| 2006-10-06 00:00:00 | ****** UNSAT 3RD REVIEW ****** |
| | |
| | ** PLEASE SEE THERE ARE SOME NEW ITEMS |
| | FROM PREVIOUS REVIEW AND NEW COMMENTS |
| | DUE TO RISER BEING COMPLETELY REVISED |
| | FOR MAIN HOUSE ETC. |
| | PLEASE SEE NOTES BELOW ARE TAKEN FROM |
| | PREVIOUS TWO REVIEWS ALONG WITH ALL NEW |
| | NOTES ADDED TO BOTTOM OF OLD NOTES. |
| | |
| | |
| | 1) NOTE: OK, HOWEVER NOW SUBMITTING |
| | COMPLETED PLANS, HOWEVER THERE ARE MANY |
| | ITEMS NOT CODE COMPLIANT, SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW #2** |
| | NO, PLEASE SEE PANEL AT MAIN |
| | HOUSE MAY NOT BE USED CARRYING BRANCH |
| | CIRCUITS TO CABANA. PLEASE SEE MISSING |
| | PANEL, GROUNDING, DISCONNECTING MEANS |
| | ETC AS PREVIOUSLY NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE COMPLETE PLANS FOR |
| | REVIEW. PLEASE SEE NO INFORMATION WAS |
| | SUBMITTED FOR NEW REQUIRED PANEL, MEANS |
| | OF DISCONNECT, PANEL SCHEDULE, GROUNDING |
| | ETC AT THE DETACHED BLDG. |
| | PLEASE SEE 225.31-225.39, 250.32,250.50, |
| | 215.5, 240.21 ETC |
| | |
| | 2) NOTE: NO, PLEASE SEE LOAD |
| | CALCULAITONS SUBMITTED ARE NOT CODE |
| | COMPLIANT PER NEC AND PLEASE SEE NEW |
| | COMMENTS BASED ON REVISED PLANS. |
| | |
| | ** PREVIOUS REVIEW #2 NOTE ** |
| | NO, PLEASE SEE LOAD |
| | CALCULATIONS DO NOT MEET CODE PER |
| | 220.31B. PLEASE SEE PANEL SCHEDULE IS |
| | NOT COMPLETE WITH ALL INFORMATION AS |
| | REQUIRED. ONLY ONE CIRCUIT BEING SHOWN |
| | FOR ALL LTS AND GEN PURPOSE RECEPTS, |
| | MISSING ARC FAULT PROTECTION AS UPSTAIRS |
| | IS AN ADAPTBALE SLEEPING RM. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE COMPLETE AND CORRELATE |
| | ALL CIRCUITING ON PLANS WITH PANEL |
| | SCHEDULE AND COMPLETE LOAD CALCULATIONS. |
| | PLEASE SEE PLANS SHOW ITEMS WHICH ARE |
| | NOT FIGURED OR SHOWN ON PANEL |
| | SCHEDULE/LOAD CALCS. |
| | PLEASE KNOW, ALL CIRCUITS SHALL BE |
| | SPECIFIC TO ROOMS AND AREAS IN |
| | STRUCTURE. |
| | PLEASE SEE MORE THEN ONE SM APPL CIRCUIT |
| | IS INDICATE HOWEVER ONLY TWO ARE |
| | FIGURED. |
| | PLEASE SEE NO TANKLESS WH IS SHOWN ON |
| | PANEL SCHEDULE OR FIGURED IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE ONLY ONE A/C SYSTEM IS |
| | FIGURED IN LOADS. |
| | PLEASE SEE NO LOADS FROM EXISTING |
| | DWELLING IS SHOWN OR FIGURED IN WITH NEW |
| | LOADS. |
| | PLEASE LABEL ALL RMS/AREAS ON PLANS. |
| | 240.4,310.16,220.31B,408.4 |
| | FBC 106.1.2, 106.1.3 ADMIN SECT. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: NO, SOME INFORMATION SUBMITTED |
| | HOWEVER SEE NEW NOTES FOR DISCONNECTING |
| | MEANS ETC DUE TO SPECS BEING SUBMITTED. |
| | PLEASE SEE 210.63,210.70 |
| | |
| | ** PREVIOUS REVIEW #2 NOTE ** |
| | NO, NO CORRECTIONS MADE, AND |
| | ITEMS NOT SHOWN AS REQUIRED PER CODE. |
| | A NOTE WAS ADDED TO SEE LOCATIONS OF |
| | CU'S ON SURVEY, HOWEVER THE ELECTRICAL |
| | PLANS ARE REQUIRED TO CONTAIN THE |
| | ELECTRICAL INFORMATION AS REQUIRED. |
| | DISCONNECTS, RECEPTS FOR CU'S ETC, |
| | MIN CLEARENCES ETC. |
| | PLEASE SUBMIT THE SPECS/MANUFACTURES CUT |
| | SHEETS FOR THE TANKLESS WATER HEATER |
| | UNIT. PLEASE BE SURE THE SHEETS CONTAIN |
| | THE LISTING FROM A NRTL. |
| | 110.26,210.63,210.8,440.11,240.24,422.31 |
| | ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | |
| | PLEASE SEE 110.26, 240.24, |
| | 440.11, 422.31 ETCFOR MIN DISCONNECTS |
| | REQUIRED FOR AHU/ TKLESS WH. PLEASE SEE |
| | AREAS FOR MIN CLEARENCES, AND STORAGE |
| | AREAS WHERE EASILY IGNITIBLE MATERIALS |
| | AND OCP. |
| | |
| | 5) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | |
| | ** NEW NOTES 2ND REVIEW ** |
| | |
| | 6) NOTE:NO, PLEASE SEE DUE TO REPEAT |
| | COMMENTS A FEE HAS BEEN ASSESSED TO THE |
| | DESIGN TEAM AS REQUIRED PER FS |
| | 553.80(2)(B). THE AMOUNT OF $1300.24 |
| | MUST BE PAID BEFORE NEXT RESUB OF PLANS. |
| | IT IS THE SUGGESTION OF THIS OFFICE AS |
| | ONE SET OF PLANS ARE BEING RETAINED , |
| | THAT A MEETING BE HELD WITH ALL RELEVANT |
| | PARTIES TO GO OVER PLANS ETC. PLEASE |
| | KNOW, IF PLANS COME BACK FOR A FORTH |
| | REVIEW AND "ANY" OF THE SAME COMMENTS |
| | ARE NOT ADDRESSED, THE FEE IS ASSESSED |
| | ONCE MORE. PLANS MAY NOW ALL BE TURNED |
| | INTO THE STATE BOARD OF ARCHIECTS FOR |
| | REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT CODE COMPLIANT |
| | COMMENTS FOR DESIGN PROFESSIONAL. |
| | PLEASEKNOW, ONE COPY OF EACH SET OF |
| | ELECTRICAL IS BEING RETAINED. PLEASE |
| | KNOW, IT MAY BE REQUIRED BY THIS OFFICE |
| | THAT PLANS BE DONE BY AN ARCHITECT, |
| | ENGINEER OR PERSON LICENSED UNDER FS |
| | 489. |
| | |
| | 7) NOTE: OK. |
| | |
| | *********************************** |
| | THIS FYI WAS PLACED ON PREVIOUS REVIEW. |
| | |
| | ** PLEASE KNOW, DUE TO PLANS NOT BEING |
| | COMPLETE AT THIS TIME, THERE MAY BE |
| | FUTURE COMMENTS AS PLANS WILL CHANGE. |
| | |
| | ************************************ |
| | |
| | |
| | |
| | *** NEW NOTES FOR 3RD REVIEW DUE TO NEW |
| | PLANS BEING SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE RISER, PLEASE |
| | CORRELATE AS THIS RISER IS COMPLETELY |
| | DIFFERENT FROM THEMAIN HOUSE PLANS AND |
| | NOW DOES NOT MEET MANY ITEMS CODE |
| | RELATED.. |
| | |
| | A) PLEASE SEE RISER NOW SHOWS A NEW 150A |
| | PANEL "B", WHICH IS BEING FED FROM |
| | 3-#3'S WHICH ARE ONLY RATED AT 100A'S. |
| | PLEASE PREVIOUS REVISED RISER SHOWS A |
| | 125A PANEL "B" WITH A 100A MCB AND NOW |
| | SERVICE IS BEING INCREASED AND NO |
| | CONSIDERATION HAS BEEN TAKEN TO THE |
| | INCREASE FOR SERVICE ENTRANCE CONDUCTORS |
| | FOR NEW 150A MCB PANEL AND INCREASED |
| | SERVICE. |
| | |
| | B) PLEASE SEE 250.66, 310.15B6, 310.16, |
| | AS THE SEC'S TOTAL WILL NOW BE INCREASED |
| | ,T HE GROUNDING ELECTRODE CONDUCTOR WILL |
| | NOW BE REQUIRED TO MEET 250.66. THE |
| | PREVIOUS #2, IS NO LONGER LARGE ENOUGH. |
| | |
| | C) PLEASE SEE RISER SHOWS 3-3/0'S AND |
| | 1-#6 IN AN 1 1/4" CONDUIT FROM PANEL "B" |
| | TO NEW PANEL "C" (CABANAN PANEL). |
| | PLEASE SEE THE FIRST ITEM IS THAT PANEL |
| | "B" SHOWS A 2-POLE 70A BRKR FEEDING NEW |
| | PANEL "C", 3/0'S WILL NOT FIT INTO A 70A |
| | BREAKER. |
| | PLEASE SEE THE SECOND ITEM IS THAT PANEL |
| | "B" SHOWS #4'S WHICH IS COMPLETELY |
| | DIFFERENT FROM RISER WHICH SHOWS 3/0'S? |
| | THE THIRD ISSUE IS THAT 3-3/0'S AND 1-#6 |
| | WILL NOT FIT INTO 1 1/4" CONDUIT AS |
| | SHOWN ON RISER. PLEASE SEE TABLES IN |
| | CHAPTER 9. |
| | PLEASE SEE , 240.4,310.15B6,310.16, |
| | CHAPTE 9, 215.2, ETC ETC |
| | |
| | 2) NOTE; PLEASE SEE NOW THE SPECS FOR |
| | THE NEW TANKLESS WATER HEATER IS BEING |
| | SUBMITTED FOR THE FIRST TIME. PLEASE SEE |
| | THE UNIT SUBMITTED ITSELF AT 17.25KW |
| | EXCEEDS THE PROPOSED 70A FEED TO THE |
| | PANEL "C". PLEASE SEE THE LOADS ON PANEL |
| | "C" ARE NOT CORRECT AS THEY DO NOT ADD |
| | UP. |
| | THE TKLESS WH IS OVER 70A'S ALONE !!! |
| | PLEASE SEE THE * ON SPEC SHEETS WHICH |
| | EVEN STATES A MIN SERVICE FOR THIS SIZE |
| | UNIT FOR A DWELLING. THE MIN OCP FOR THE |
| | UNIT IS 80A'S, WHICH IS STATED ON SPECS. |
| | PLEASE KNOW, IF THE PANEL IS FEEDING |
| | THIS UNIT IS OUTSIDE,WITH TWO-2-POLE |
| | 40'S, THEN PLANS WOULD SHOW MORE THAN |
| | ONE DISCONNECT INSIDE FEEDING THIS UNIT. |
| | 422.11, 110.26, 422.31, 422.30 ETC. |
| | 110.3,90.7. |
| | |
| | 3) NOTE: PLEASE SEE 210.52 AS RAILING IS |
| | CONSIDERED WALL SPACE AND WALL SPACE ON |
| | 2ND FLR IS MISSING ONE RECEPT. IF THIS |
| | WAS THE ONLY ITEM IT WOULD BE REDLINED. |
| | |
| | |
| | 4) NOTE: PLEASE KNOW, IF THIS RISER HAS |
| | INDEED CHANGED THIS MUCH AS SHOWN FOR |
| | THE MAIN HOUSE SERVICE FROM THE LAST |
| | REVISION WHICH WAS SUBMITTED, PLEASE |
| | SUBMIT REVISED PLANS FOR MAIN HOUSE, AS |
| | THE WILL GREATLY AFFECT THE ELECTRICAL |
| | INSPECTIONS FOR MAIN HOUSE. |
| | |
| | |
| | 3) NOTE: PLEASE SEE PANEL"C"/ CABANA |
| | PANEL ON RISER IS BEING SHOWN AS A 100A |
| | MCB PANEL, YET THE PLANS ALSO SHOW A |
| | DISCONNECT OUTSIDE WHICH IS NOT ON |
| | RISER?? |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |