Plan Review Details - Permit 06061694
Plan Review Stops For Permit 06061694
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-03-01 Cont ID  
Sent By amorse Date 2008-03-01 Time 10:43 Rev Time 0.00
Received By amorse Date 2008-03-01 Time 10:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-09-29 Cont ID  
Sent By amorse Date 2007-09-29 Time 09:25 Rev Time 0.00
Received By amorse Date 2007-09-29 Time 09:25 Sent To PC
Notes
2007-09-29 09:26:35 
  
 ROOFING REVISION, CHANGE OF ROOF TILE, PRODUCT APPROVAL
 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-27 Cont ID  
Sent By amorse Date 2007-09-27 Time 16:56 Rev Time 0.00
Received By amorse Date 2007-09-27 Time 16:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-27 Cont ID  
Sent By lmartine Date 2007-03-27 Time 17:12 Rev Time 0.00
Received By lmartine Date 2007-03-27 Time 17:11 Sent To  
Notes
2007-03-27 17:13:01RESTAMP ROOF SUBMITTAL, OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-23 Cont ID  
Sent By rnuquist Date 2007-01-23 Time 14:39 Rev Time 0.00
Received By rnuquist Date 2007-01-23 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-19 Cont ID  
Sent By rnuquist Date 2006-11-19 Time 21:52 Rev Time 0.00
Received By rnuquist Date 2006-11-19 Time 21:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-20 Cont ID  
Sent By amorse Date 2006-09-20 Time 12:18 Rev Time 0.00
Received By amorse Date 2006-09-20 Time 12:18 Sent To PC
Notes
2006-09-20 00:00:00 
  
 ***************PROVISO****************
  
 HANDRAILS SHALL MEET THE REQUIREMENTS OF
 1012.1-1012.3 FBC AND THE LOAD
 REQUIREMENTS PER 1607.7.1 FBC
  
 **************************************
  
  
 NOTE: ORIGINAL APPLICATION MUST BE IN
 THE SUBMITTAL BEFORE A PERMIT CAN BE
 ISSUED
  
 PLEASE BE SURE TO ENCLOSE ALL
 DOCUMENTS (ENERGY CALC'S, PRODUCT
 APPROVALS ETC.)AND THE SHEET WITH THE
 COUNTY IMPACT STAMP WHEN RESUBMITTING
 FOR OTHER FAILED REVIEWS. THESE MUST BE
 PRESENT FOR FINAL STAMPING OF PLANS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By amorse Date 2006-07-28 Time 08:49 Rev Time 0.00
Received By amorse Date 2006-07-28 Time 08:11 Sent To  
Notes
2006-07-28 00:00:00 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 2) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL.(NOT SIGNED BY OWNER/AGENT)
  
 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 4) PROVIDE THE COMPONENT AND CLADDING
 DESIGN PRESSURES PER 1603.1.4 FBC
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 *****NOTE A STACK OF PAPER NOT SEPERATED
 INTO INDIVIDUAL PRODUCT APPROVALS IS NOT
 ACCEPTABLE, REMOVE ALL NON-APPLICABLE
 PRODUCTS AND SUPPLY 2 COPIES OF EACH
 THAT APPLY TO THE PROJECT THAT IS TO BE
 PERMITTED******
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) PLEASE CLARIFY ELEVATIONS, DETAILS BB
 AND CC SHOW FLOOR AND BALCONY JOISTS AT
 SAME ELEV. BUT SECTION 2/5 NOTES A 4"
 STEP DOWN. ALSO SECTIONS ON PAGE 5 HAVE
 FIN. FL. AT APPROX 10'-11 1/2" VERSES
 11'-9" ON ELEVATION DRAWINGS ON PAGE 1.
  
 8) TOTAL RISE OF STAIRS IS 11'-7 1/2"
 FIN. FL. TO FIN. FL. AGAIN DIFFERS FROM
 ELEVATION DRAWING
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-30 Cont ID  
Sent By dpalmer Date 2006-10-30 Time 15:56 Rev Time 0.00
Received By dpalmer Date 2006-10-30 Time 10:50 Sent To P
Notes
2006-10-30 16:02:06*** REDLINED,
  
 RISER FOR MAIN HOUSE PLANS NEEDS TO BE REVISED AS SOON
 AS POSSIBLE IN ORDER NOT TO DELAY INSPECTIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 07:06 Sent To P
Notes
2006-10-06 00:00:00****** UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE THERE ARE SOME NEW ITEMS
 FROM PREVIOUS REVIEW AND NEW COMMENTS
 DUE TO RISER BEING COMPLETELY REVISED
 FOR MAIN HOUSE ETC.
 PLEASE SEE NOTES BELOW ARE TAKEN FROM
 PREVIOUS TWO REVIEWS ALONG WITH ALL NEW
 NOTES ADDED TO BOTTOM OF OLD NOTES.
  
  
 1) NOTE: OK, HOWEVER NOW SUBMITTING
 COMPLETED PLANS, HOWEVER THERE ARE MANY
 ITEMS NOT CODE COMPLIANT, SEE NEW NOTES.
  
 ** PREVIOUS REVIEW #2**
 NO, PLEASE SEE PANEL AT MAIN
 HOUSE MAY NOT BE USED CARRYING BRANCH
 CIRCUITS TO CABANA. PLEASE SEE MISSING
 PANEL, GROUNDING, DISCONNECTING MEANS
 ETC AS PREVIOUSLY NOTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE COMPLETE PLANS FOR
 REVIEW. PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR NEW REQUIRED PANEL, MEANS
 OF DISCONNECT, PANEL SCHEDULE, GROUNDING
 ETC AT THE DETACHED BLDG.
 PLEASE SEE 225.31-225.39, 250.32,250.50,
 215.5, 240.21 ETC
  
 2) NOTE: NO, PLEASE SEE LOAD
 CALCULAITONS SUBMITTED ARE NOT CODE
 COMPLIANT PER NEC AND PLEASE SEE NEW
 COMMENTS BASED ON REVISED PLANS.
  
 ** PREVIOUS REVIEW #2 NOTE **
 NO, PLEASE SEE LOAD
 CALCULATIONS DO NOT MEET CODE PER
 220.31B. PLEASE SEE PANEL SCHEDULE IS
 NOT COMPLETE WITH ALL INFORMATION AS
 REQUIRED. ONLY ONE CIRCUIT BEING SHOWN
 FOR ALL LTS AND GEN PURPOSE RECEPTS,
 MISSING ARC FAULT PROTECTION AS UPSTAIRS
 IS AN ADAPTBALE SLEEPING RM.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE COMPLETE AND CORRELATE
 ALL CIRCUITING ON PLANS WITH PANEL
 SCHEDULE AND COMPLETE LOAD CALCULATIONS.
 PLEASE SEE PLANS SHOW ITEMS WHICH ARE
 NOT FIGURED OR SHOWN ON PANEL
 SCHEDULE/LOAD CALCS.
 PLEASE KNOW, ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN
 STRUCTURE.
 PLEASE SEE MORE THEN ONE SM APPL CIRCUIT
 IS INDICATE HOWEVER ONLY TWO ARE
 FIGURED.
 PLEASE SEE NO TANKLESS WH IS SHOWN ON
 PANEL SCHEDULE OR FIGURED IN LOAD
 CALCULATIONS.
 PLEASE SEE ONLY ONE A/C SYSTEM IS
 FIGURED IN LOADS.
 PLEASE SEE NO LOADS FROM EXISTING
 DWELLING IS SHOWN OR FIGURED IN WITH NEW
 LOADS.
 PLEASE LABEL ALL RMS/AREAS ON PLANS.
 240.4,310.16,220.31B,408.4
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 3) NOTE: OK.
  
 4) NOTE: NO, SOME INFORMATION SUBMITTED
 HOWEVER SEE NEW NOTES FOR DISCONNECTING
 MEANS ETC DUE TO SPECS BEING SUBMITTED.
 PLEASE SEE 210.63,210.70
  
 ** PREVIOUS REVIEW #2 NOTE **
 NO, NO CORRECTIONS MADE, AND
 ITEMS NOT SHOWN AS REQUIRED PER CODE.
 A NOTE WAS ADDED TO SEE LOCATIONS OF
 CU'S ON SURVEY, HOWEVER THE ELECTRICAL
 PLANS ARE REQUIRED TO CONTAIN THE
 ELECTRICAL INFORMATION AS REQUIRED.
 DISCONNECTS, RECEPTS FOR CU'S ETC,
 MIN CLEARENCES ETC.
 PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS FOR THE TANKLESS WATER HEATER
 UNIT. PLEASE BE SURE THE SHEETS CONTAIN
 THE LISTING FROM A NRTL.
 110.26,210.63,210.8,440.11,240.24,422.31
 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
  
 PLEASE SEE 110.26, 240.24,
 440.11, 422.31 ETCFOR MIN DISCONNECTS
 REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE
 AREAS FOR MIN CLEARENCES, AND STORAGE
 AREAS WHERE EASILY IGNITIBLE MATERIALS
 AND OCP.
  
 5) NOTE: OK, HOWEVER SEE NEW NOTES.
  
  
 ** NEW NOTES 2ND REVIEW **
  
 6) NOTE:NO, PLEASE SEE DUE TO REPEAT
 COMMENTS A FEE HAS BEEN ASSESSED TO THE
 DESIGN TEAM AS REQUIRED PER FS
 553.80(2)(B). THE AMOUNT OF $1300.24
 MUST BE PAID BEFORE NEXT RESUB OF PLANS.
 IT IS THE SUGGESTION OF THIS OFFICE AS
 ONE SET OF PLANS ARE BEING RETAINED ,
 THAT A MEETING BE HELD WITH ALL RELEVANT
 PARTIES TO GO OVER PLANS ETC. PLEASE
 KNOW, IF PLANS COME BACK FOR A FORTH
 REVIEW AND "ANY" OF THE SAME COMMENTS
 ARE NOT ADDRESSED, THE FEE IS ASSESSED
 ONCE MORE. PLANS MAY NOW ALL BE TURNED
 INTO THE STATE BOARD OF ARCHIECTS FOR
 REVIEW.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS FOR DESIGN PROFESSIONAL.
 PLEASEKNOW, ONE COPY OF EACH SET OF
 ELECTRICAL IS BEING RETAINED. PLEASE
 KNOW, IT MAY BE REQUIRED BY THIS OFFICE
 THAT PLANS BE DONE BY AN ARCHITECT,
 ENGINEER OR PERSON LICENSED UNDER FS
 489.
  
 7) NOTE: OK.
  
 ***********************************
 THIS FYI WAS PLACED ON PREVIOUS REVIEW.
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 FUTURE COMMENTS AS PLANS WILL CHANGE.
  
 ************************************
  
  
  
 *** NEW NOTES FOR 3RD REVIEW DUE TO NEW
 PLANS BEING SUBMITTED.
  
 1) NOTE: PLEASE SEE RISER, PLEASE
 CORRELATE AS THIS RISER IS COMPLETELY
 DIFFERENT FROM THEMAIN HOUSE PLANS AND
 NOW DOES NOT MEET MANY ITEMS CODE
 RELATED..
  
 A) PLEASE SEE RISER NOW SHOWS A NEW 150A
 PANEL "B", WHICH IS BEING FED FROM
 3-#3'S WHICH ARE ONLY RATED AT 100A'S.
 PLEASE PREVIOUS REVISED RISER SHOWS A
 125A PANEL "B" WITH A 100A MCB AND NOW
 SERVICE IS BEING INCREASED AND NO
 CONSIDERATION HAS BEEN TAKEN TO THE
 INCREASE FOR SERVICE ENTRANCE CONDUCTORS
 FOR NEW 150A MCB PANEL AND INCREASED
 SERVICE.
  
 B) PLEASE SEE 250.66, 310.15B6, 310.16,
 AS THE SEC'S TOTAL WILL NOW BE INCREASED
 ,T HE GROUNDING ELECTRODE CONDUCTOR WILL
 NOW BE REQUIRED TO MEET 250.66. THE
 PREVIOUS #2, IS NO LONGER LARGE ENOUGH.
  
 C) PLEASE SEE RISER SHOWS 3-3/0'S AND
 1-#6 IN AN 1 1/4" CONDUIT FROM PANEL "B"
 TO NEW PANEL "C" (CABANAN PANEL).
 PLEASE SEE THE FIRST ITEM IS THAT PANEL
 "B" SHOWS A 2-POLE 70A BRKR FEEDING NEW
 PANEL "C", 3/0'S WILL NOT FIT INTO A 70A
 BREAKER.
 PLEASE SEE THE SECOND ITEM IS THAT PANEL
 "B" SHOWS #4'S WHICH IS COMPLETELY
 DIFFERENT FROM RISER WHICH SHOWS 3/0'S?
 THE THIRD ISSUE IS THAT 3-3/0'S AND 1-#6
 WILL NOT FIT INTO 1 1/4" CONDUIT AS
 SHOWN ON RISER. PLEASE SEE TABLES IN
 CHAPTER 9.
 PLEASE SEE , 240.4,310.15B6,310.16,
 CHAPTE 9, 215.2, ETC ETC
  
 2) NOTE; PLEASE SEE NOW THE SPECS FOR
 THE NEW TANKLESS WATER HEATER IS BEING
 SUBMITTED FOR THE FIRST TIME. PLEASE SEE
 THE UNIT SUBMITTED ITSELF AT 17.25KW
 EXCEEDS THE PROPOSED 70A FEED TO THE
 PANEL "C". PLEASE SEE THE LOADS ON PANEL
 "C" ARE NOT CORRECT AS THEY DO NOT ADD
 UP.
 THE TKLESS WH IS OVER 70A'S ALONE !!!
 PLEASE SEE THE * ON SPEC SHEETS WHICH
 EVEN STATES A MIN SERVICE FOR THIS SIZE
 UNIT FOR A DWELLING. THE MIN OCP FOR THE
 UNIT IS 80A'S, WHICH IS STATED ON SPECS.
 PLEASE KNOW, IF THE PANEL IS FEEDING
 THIS UNIT IS OUTSIDE,WITH TWO-2-POLE
 40'S, THEN PLANS WOULD SHOW MORE THAN
 ONE DISCONNECT INSIDE FEEDING THIS UNIT.
 422.11, 110.26, 422.31, 422.30 ETC.
 110.3,90.7.
  
 3) NOTE: PLEASE SEE 210.52 AS RAILING IS
 CONSIDERED WALL SPACE AND WALL SPACE ON
 2ND FLR IS MISSING ONE RECEPT. IF THIS
 WAS THE ONLY ITEM IT WOULD BE REDLINED.
  
  
 4) NOTE: PLEASE KNOW, IF THIS RISER HAS
 INDEED CHANGED THIS MUCH AS SHOWN FOR
 THE MAIN HOUSE SERVICE FROM THE LAST
 REVISION WHICH WAS SUBMITTED, PLEASE
 SUBMIT REVISED PLANS FOR MAIN HOUSE, AS
 THE WILL GREATLY AFFECT THE ELECTRICAL
 INSPECTIONS FOR MAIN HOUSE.
  
  
 3) NOTE: PLEASE SEE PANEL"C"/ CABANA
 PANEL ON RISER IS BEING SHOWN AS A 100A
 MCB PANEL, YET THE PLANS ALSO SHOW A
 DISCONNECT OUTSIDE WHICH IS NOT ON
 RISER??
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 07:42 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 07:07 Sent To M
Notes
2006-09-08 00:00:00****** UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE MOST ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED AND
 PLANSARE NOT CODE COMPLIANT. PLEASE
 SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW NOTES ALONG WITH NEW
 NOTES ADDED.
  
  
 1) NOTE: NO, PLEASE SEE PANEL AT MAIN
 HOUSE MAY NOT BE USED CARRYING BRANCH
 CIRCUITS TO CABANA. PLEASE SEE MISSING
 PANEL, GROUNDING, DISCONNECTING MEANS
 ETC AS PREVIOUSLY NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PLANS FOR
 REVIEW. PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR NEW REQUIRED PANEL, MEANS
 OF DISCONNECT, PANEL SCHEDULE, GROUNDING
 ETC AT THE DETACHED BLDG.
 PLEASE SEE 225.31-225.39, 250.32,250.50,
 215.5, 240.21 ETC
  
 2) NOTE:NO, PLEASE SEE LOAD
 CALCULATIONS DO NOT MEET CODE PER
 220.31B. PLEASE SEE PANEL SCHEDULE IS
 NOT COMPLETE WITH ALL INFORMATION AS
 REQUIRED. ONLY ONE CIRCUIT BEING SHOWN
 FOR ALL LTS AND GEN PURPOSE RECEPTS,
 MISSING ARC FAULT PROTECTION AS UPSTAIRS
 IS AN ADAPTBALE SLEEPING RM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE AND CORRELATE
 ALL CIRCUITING ON PLANS WITH PANEL
 SCHEDULE AND COMPLETE LOAD CALCULATIONS.
 PLEASE SEE PLANS SHOW ITEMS WHICH ARE
 NOT FIGURED OR SHOWN ON PANEL
 SCHEDULE/LOAD CALCS.
 PLEASE KNOW, ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN
 STRUCTURE.
 PLEASE SEE MORE THEN ONE SM APPL CIRCUIT
 IS INDICATE HOWEVER ONLY TWO ARE
 FIGURED.
 PLEASE SEE NO TANKLESS WH IS SHOWN ON
 PANEL SCHEDULE OR FIGURED IN LOAD
 CALCULATIONS.
 PLEASE SEE ONLY ONE A/C SYSTEM IS
 FIGURED IN LOADS.
 PLEASE SEE NO LOADS FROM EXISTING
 DWELLING IS SHOWN OR FIGURED IN WITH NEW
 LOADS.
 PLEASE LABEL ALL RMS/AREAS ON PLANS.
 240.4,310.16,220.31B,408.4
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 3) NOTE: OK.
  
 4) NOTE: NO, NO CORRECTIONS MADE, AND
 ITEMS NOT SHOWN AS REQUIRED PER CODE.
 A NOTE WAS ADDED TO SEE LOCATIONS OF
 CU'S ON SURVEY, HOWEVER THE ELECTRICAL
 PLANS ARE REQUIRED TO CONTAIN THE
 ELECTRICAL INFORMATION AS REQUIRED.
 DISCONNECTS, RECEPTS FOR CU'S ETC,
 MIN CLEARENCES ETC.
 PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS FOR THE TANKLESS WATER HEATER
 UNIT. PLEASE BE SURE THE SHEETS CONTAIN
 THE LISTING FROM A NRTL.
 110.26,210.63,210.8,440.11,240.24,422.31
 ETC.
  
 ** PREVIOUS REVIEW NOTE**
  
 PLEASE SEE 110.26, 240.24,
 440.11, 422.31 ETCFOR MIN DISCONNECTS
 REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE
 AREAS FOR MIN CLEARENCES, AND STORAGE
 AREAS WHERE EASILY IGNITIBLE MATERIALS
 AND OCP.
  
 5) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTES **
 PLEASE SEE PLANS DO NOT CONTAIN
 ANY PRINTED NAME AND SIGNATURE OF THE
 PERSON TAKING RESPONSIBILITY FOR PLANS
 AND DESIGN.
 **WHEN PLANS ARE REQUIRED TO BE DONE BY
 AN ARCHITECT OR ENGINEER PLEASE SEE FS
 481/471
 FBC 106.1.2 ADMIN SECT.
  
 ** NEW NOTES **
  
 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT CODE COMPLIANT
 COMMENTS FOR DESIGN PROFESSIONAL.
 PLEASEKNOW, ONE COPY OF EACH SET OF
 ELECTRICAL IS BEING RETAINED. PLEASE
 KNOW, IT MAY BE REQUIRED BY THIS OFFICE
 THAT PLANS BE DONE BY AN ARCHITECT,
 ENGINEER OR PERSON LICENSED UNDER FS
 489.
  
 7) NOTE: PLEASE SEE SURVEY IS REQUIRED
 TO CONTAIN AN ORIGINAL SIGNATURE PER FS
 472.025. PLEASE SEE FAC 61G17.
 STATEMENT ON SURVEY MENTIONS "NOT VALID
 WITHOUT SIGNATURE AND RAISED SEAL". A
 RIASED SEAL OVER A PHOTO-COPIED
 SIGNATURE DOES NOT MAKE THIS VALID.
 THIS COMMENT IS NOT FOR "ON TARGET"
 DESIGNS.
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 FUTURE COMMENTS AS PLANS WILL CHANGE.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOUDL BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By dpalmer Date 2006-07-19 Time 07:29 Rev Time 0.00
Received By dpalmer Date 2006-07-19 Time 07:04 Sent To M
Notes
2006-07-19 00:00:00****** UNSAT ******
  
 1) NOTE: PLEASE COMPLETE PLANS FOR
 REVIEW. PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR NEW REQUIRED PANEL, MEANS
 OF DISCONNECT, PANEL SCHEDULE, GROUNDING
 ETC AT THE DETACHED BLDG.
 PLEASE SEE 225.31-225.39, 250.32,250.50,
 215.5, 240.21 ETC
  
 2) NOTE: PLEASE COMPLETE AND CORRELATE
 ALL CIRCUITING ON PLANS WITH PANEL
 SCHEDULE AND COMPLETE LOAD CALCULATIONS.
 PLEASE SEE PLANS SHOW ITEMS WHICH ARE
 NOT FIGURED OR SHOWN ON PANEL
 SCHEDULE/LOAD CALCS.
 PLEASE KNOW, ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN
 STRUCTURE.
 PLEASE SEE MORE THEN ONE SM APPL CIRCUIT
 IS INDICATE HOWEVER ONLY TWO ARE
 FIGURED.
 PLEASE SEE NO TANKLESS WH IS SHOWN ON
 PANEL SCHEDULE OR FIGAURED IN LOAD
 CALCULATIONS.
 PLEASE SEE ONLY ONE A/C SYSTEM IS
 FIGURED IN LOADS.
 PLEASE SEE NO LOADS FROM EXISTING
 DWELLING IS SHOWN OR FIGURED IN WITH NEW
 LOADS.
 PLEASE LABEL ALL RMS/AREAS ON PLANS.
 240.4,310.16,220.31B,408.4
 FBC 106.1.2, 106.1.3 ADMIN SECT.
  
 3) NOTE: PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUITS.
 210.52D, 210.11C3
  
 4) NOTE: PLEASE SEE 110.26, 240.24,
 440.11, 422.31 ETCFOR MIN DISCONNECTS
 REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE
 AREAS FOR MIN CLEARENCES, AND STORAGE
 AREAS WHERE EASILY IGNITIBLE MATERIALS
 AND OCP.
  
 5) NOTE: PLEASE SEE PLANS DO NOT CONTAIN
 ANY PRINTED NAME AND SIGNATURE OF THE
 PERSON TAKING RESPONSIBILITY FOR PLANS
 AND DESIGN.
 **WHEN PLANS ARE REQUIRED TO BE DONE BY
 AN ARCHITECT OR ENGINEER PLEASE SEE FS
 481/471
 FBC 106.1.2 ADMIN SECT.
  
 ** PLEASE KNOW, DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 FUTURE COMMENTS AS PLANS WILL CHANGE.
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF THE OLD/VOIDED REMOVED
 SHEETS SHOUDL BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-02-27 Cont ID  
Sent By adarroug Date 2008-02-27 Time 12:25 Rev Time 0.00
Received By adarroug Date 2008-02-27 Time 12:25 Sent To B
Notes
2008-02-27 12:25:27TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 10:44 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 10:44 Sent To B
Notes
2007-09-28 10:44:34TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 09:20 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 09:20 Sent To B
Notes
2007-09-24 09:21:19TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 10:31 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 10:31 Sent To M
Notes
2007-06-21 10:31:35TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 09:42 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 09:41 Sent To B
Notes
2007-03-23 09:42:20TO "LMARTINEZ" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 11:54 Sent To B
Notes
2006-12-22 11:55:01TO "LMARTINEZ" DESK/SUBMITTAL--TRUSS DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 15:21 Sent To B
Notes
2006-11-12 15:21:50TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 09:13 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 09:13 Sent To Z
Notes
2006-11-07 09:13:49TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 10:14 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 10:14 Sent To E
Notes
2006-10-30 10:14:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-03 Cont ID  
Sent By adarroug Date 2006-10-03 Time 17:44 Rev Time 0.00
Received By adarroug Date 2006-10-03 Time 17:44 Sent To E
Notes
2006-10-03 00:00:00TO "DPALMER"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 10:41 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 10:41 Sent To Z
Notes
2006-09-29 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 16:30 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 16:24 Sent To  
Notes
2006-08-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 16:27 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 16:27 Sent To Z
Notes
2006-08-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 10:50 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 10:50 Sent To E
Notes
2006-07-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-28 Time   Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 09:18 Sent To  
Notes
2006-07-05 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-29 Cont ID  
Sent By tgordon Date 2007-06-29 Time 10:28 Rev Time 0.20
Received By tgordon Date 2007-06-29 Time 10:28 Sent To  
Notes
2007-06-29 10:29:00*** PROVISO ***
 1) M1601.10 MECHANICAL CLOSETS.
 THE INTERIOR SURFACES OF MECHANICAL
 CLOSETS SHALL BE SHEATHED WITH A
 CONTINUOUS AIR BARRIER AS SPECIFIED IN
 SECTION M1601.10.1 AND SHALL BE SEALED
 WITH APPROVED CLOSURE SYSTEMS AS
 SPECIFIED IN SECTION M1601.10.2 . ALL
 JOINTS SHALL BE SEALED BETWEEN AIR
 BARRIER SEGMENTS AND BETWEEN THE AIR
 BARRIERS OF WALLS AND THOSE OF THE
 CEILING, FLOOR AND DOOR FRAMING. ALL
 PENETRATIONS OF THE AIR BARRIER
 INCLUDING, BUT NOT LIMITED TO, THOSE BY
 AIR DUCTS, PLENUMS, PIPES, SERVICE
 LINES, REFRIGERANT LINES, ELECTRICAL
 WIRING, AND CONDENSATE DRAIN LINES SHALL
 BE SEALED TO THE AIR BARRIER AND
 APPROVED CLOSURE SYSTEMS.
 EXCEPTION : AIR PASSAGEWAYS INTO THE
 CLOSET FROM CONDITIONED SPACE THAT ARE SPECIFICALLY
 DESIGNED FOR RETURN AIR
 FLOW.
 THROUGH-WALL, THROUGH-FLOOR AND
 THROUGH-CEILING AIR PASSAGEWAYS INTO THE
 CLOSET SHALL BE FRAMED AND SEALED TO
 FORM AN AIRTIGHT PASSAGEWAY USING
 APPROVED AIR DUCT MATERIALS AND APPROVED
 CLOSURE SYSTEMS.
 DUCT PENETRATIONS THROUGH ANY PART OF
 THE CEILING, WALLS OR FLOOR OF A
 MECHANICAL CLOSET SHALL HAVE SUFFICIENT
 SPACE BETWEEN SURROUNDING CEILING, WALLS
 OR FLOOR AND ANY DUCT OR PLENUM
 PENETRATION TO ALLOW FOR SEALING OF THE PENETRATION AND
 INSPECTION OF THE SEAL.
 CLOTHES WASHERS, CLOTHES DRYERS,
 COMBUSTION WATER HEATERS AND ATMOSPHERIC COMBUSTION
 FURNACES SHALL NOT BE LOCATED
 IN MECHANICAL CLOSETS USED AS RETURN AIR
 PLENUMS.
  
 M1601.10.1 APPROVED AIR BARRIERS.
 THE FOLLOWING AIR BARRIERS ARE APPROVED
 FOR USE IN MECHANICAL CLOSETS:
 1.ONE-HALF INCH (12.7 MM) THICK OR
 GREATER GYPSUM WALLBOARD, TAPED AND
 SEALED.
 2.OTHER PANELIZED MATERIALS HAVING
 INWARD FACING SURFACES WITH AN AIR
 POROSITY NO GREATER THAN THAT OF A DUCT
 PRODUCT MEETING SECTION 22 OF UL 181
 WHICH ARE SEALED ON ALL INTERIOR
 SURFACES TO CREATE A CONTINUOUS AIR
 BARRIER. PER 2004 FBC/R.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-27 Cont ID  
Sent By tgordon Date 2007-06-27 Time 08:52 Rev Time 0.30
Received By tgordon Date 2007-06-27 Time 08:52 Sent To  
Notes
2007-06-27 09:01:35REVISED MECHANICAL PLANS
 *** DENIED ***
 1) REVISED PLANS SHOW NO RETURN AIR GRILL SO AIR MAY
 RETURN TO AHU.
  
 2) PLANS 2ND. FLOOR SHOW 8" SUPPLY AIR DUCT GOING TO A
 10X10 SUPPLY AIR GRILL THEN TO A MIXING BOX, SHOULDN'T
 IT GO TO THE MIXING BOX THEN THE 10X10 SUPPLY AIR
 GRILL, PLEASE CORRECT IF SO.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 08:28 Rev Time 0.30
Received By tgordon Date 2006-09-11 Time 08:28 Sent To P
Notes
2006-09-11 00:00:00*** PROVISO ***
 1) M1601.10 MECHANICAL CLOSETS.
 THE INTERIOR SURFACES OF MECHANICAL
 CLOSETS SHALL BE SHEATHED WITH A
 CONTINUOUS AIR BARRIER AS SPECIFIED IN
 SECTION M1601.10.1 AND SHALL BE SEALED
 WITH APPROVED CLOSURE SYSTEMS AS
 SPECIFIED IN SECTION M1601.10.2 . ALL
 JOINTS SHALL BE SEALED BETWEEN AIR
 BARRIER SEGMENTS AND BETWEEN THE AIR
 BARRIERS OF WALLS AND THOSE OF THE
 CEILING, FLOOR AND DOOR FRAMING. ALL
 PENETRATIONS OF THE AIR BARRIER
 INCLUDING, BUT NOT LIMITED TO, THOSE BY
 AIR DUCTS, PLENUMS, PIPES, SERVICE
 LINES, REFRIGERANT LINES, ELECTRICAL
 WIRING, AND CONDENSATE DRAIN LINES SHALL
 BE SEALED TO THE AIR BARRIER AND
 APPROVED CLOSURE SYSTEMS.
 EXCEPTION : AIR PASSAGEWAYS INTO THE
 CLOSET FROM CONDITIONED SPACE THAT ARE SPECIFICALLY
 DESIGNED FOR RETURN AIR
 FLOW.
 THROUGH-WALL, THROUGH-FLOOR AND
 THROUGH-CEILING AIR PASSAGEWAYS INTO THE
 CLOSET SHALL BE FRAMED AND SEALED TO
 FORM AN AIRTIGHT PASSAGEWAY USING
 APPROVED AIR DUCT MATERIALS AND APPROVED
 CLOSURE SYSTEMS.
 DUCT PENETRATIONS THROUGH ANY PART OF
 THE CEILING, WALLS OR FLOOR OF A
 MECHANICAL CLOSET SHALL HAVE SUFFICIENT
 SPACE BETWEEN SURROUNDING CEILING, WALLS
 OR FLOOR AND ANY DUCT OR PLENUM
 PENETRATION TO ALLOW FOR SEALING OF THE PENETRATION AND
 INSPECTION OF THE SEAL.
 CLOTHES WASHERS, CLOTHES DRYERS,
 COMBUSTION WATER HEATERS AND ATMOSPHERIC COMBUSTION
 FURNACES SHALL NOT BE LOCATED
 IN MECHANICAL CLOSETS USED AS RETURN AIR
 PLENUMS.
  
 M1601.10.1 APPROVED AIR BARRIERS.
 THE FOLLOWING AIR BARRIERS ARE APPROVED
 FOR USE IN MECHANICAL CLOSETS:
 1.ONE-HALF INCH (12.7 MM) THICK OR
 GREATER GYPSUM WALLBOARD, TAPED AND
 SEALED.
 2.OTHER PANELIZED MATERIALS HAVING
 INWARD FACING SURFACES WITH AN AIR
 POROSITY NO GREATER THAN THAT OF A DUCT
 PRODUCT MEETING SECTION 22 OF UL 181
 WHICH ARE SEALED ON ALL INTERIOR
 SURFACES TO CREATE A CONTINUOUS AIR
 BARRIER. PER 2004 FBC/R.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By tgordon Date 2006-07-19 Time 09:16 Rev Time 1.00
Received By tgordon Date 2006-07-19 Time 09:16 Sent To P
Notes
2006-07-19 00:00:00*** DENIED ***
 1) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 . (SEE TITLE BLOCK).
  
 2) NEED JOB ADDRESS ON MECHANICAL PLANS.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 4) IF ENGINEER'S INFORMATION IS IN TITLE
 BLOCK, THEN HE MUST SEAL PLANS, SEE
 MECHANICAL PLANS ENGINEER'S SIGNATURE
 AND DATE BUT NO SEAL, PLEASE CORRECT.
  
 5) SEE ELECTRICAL PLANS ARE CALLING FOR
 10 KW HEATER, ENERGY CALCULATIONS AND
 MANUAL J CAL'S. ARE CALLING FOR 5KW
 HEAT, PLEASE CORRECT.
  
 6) SHOW ON MECHANICAL PLANS WHERE THE
 CHASE WILL BE FOR THE 10" DUCT TO THE
 SECOND FLOOR.
  
 7) SHOW ON MECHANICAL PLANS AN A/C
 EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION.
  
 8) PLEASE BE ADVISED IF BELOW THE
 STAIRWAY IS TO BE USED AS A MECHANICAL
 CLOSET THEN IT MUST COMPLY WITH M1601.10
  
 9) M1601.10 MECHANICAL CLOSETS.
 THE INTERIOR SURFACES OF MECHANICAL
 CLOSETS SHALL BE SHEATHED WITH A
 CONTINUOUS AIR BARRIER AS SPECIFIED IN
 SECTION M1601.10.1 AND SHALL BE SEALED
 WITH APPROVED CLOSURE SYSTEMS AS
 SPECIFIED IN SECTION M1601.10.2 . ALL
 JOINTS SHALL BE SEALED BETWEEN AIR
 BARRIER SEGMENTS AND BETWEEN THE AIR
 BARRIERS OF WALLS AND THOSE OF THE
 CEILING, FLOOR AND DOOR FRAMING. ALL
 PENETRATIONS OF THE AIR BARRIER
 INCLUDING, BUT NOT LIMITED TO, THOSE BY
 AIR DUCTS, PLENUMS, PIPES, SERVICE
 LINES, REFRIGERANT LINES, ELECTRICAL
 WIRING, AND CONDENSATE DRAIN LINES SHALL
 BE SEALED TO THE AIR BARRIER AND
 APPROVED CLOSURE SYSTEMS.
 EXCEPTION : AIR PASSAGEWAYS INTO THE
 CLOSET FROM CONDITIONED SPACE THAT ARE
 SPECIFICALLY DESIGNED FOR RETURN AIR
 FLOW.
 THROUGH-WALL, THROUGH-FLOOR AND
 THROUGH-CEILING AIR PASSAGEWAYS INTO THE
 CLOSET SHALL BE FRAMED AND SEALED TO
 FORM AN AIRTIGHT PASSAGEWAY USING
 APPROVED AIR DUCT MATERIALS AND APPROVED
 CLOSURE SYSTEMS.
 DUCT PENETRATIONS THROUGH ANY PART OF
 THE CEILING, WALLS OR FLOOR OF A
 MECHANICAL CLOSET SHALL HAVE SUFFICIENT
 SPACE BETWEEN SURROUNDING CEILING, WALLS
 OR FLOOR AND ANY DUCT OR PLENUM
 PENETRATION TO ALLOW FOR SEALING OF THE
 PENETRATION AND INSPECTION OF THE SEAL.
 CLOTHES WASHERS, CLOTHES DRYERS,
 COMBUSTION WATER HEATERS AND ATMOSPHERIC
 COMBUSTION FURNACES SHALL NOT BE LOCATED
 IN MECHANICAL CLOSETS USED AS RETURN AIR
 PLENUMS.
  
 M1601.10.1 APPROVED AIR BARRIERS.
 THE FOLLOWING AIR BARRIERS ARE APPROVED
 FOR USE IN MECHANICAL CLOSETS:
 1.ONE-HALF INCH (12.7 MM) THICK OR
 GREATER GYPSUM WALLBOARD, TAPED AND
 SEALED.
 2.OTHER PANELIZED MATERIALS HAVING
 INWARD FACING SURFACES WITH AN AIR
 POROSITY NO GREATER THAN THAT OF A DUCT
 PRODUCT MEETING SECTION 22 OF UL 181
 WHICH ARE SEALED ON ALL INTERIOR
 SURFACES TO CREATE A CONTINUOUS AIR
 BARRIER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-31 Cont ID  
Sent By jleech Date 2006-10-31 Time 07:51 Rev Time 0.00
Received By jleech Date 2006-10-31 Time 07:51 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-20 Cont ID  
Sent By jleech Date 2006-10-20 Time 14:05 Rev Time 0.00
Received By jleech Date 2006-10-20 Time 14:05 Sent To  
Notes
2006-10-20 14:07:07ONLY ONE SET OF PLUMBING PLANS

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-19 Cont ID  
Sent By jleech Date 2006-09-19 Time 07:37 Rev Time 0.00
Received By jleech Date 2006-09-19 Time 07:37 Sent To B
Notes
2006-09-19 00:00:00DENIED;
 1.PLANS DO NOT CONTAIN ANY PRINTED NAME
 OF PERSON TAKING RESPONSIBITY FOR PLANS
 AND DESIGN.
 2.(SECOND REQUEST) NEED SPEC. SHEETS FOR
 TANKLESS WATER HEATER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-22 Cont ID  
Sent By jleech Date 2006-07-22 Time 13:23 Rev Time 0.00
Received By jleech Date 2006-07-22 Time 13:22 Sent To B
Notes
2006-07-22 00:00:00DENIED;
 1. PLANS TO BE SIGNED BY THE PERSON
 RESPONSIBLE.
 2.SANYARY RISER DIAGRAM; (A)THE TUB IS
 NOT VENTED. (B)SINK ON FIRST FLOOR IS
 NOT SHOWNON RISER DIAGRAM.
 3.SUBMIT SPEC. SHEETS ON TANKLESS WATER
 HEATER.
 4.PLUMBING PLAN REVIEW CANNOT BE
 APPROVED UNTIL ZONING IS PASSED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2006-11-10 Cont ID  
Sent By mmclean Date 2006-11-10 Time 09:26 Rev Time 0.00
Received By mmclean Date 2006-11-10 Time 09:26 Sent To  
Notes
2006-11-11 09:27:09REVISION - POOL CABANA MOVED FROM 71/2 FT TO 5FT ON THE
 SIDE.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-10-02 Cont ID  
Sent By mmclean Date 2006-10-02 Time 18:47 Rev Time 0.00
Received By mmclean Date 2006-10-02 Time 18:47 Sent To I
Notes
2006-10-02 00:00:00NOTE: THE PROPOSED POOL EQUIPMENT SHALL
 NOT BE CLOSER THAN 6FT FROM SIDE
 PROPERTY LINE.
  
 NOTE: THE PROPOSED POOL CABANA CANNOT BE
 USED A SEPARATE LIVING SPACE AND MUST
 NOT HAVE ANY COOKING FACILITY.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-25 Cont ID  
Sent By mmclean Date 2006-08-25 Time 18:50 Rev Time 0.00
Received By mmclean Date 2006-08-25 Time 18:50 Sent To I
Notes
2006-08-25 00:00:00NOTE: THE PROPOSED POOL CABANA CANNOT BE
 USED A SEPARATE LIVING SPACE AND MUST
 NOT HAVE ANY COOKING FACILITY.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By mmclean Date 2006-07-17 Time 13:54 Rev Time 0.00
Received By mmclean Date 2006-07-17 Time 13:54 Sent To I
Notes
2006-07-17 00:00:00DENIED,
 1. THE PROPOSED A/C UNIT (SHOWN ON THE
 FLOOR PLANS) MUST BE SHOWN ON THE TWO
 COPY OF SURVEY.
 2. THE PROPOSED POOL CABANA CANNOT BE
 USED AS A GUEST HOUSE (ZONED S7 - SINGLE
 FAMILY RESIDENCE ONLY). POOL CABANA
 CANNOT BE USED AS A SEPERATE LIVING
 SPACE AND CANNOT HAVE ANOTHER COOKING
 FACILITY.
 3. MUST REMOVE THE "GUEST HOUSE" OFF THE
 SURVEY AND IDENTIFY THE ACCESSORY
 STRUCTURE AS A POOL CABANA AND ANY
 COOKING FACILITY WITHIN THE STRUCTURE
 REMOVED.
  
 NOTE:SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720