART OF THE BREAKER.
 FBC106.1.2
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-08 Cont ID  
Sent By dpalmer Date 2006-07-08 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2006-07-07 Time 22:19 Sent To  
Notes
2006-07-08 00:00:00****** UNSAT *******
  
 ** IMPORTANT**
 PLEASE SEE NOTE SUNDER PERMIT NUMBER
 06061760 AS THIS IS THE PERMIT FOR
 CREATING SHELL SPACE FOR THIS BULD OUT.
 PLEASE SEE NOTES BELOW FOR COORDINATION
 ISSUES FOR EACH.
  
  
 1) NOTE: PLEASE KNOW, ONCE ALL REVIEWS
 ARE DONE AND BEFORE RSUBMITTING PLANS
 ALL OLD/VOIDED SHEETS SHALL BE
 COMPLETELTY REMOVED FROM SETS AND ONLY
 THE NEW REVISED SHEETS SHALL BE INSERTED
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE SET OF THE OLD/VOIDED
 REMOVED SHEETS SHOULD BE SUBMITTED AS
 REFERENCE.
 106.1 ADMIN SECT FBC.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR
 ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME AND
 PRINTED LICENSE NUMBER FOR SAID
 ARCHITECT ALSO.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 PLANS AND FOR ALL SHEETS CONTAINING THIS
 TITLE BLOCK WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS FOR
 THE BUILD OUT DOES NOT CORRELATE WITH
 SCOPE OF WORK AND ELECTRICAL PLANS BEING
 DONE FOR SHELL. PLEASE SEE PANELS ARE
 SHOWN IN DIFFERENT LOCATIONS, LABELING
 ETC. PLEASE SEE THIS SET OF PLANS OWULD
 PLACE THE NEW PANELS ETC IN THE FUTURE
 BATHRM.
 PLEASE SEE 110.26 ETC
 PLEASE COORDINATE WITH FUTURE TENANT.
  
 4) NOTE: PLEASE SEE THAT ALL THE CURRENT
 CODES ARE REFLECTED AS ADOPTED BY THE
 STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING SHALL BE INDICATED ON PLANS.
 PLEASE ALSO SEE SOME CODES REFLECTED ON
 PLANS ARE FROM THE "1996" NEC.
 PLEASE REF; 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, AND 2004 FBC.
  
 5) NOTE: PLEASE SEE THE PERMIT FOR
 CREATING THIS TENANT SPACE SHOWS THE HV
 277/480V ELECTRICAL PANEL BEING
 INSTALLED BY THEM.??
 IN EITHER CASE, AFTER COORDINATION ON
 DESIGNERS BEHALF, IF THIS SCOPE OF WORK
 IS GOING TO INCLUDE THE INSTALATION OF
 PANEL INTO TENANT SPACE. PLEASE IDENTIFY
 THE EXISTING LOAD ON THE 1200A MAIN
 SHOWN ALONG WITH NEW LOAD OF THIS
 TENANT.
 PLEASE INCLUDE THE CONDUCTORS FROM
 GUTTER TO METER, METER TO MAIN ETC.
 IF THE PANEL "H" WHICH IS SHOWN ON THESE
 PLANS OR PANEL "A" WHICH IS SHOWN ON THE
 OTHER IS GOING TO BE INSTALLED UNDER
 THIS PERMIT PLEASE REVISE.
 PLEASE INDICATE BY NOTE THAT A
 "FLOATING NEUTRAL" SHALL BE INSTALLED.
 250.6,250.24B,310.16,240.4, 215.5, ETC
  
 6) NOTE: PLEASE INDICATE THE AIC RATING
 FOR NEW MAIN.
 110.9.
  
 7) NOTE: PLEASE SEE COLOR CODING FOR THE
 277/480/V SHALL BE BROWN, PURPLE,
 YELLOW.
 FOR ABC PHASES.
  
 8) NOTE: PLEASE SEE PANEL SCHEDULES AND
 RISER AS MANY ITEMS ARE VERY LIGHT IN
 THE PRINT AND EASILY READABLE.
 PLEASE BE SURE PLANS ARE RE-PRINTED TO
 BE CLEAR AND VISABLE.
 106.1.3 ADMIN SECT
  
 9) NOTE: PLEASE VERIFY THE CONTINUOUS
 LOADS AT 125%. A DEMAND IS SHOWN, AND
 APPEARS TO BE THE 125%, HOWEVER IF SO,
 PLEASE INDICATE.
 215.3,230.42 ETC
  
 10) NOTE: PLEASE CLARIFY LOADS ON TRACK
 LTS, IF THE LOADS ARE INDEED SHOWN PER
 220.12.
 PLEASE ADJUST CALCULATIONS IF NEEDED.
  
 11) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL "H" TO
 TRANSFORMER.
 250.110,250.122
  
 12) NOTE: PLEASE CLARIFY WHERE THE NEW
 SIGN CIRCUIT IS LOCATED.?
 600.5
  
 13) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SHOW THE TIME SCHEDULING, THE
 LOCATION OF THE REQUIRED PVER RIDES
 DEVICES, AND THE TYPE OF PROPOSED OVER
 RIDE DEVICES.
 PLEASE KNOW, IF A TIMER TYPE, A MAX OF
 4HRS SHALL BE INDICATED. IF AN OCC
 SENSORS, MOTION TYPE DEVICE ETC IS BEING
 SHOWN , A MAX TIME OF 30 MINS SHALL BE
 INDICATED.
  
 14) NOTE: PLEASE VERIFY TRANSFORMER
 LOCATION, AS IT APPEARS TO BE SHOWN IN
 BATHRM?
 PLEASE ALSO INDICATE THE STRUCTURAL
 DETAIL ON MOUNTING THIS
 UNIT.;(WALL,CEILING ECT).
  
 15) NOTE: PLEASE CORRELATE ADDRESS AND
 SUITE # WHICH IS GOING TO BE FOR THIS
 UNIT, AS TITLE BLOCK INDICATES SUITE #
 128 AND PERMIT APPLICATION INDICATES
 #126?
 PLEASE KNOW, IF 126, THEN ADJUST PLANS.
 106.1.2
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2006-07-07 00:00:00** ELECTRICAL REVIEW IN PROGRESS

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-10-23 Cont ID  
Sent By mwennerg Date 2006-10-23 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2006-10-23 Time 14:08 Sent To  
Notes
2006-10-23 14:09:37PLANS APPROVED ON 9/26/06. RESTAMPED ON 10/23/06.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-09-26 Cont ID  
Sent By mawillia Date 2006-09-26 Time 16:26 Rev Time 0.00
Received By mawillia Date 2006-09-26 Time 16:26 Sent To  
Notes
2006-09-26 00:00:00**ALL PREVIOUS FIRE PLAN REVIEW COMMENTS
 HAVE BEEN ADDRESSED AND/OR CORRECTED**

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-07 Cont ID  
Sent By mawillia Date 2006-09-07 Time 12:36 Rev Time 0.00
Received By mawillia Date 2006-09-07 Time 12:36 Sent To  
Notes
2006-09-07 00:00:00*****RESPONSES/CORRECTIONS TO FIRE PLAN
 REVIEW OF 07/10/2006*****
  
  
  
  
  
 1.) OK
  
 2.) OK
  
 3.) OK. THE BUBBLED ITEMS ON REVISED
 A2.0 WOULD SEEM TO INDICATE THAT TWO
 EMERGENCY LIGHTS HAVE BEEN ADDED;
 HOWEVER BY MAKING A COMPARISON TO THE
 OLD SHEETS ONLY ONE EMERGENCY LIGHT WAS
 ADDED (BUBBLED).
  
 4.) OK
  
 5.) COMMENT STILL NOT ADDRESSED. THE
 BUBBLED ITEMS ON REVISED A2.0 ARE
 EMERGENCY LIGHTS WHICH ARE NOT PART OF
 THE FIRE ALARM SYSTEM. PLEASE INDICATE
 ANY EXISTING OR NEW FIRE ALARM STROBES
 WITHIN THE TENANT SPACE.
  
 6.) OK; HOWEVER IT IS RECOMMENDED THAT
 IN ADDITION TO THE FIRE EXTINGUISHER
 LOCATED IN THE STOREROOM (SEE CS-2), A
 CERTIFIED AND TAGGED 2A10BC FIRE
 EXTINGUISHER BE LOCATED IN THE SALES
 AREA 3' TO 5' ABOVE THE FLOOR IN AN
 OBVIOUS AND ACCESSIBLE LOCATION.
  
 7.) OK
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 11:35 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 11:15 Sent To  
Notes
2006-07-10 00:00:001. CONSTRUCTION, DEMOLTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. ONLY TWO EMERGENCY LIGHTS ARE SHOWN
 ON THE REFLECTED CEILING PLAN. THERE
 DOES NOT APPEAR TO BE ENOUGH EMERGENCY
 LIGHT FIXTURES WITHIN THE SPACE.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER REMODEL REQUIRED.
  
 5. PLEASE INDICATE ANY EXISTING OR NEW
 FIRE ALARM HORN STROBES WITHIN THE
 TENANT SPACE.
  
 6. PLEASE INDICATE LOCATIONS OF PORTABLE
 FIRE EXTINGUISHERS.
  
 7. PLEASE PROVIDE DETAILS ON FLAME
 SPREAD FOR THE HANGING CURTAINS THAT
 SEPARATE THE DRESSING ROOMS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 13:21 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 13:21 Sent To E
Notes
2007-05-08 13:21:31TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 08:52 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 08:52 Sent To  
Notes
2007-04-23 08:54:26TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 16:41 Sent To M
Notes
2007-03-23 16:41:59TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 18:35 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 18:35 Sent To E
Notes
2007-02-22 18:35:33TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 13:23 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 13:23 Sent To E
Notes
2006-10-26 13:23:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-20 Cont ID  
Sent By dpalmer Date 2006-10-20 Time 20:59 Rev Time 0.00
Received By dpalmer Date 2006-10-20 Time 20:58 Sent To  
Notes
2006-10-20 21:00:01TO BOB BOARD #10, EXPEDITED PER NEIL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 14:18 Sent To  
Notes
2006-09-15 00:00:00WAITING FOR "BOB"
 TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 11:52 Sent To  
Notes
2006-08-28 00:00:00TO "BOB"#4
2006-08-16 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-20 Time   Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 11:35 Sent To  
Notes
2006-07-03 00:00:00TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-04-23 Cont ID  
Sent By tgordon Date 2007-04-23 Time 16:18 Rev Time 0.25
Received By tgordon Date 2007-04-23 Time 16:18 Sent To  
Notes
2007-04-23 16:19:40REVISION TO MECH. PLANS PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 13:41 Rev Time 0.20
Received By tgordon Date 2007-03-28 Time 13:41 Sent To  
Notes
2007-03-28 13:46:24RECEIVED SUBMITTAL LETTER, DUE TO DUCT CHANGES
 MECHANICAL PLANS WILL NEED TO BE REVISED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-23 Cont ID  
Sent By tgordon Date 2006-10-23 Time 08:42 Rev Time 0.30
Received By tgordon Date 2006-10-23 Time 08:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-09-28 Cont ID  
Sent By tgordon Date 2006-09-28 Time 09:11 Rev Time 0.20
Received By tgordon Date 2006-09-28 Time 09:11 Sent To  
Notes
2006-09-28 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By tgordon Date 2006-09-05 Time 11:28 Rev Time 0.30
Received By tgordon Date 2006-09-05 Time 11:28 Sent To  
Notes
2006-09-05 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 13:46 Rev Time 0.30
Received By tgordon Date 2006-07-11 Time 13:46 Sent To  
Notes
2006-07-11 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #2 AND
 15, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-24 Cont ID  
Sent By jleech Date 2006-10-24 Time 07:00 Rev Time 0.00
Received By jleech Date 2006-10-24 Time 07:00 Sent To  
Notes
2006-10-24 07:03:59 
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-05 Cont ID  
Sent By jleech Date 2006-10-05 Time 08:00 Rev Time 0.00
Received By jleech Date 2006-10-05 Time 08:00 Sent To  
Notes
2006-10-05 00:00:00DENIED;
 PLUMBING REVIEW OK. MUST COMPLY WITH
 BUILDING PLAN REVIEW NOTES 3 AND 5
 BEFORE PLUMBING PAGES CAN BE APPROVED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-09 Cont ID  
Sent By jleech Date 2006-09-09 Time 07:14 Rev Time 0.00
Received By jleech Date 2006-09-09 Time 07:14 Sent To  
Notes
2006-09-09 00:00:00NOTES;
 SEE BUILDING PLAN REVIEW NOTES 3 & 5.
 1.SHOW DETAIL OF HANDICAP FITTING ROOM
 BENCH AND MIRROR PER. SECTION 11-4.35.4
 AND 11-4.35.5 OF THE FBC-2004 BUILDING
 CODE CHAPTER 11.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By jleech Date 2006-07-13 Time 08:15 Rev Time 0.00
Received By jleech Date 2006-07-13 Time 08:15 Sent To  
Notes
2006-07-13 00:00:00DENIED;
 1.PAGE CS-2 PLUMBING FIXTURE
 REQUIREMENTS REFERS TO FBC-2004 CHAPTER
 29. CHAPTER 29 REFERS YOU TO FBC-2004
 PLUMBING CODE. SEE TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES,
 OCCUPANCY "B" ONE DRINKING FOUNTAIN IS
 REQUIRED. DRINKING FOUNTAIN IS REQUIRED
 TO BE PART OF THE PLUMBING SYSTEM,
 410.1.
 2.TRAP PRIMER REQUIRED FOR FLOOR DRAIN
 PLEASE ADD NOTE TO PLANS.
 3.WASTE AND VENT RISER DIAGRAM; LAVATORY
 VENT WILL VENT THE BATHROOM GROUP. VENTS
 NOT NEEDED ON TOILET AND FLOOR DRAIN.
 SEE PLUMBING CHAPTER 9 VENTING SEC.
 909.1, WET VENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695