| 2006-07-10 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLAN REVIEW : |
| | |
| | 1. PER FBC-2004, CHAPTER 1, SECTION 106, |
| | DRAWINGS SUBMITTED IN PENCIL ARE |
| | UNACCEPTABLE. |
| | 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | 4. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 5. TYPE OF GAS, (LP OR NATURAL) |
| | 6. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | (NOTE: IF SYSTEM IS A 2LB SYSTEM, |
| | MANUFACTURE SHEETS REQUIRED ON THE |
| | REGULATORS) |
| | 8. THERE IS A GAS PERMIT ISSUED FOR THIS |
| | ADDRESS AS OF 6/28/06 FOR FLORIDA PUBLIC |
| | UTILITIES, IF THERE IS A CHANGE OF |
| | CONTRACTORS FOR THIS ADDRESS PLEASE |
| | NOTIFY THE OCCUPATIONAL LICENSE/ PERMIT |
| | SUPERVISOR ADRIANNA MCKENZIE (561) |
| | 805-6681 FOR THE PROPER PROCEDURES. |
| | |
| | END OF COMMENTS: |
| | |